Texecom PREMIER 168 Скачать руководство пользователя страница 20

Installation 

 Premier Elite Series Installation Manual 

20 

 INS176-15 

 Connecting Devices to the Network 

Before  connecting  keypads,  zone  expanders  and  output  modules, 

isolate  ALL  power  from  the  control  panel  (AC  Mains  &  Battery).  Do 

not continue if there is still power present on the control panel. 

 

Connecting  devices  with  power  still  present  on  the  control 

panel may damage the device or control panel and invalidate 

any warranty. 

Keypads, zone expanders and output modules are all connected to the 

same  network  terminals  located  at  the  bottom  left  hand  corner  of  the 

control  panel  and  may  be  connected  serially  (daisy  chain),  in  parallel 

(star) or any combination of the two (see Figure 1, page 22 for details). 

 

No more than 8 zone expanders, 8 keypads and 4 output modules 

can be connected to each network.  

The maximum number of devices that can be connected in total 

will depend on the control panel fitted. 

Whenever new devices are connected to the networks, they must be 

confirmed onto the system using the ‘Confirm Devices’ menu option 

(see page 133 for details). 

Wiring the Network 

The networks are made up of four terminals incorporating power and 

data.  To  ensure  correct  operation,  all  four  terminals  on  the  device 

must  be  connected  to  the  corresponding  terminals  on  the  control 

panel,  or  previous  device  (see  Figure  1,  page  22  for  details).  The 

table below shows each terminal and its description: 

Terminal 

Description 

+12V Supply 

0V Supply 

Transmit Data 

Receive Data 

Devices can be connected using 4-core cable. However, it is recommended 

that 6 or 8-

core cable is used as the spare cores can be used to ‘Double Up’ 

on the power connections if needed. 

Stranded tinned annealed copper BS4737 7/0.2 alarm cable can 

be used for most installations. However, under certain conditions 

it may be necessary to use screened cable of the same 

specification. 

PLEASE NOTE. The conductor resistance should be no greater 

than 8

 per 100metres. 

The usage of Low grade TCCA (tinned copper clad cable) can 

have a detrimental effect on the operation of the system and the 

cable distances specified in this manual. 

 

Cable Distances 

The  maximum  recommended  distance  for  devices  when  using 

standard 7/0.2 alarm cable is: 

 

250m  for  each  branch  when  using  the  star  (parallel) 

configuration 

 

When  using  a  daisy  chain  (series)  configuration  the  maximum 

distance  will  depend  on  the  number  of  devices  connected  on 

the chain. The more devices that are connected, the shorter the 

distance  to  the  last  device  (this  is  due  to  voltage  drop  in  the 

cable) 

Whichever  method  of  wiring  configuration  is  used,  ensure  that  the 

voltage between the ‘+’ and ‘–’ terminals at each device is no lower 

than 10.0V when the system is running on the standby battery. 

The  table  below  shows  maximum  cable  runs  when  one  keypad  or 

expander  is  installed  using  standard  7/0.2  alarm  cable  with  various 

loads: 

Configuration 

Max. Cable Run 

1. 

Keypad  + 2 PIR’s @15mA

 

250m 

2. 

Ex 2 PIR’s @15mA

 

250m 

3.

 

Ex 8 PIR’s @15mA

 

100m 

4.

 As No. 3 + 16

 Speaker  

30m 

Distances of up to 1km can be achieved between the control panel and 

a  device.  However,  a  power  supply  must  be  installed  close  to  the 

device  to  power  it  locally,  this  will  help  to  overcome  voltage  drop 

caused by the long cable run. 

Overcoming Voltage Drop 

There are several ways to overcome voltage drop: 

 

Use thicker lower resistance cable. Standard 7/0.2 alarm cable 
has a resistance of 8

 per 100m 

 

Double up on the power connections 

 this will require using a 6 

or 8-core cable rather than a 4-core cable 

 

Install a power supply to power the device locally, remember to 

common the two negative connections 

Installing a Power Supply 

When a power supply is installed, the 0V connections on the power 

supply  must  be  connected  through  to  0V  on  the  control  panel  and 

the +12V connection between the control panel and the device must 

be disconnected (see Figure 2, page 22 for details). 

Use of pull up resistors 

In certain circumstances it may be necessary to use pull up resistors. Constant network errors, devices dropping of off networks, or the use of poor 

quality cable can all be helped by utilising resistors to "pull" the network up. making sure that errors in data flow are minimised. The diagram below 

details the type and placement of the resistors. 

 

 

+

-

T

R

N

E

TW

O

R

K

 O

U

T

Control Panel

Network 1 or 2

+ -

T R

NETWORK OUT

Keypad or

Expander

+ -

T R

NETWORK OUT

Keypad or

Expander

+ -

T R

NETWORK OUT

Keypad or

Expander

Connect 1K resistor 

between  R  and  +  at 

the Control Panel

1

K

1

K

Connect 1K resistor 

between  T  and  +  at 

the furthest network 

device

Содержание PREMIER 168

Страница 1: ...INS176 15 Premier Elite Series Installation Manual ...

