MON2 Terminal Meter Selection
Program
Terminal
Analog Output Terminals
This parameter is used to set the output function of the MON2 analog output
terminal. The available assignments for this output terminal are listed in
Table 8
on pg. 240
.
The MON2 analog output terminal produces an output voltage or current that is
proportional to the magnitude of the function assigned to this terminal.
Note:
The Expansion IO Card Option 2 option board (P/N ETB004Z)
is required to use this terminal.
See the Expansion IO Card Option 2 Instruction Manual (P/N 58686) for
additional information on the function of this terminal.
MON2 Terminal Setup Parameters
F674
— MON2 Output Function
F675
— MON2 Terminal Meter Adjustment
F691
— MON2 Voltage/Current Output Switching
F692
— MON2 Output Gradient Characteristic
F693
— MON2 Bias Adjustment Set Zero Level
Direct Access Number — F674
Parameter Type — Selection List
Factory Default — Output Frequency
Changeable During Run — Yes
MON2 Terminal Meter Adjustment
Program
Terminal
Analog Output Terminals
This parameter is used to set the gain of the MON2 output terminal and is used
in conjunction with the settings of parameter
F674
.
See parameter
F674
for additional information on this setting.
Direct Access Number — F675
Parameter Type — Numerical
Factory Default — 512
Changeable During Run — Yes
Minimum — 1
Maximum — 1280
FP Terminal Pulse Output Function
Program
Terminal
Analog Output Terminals
This parameter sets the functionality of the FP output terminal to any one of the
user-selectable functions listed in
Table 10 on pg. 242
.
As the assigned function changes in magnitude or frequency, the pulse count of
the FP output terminal pulse train changes in direct proportion to changes in the
assigned function.
Note:
The duty cycle of the output pulse train remains at 65 ±5.0 µ S.
This parameter is used in conjunction with parameter
F677
.
Direct Access Number — F676
Parameter Type — Selection List
Factory Default — Output Frequency
Changeable During Run — Yes
Pulse Output Frequency (FP)
Program
Terminal
Analog Output Terminals
This parameter scales the FP output terminal by setting the pulses-per-second
output signal of the FP terminal.
See
F676
for additional information on this parameter.
Direct Access Number — F677
Parameter Type — Numerical
Factory Default — 3.84
Changeable During Run — Yes
Minimum — 1.00
Maximum — 43.20
Units — Pulses/Second
FP
F674
F677