Express Stop Decel Time
Program
Special
Accel/Decel 1 – 4
This parameter specifies the time in seconds for the output of the ASD to go
from the Maximum Frequency to 0.0 Hz during an Express Stop. When
enabled at
F493
, this setting is used as an alternate deceleration time.
The Accel/Decel Pattern may be set using
F512
.
This parameter may be further defined by the settings of
F506
–
F509
.
Note:
A deceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads. Automatic
Accel/Decel, Stall, and Ridethrough settings may lengthen the
actual deceleration times.
Direct Access Number — F511
Parameter Type — Numerical
Factory Default — 1.5
Changeable During Run — Yes
Minimum — 0.1
Maximum — 6000
Units — Seconds
Express Stop Acceleration/Deceleration Pattern
Program
Special
Accel/Decel 1 – 4
This parameter enables a user-selected preprogrammed output profile that
controls the acceleration and deceleration pattern during an Express Stop.
See
F502
for additional information on this parameter.
Settings:
Linear
S-Pattern 1
S-Pattern 2
Direct Access Number — F512
Parameter Type — Selection List
Factory Default — Linear
Changeable During Run — Yes
Acceleration/Deceleration Switching Frequency 2
Program
Special
Accel/Decel Special
This parameter sets the frequency at which the acceleration control is switched
from the Accel #2 profile to the Accel #3 profile during a multiple-acceleration
profile configuration.
Direct Access Number — F513
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (
F011
)
Units — Hz
Plugging Acceleration Time
Program
Special
Accel/Decel 1 – 4
This parameter specifies the time in seconds for the output of the ASD to go
from 0.0 Hz to the Maximum Frequency during Plugging. When enabled at
F494
, this setting is used as an alternate acceleration time.
The Plugging Acc/Dec Pattern may be selected at
F516
.
This parameter may be further defined by the settings of
F506
–
F509
.
See
F494
for additional information on the Plugging function.
Note:
An acceleration time shorter than that which the load will allow
may cause nuisance tripping and mechanical stress to loads.
Automatic Accel/Decel, Stall, and Ridethrough settings may
lengthen the actual acceleration times.
Direct Access Number — F514
Parameter Type — Numerical
Factory Default — 1.5
Changeable During Run — Yes
Minimum — 0.1
Maximum — 6000
Units — Seconds