ACE-tronics G9 ASD Installation and Operation Manual
25
Table 4. ACE G9-120V-PCB Default Assignment Terminal Names and Functions.
Terminal
Name
Input/Output
Default Function
(Also See
Terminal Descriptions on pg. 26
)
Circuit Config.
F
Discrete Input
Apply
120 VAC to
activate.
Forward
Run Command
— Multifunctional programmable discrete input.
Figure 10 on pg. 29.
R
Reverse
Run Command
— Multifunctional programmable discrete input.
I1
Input 1 — Multifunctional programmable discrete input.
I2
Input 2 — Multifunctional programmable discrete input.
I3
Input 3 — Multifunctional programmable discrete input.
I4
Input 4 — Multifunctional programmable discrete input.
I5
Stop Limit-Switch Forward — Multifunctional programmable discrete input.
I6
Stop Limit-Switch Reverse — Multifunctional programmable discrete input.
OUT1
Switched
Output
Brake Failure
— Multifunctional programmable discrete output.
Figure 16 on pg. 29.
OUT2
Brake Release
— Multifunctional programmable discrete output.
BRAKE-A
BRAKE relay (N.O.).
Figure 19 on pg. 29.
BRAKE-B
BRAKE relay (N.C.).
BRAKE-C
BRAKE relay (Common).
RR
Analog Input
Multifunctional programmable analog input. (0.0 to 10 VDC input).
Figure 11 on pg. 29.
RX
Multifunctional programmable analog input (±10 VDC input).
Figure 12 on pg. 29.
V/I
(Select V
or I via
SW2)
V
— Multifunctional programmable isolated analog voltage input (0 to 10
VDC input).
Figure 13 on pg. 29.
Frequency Mode 2
(Default Setting) —
I
—Multifunctional programmable
isolated analog current input (4 [0] to 20 mADC input — 0 Hz to Maximum
Frequency).
AM
Analog Output
Output Current
— Voltage output that is proportional to the output current of
the ASD or to the magnitude of the function assigned to this terminal (see
Table 8 on pg. 240
for assignment listing).
Figure 18 on pg. 29
FM
Output Frequency
— Current or Voltage output that is proportional to the
output frequency of the ASD or to the magnitude of the function assigned to
this terminal (see
Table 8 on pg. 240
). Select Current or Voltage at
F681
.
P24
DC Output
24 VDC output (200 mA max.).
Figure 14 on pg. 29
.
PP
10.0 VDC/10 mA voltage source for the external use (e.g., potentiometer).
Figure 15 on pg. 29.
FP
Pulsed Output
Frequency Pulse — Multifunctional programmable output pulse train of a
frequency based on the output frequency of the ASD (see
Table 8 on pg. 240
).
Figure 17 on pg. 29.
IICC
—
Return for the isolated V/I input terminal.
Do Not connect to
Earth Gnd or to each
other.
CC
—
Return for the AM, FM, RR, RX, P24, and the PP analog terminals.