120
ACE-tronics G9 ASD Installation and Operation Manual
RX2 Option (AI1) Input Point 1 Frequency
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the RX2 (AI1) input terminal
when the RX2 (AI1) terminal is used as the control input while operating in the
Speed Control mode.
This parameter sets RX2 (AI1) Input Point 1 Frequency and is the frequency
that is associated with the setting of RX2 (AI1) Input Point 1 Setting (
F222
)
when operating in the Speed Control mode.
See RX2 (AI1) Input Point 1 Setting (
F222
) for additional information on this
setting.
Direct Access Number — F223
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (
F011
)
Units — Hz
RX2 Option (AI1) Input Point 2 Setting
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the RX2 (AI1) input terminal
when the RX2 (AI1) terminal is used as the control input while operating in the
Speed Control mode or the Torque Control mode.
This parameter sets the RX2 (AI1) input level that is associated with RX2
(AI1) Input Point 2 Frequency
when operating in the Speed control mode or
is associated with the RX2 (AI1) Input Point 2 Rate (
F227
) when operating in
the Torque Control mode.
This value is entered as -100% to +100% of the RX2 (AI1) input signal range.
See RX2 (AI1) Input Point 1 Setting (
F222
) for additional information on this
setting when used for Speed control.
See RX2 (AI1) Input Point 1 Rate (
F226
) for additional information on this
setting when used for Torque Control.
Direct Access Number — F224
Parameter Type — Numerical
Factory Default — +100
Changeable During Run — Yes
Minimum — -100
Maximum — +100
Units — %
RX2 Option (AI1) Input Point 2 Frequency
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the RX2 (AI1) input terminal
when the RX2 (AI1) terminal is used as the control input while operating in the
Speed Control mode.
This parameter sets RX2 (AI1) Input Point 2 Frequency and is the frequency
that is associated with the setting of RX2 (AI1) Input Point 2 Setting (
F224
)
when operating in the Speed Control mode.
See RX2 (AI1) Input Point 1 Setting (
F222
) for additional information on this
setting.
Direct Access Number — F225
Parameter Type — Numerical
Factory Default — 60.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (
F011
)
Units — Hz
F223
F225