Outside of each separate dwelling unit sleeping area, within 6.4 m (21 ft) of any door to a sleeping room, the distance measured along
a path of travel.
(3) On every level of a dwelling unit, including basements.
(4) On every level of a residential board and care occupancy (small facility), including basements and excluding crawl spaces and unfinished attics.
(5) In the living area(s) of a guest suite.
(6) In the living area(s) of a residential board and care occupancy (small facility).
CO Detectors. Carbon monoxide gas moves freely in the air. The human body is most vulnerable to the effects of CO gas during sleeping hours . For
maximum protection, a CO alarm should be located outside primary sleeping areas or on each level of your home.
The electronic sensor detects carbon monoxide, measures the concentration and sounds a loud alarm before a potentially harmful level is reached.
Do NOT place the CO alarm in the following areas:
• Where the temperature may drop below -10ºC or exceed 40 ºC.
• Near paint thinner fumes.
• Within 5 feet (1.5 meters) of open flame appliances such as furnaces, stoves and fireplaces.
• In exhaust streams from gas engines, vents, flues or chimneys.
• In close proximity to an automobile exhaust pipe; this will damage the detector.
Progate. Begin the installation by mounting additional modules in the cabinet using the stand-offs provided, then mount the cabinet in a dry, protected
area with access to un switched AC power. Install hardware in the sequence indicated in the following pages. Do NOT apply power until installation is
complete.
4.2.12.2 [4-Wire] Smoke detector Wiring
Connect the 4-wire smoke detectors and a relay as shown in the figure below. Install the 4-wire smoke detectors with 18 gauge wire. If power is
interrupted, the relay causes the control panel to transmit the Fire Loop Trouble report. To reset (unlatch), connect the smo
ke detector’s negative (-) to a
PGM.
If you want to edit existing configuration, You have to read
it (press “Read” in the command line)
Edit settings,
Write edited configuration (press “Write” in the command line)
The parameters of the zone should be defined as a “Fire Zone”.
If a line short occurs or the smoke detector activates, whether the system is
armed or disarmed, the control panel will generate an alarm. If the line is open, the “Zone Fault” report code is sent to the monitoring station or to the user,
if programmed.
Figure 53 4-Wire Smoke Detector Installation