Страница 2: ...ll be sent in the Text Message 41 AV Module 42 ComIP Module 42 Commissioning 43 ComWiFi 43 USB Com 47 PC Com 47 Connecting a Computer 47 Connecting a Printer 47 4 Commissioning and Troubleshooting 48 Commissioning 48 Trouble Shooting 48 Reset and Service Messages 50 5 Programming the Control Panel 51 Introduction 51 Copying and Pasting 53 Log Off Engineer 53 Resetting the Engineers Code User 00 53...

Страница 3: ...9 Optional Additional Panel Settings 109 Defaulting the Com WiFi 110 Changing the ComWiFi Language 110 DualCom Inside 48 Only 111 EMIZON 21 TCD 112 WebWayOne 113 Chiron IRIS 115 Zone Alarm Reporting Codes 116 5 8 Setup Users 123 Default User Codes 124 Programming New Users 124 User Types 124 User Functions and Options 125 User Options 1 126 User Options 2 126 User Config 126 User Time Lock 126 Use...

Страница 4: ...Ne two rk No Ad d re ss Zo n e s 0 Expanders Elite 12 2 Expanders Elite 24 4 Expanders Elite 48 8 Expanders Elite 64 88 16 Expanders Elite 168 64 Expanders Elite 640 Premier XP Elite 32 W Power Ne two rk No Ad d re ss Zo n e s 0 Expanders Elite 12 1 Expanders Elite 24 1 Expanders Elite 48 2 Expanders Elite 64 88 4 Expanders Elite 168 16 Expanders Elite 640 Mobile APP Server Push Notifications Arm ...

Страница 5: ...250 500 Event Mandatory Log 3 8 programmable digicom outputs 100mA each 32 character zone text Facility for Plug on Digimodem Com300 2400 Facility for Plug on IP Module ComIP Chiron WebWayOne Emizon Facility for a plug on RedCARE RM8 Relay Module Not Premier 12 W 24 24 W 48 64 W PC Com printer port Remote Keypads LCD 32 character text display 2 fully programmable DP or EOL zones 1 fully programmab...

Страница 6: ...use with ADSL DSL Broadband WAN LAN etc ComWiFi Multi protocol communicator supporting Fast Format Contact ID and SIA Level II protocols via TCP IP High speed modem for remote uploading and downloading using the Wintex UDL software and a PC LAN WAN connection to Texecom mobile apps For use with ADSL DSL Broadband WAN LAN etc ComGSM Provides a GSM telephone path for Com300 Com2400 Digital Communica...

Страница 7: ...attery Kick start button is pressed Connect the AC mains 8 Keypad messages The keypad may show a mix of faults following first power up and go into alarm If the system goes into alarm enter the default Engineer code and the alarm tone will stop To access the Engineer Programming Menu enter the default Engineer code 9 Select Language Country Code Immediately following power up you will be prompted ...

Страница 8: ...12 W 24 W 48 64 W Control Panel Layout 48 64 W Shown Tamp Strb 0V Bell 12V Op1 Aux 12V Spk Bell Aux 12V Network F4 F3 F1 F6 Engineer Remote Com2 Com1 Load Defaults Tx Rx Aux Fault Bell 12V Enable Network 2 Wire Smoke Enable Expansion Batt Charge 0 75A 0 3A Kick Start F2 Batt DC F8 F9 USE WITH TEXECOM PSU ONLY Audio Com 1 Audio ...

Страница 9: ...trol Panel Layout Metal All Models 168 shown Com 2 F1 F5 JP7 Aux 12v 1Amp Network 2 1Amp Com 1 Heartbeat Load Defaults Expansion F3 Network 1 1Amp Kick Start Tx1 Rx1 Tx2 Rx2 Box Tamp 100mV 1Amp V F6 F2 F8 F7 F9 USE WITH TEXECOM PSU ONLY F4 Eng Keypad Bell Strb 1Amp JP10 ...

Страница 10: ...el Output 1 OP1 is a low current 500mA ve applied output see page 35 for wiring details The output is also fully programmable see page 84 for programming details 9 SPK Loudspeaker Connection These terminals can be used for connecting up to one 16 or two 8 loudspeakers see page 34 for wiring details 10 Auxiliary 12V Power These terminals are for connecting devices that require 12V power protected b...

Страница 11: ... Port can be used for connecting a 60XiD Zone Expander see page 33 for details or an AV Module see page 42 for details X 10 Module Obsolete Speech Module or a Memory Module 23 Heartbeat LED Power Light Flashes steadily to indicate that the control panel is functioning correctly If the light is ON or OFF all the time then there could be a problem see page 48 for details 24 Battery Charge Current Se...

Страница 12: ...es that require 12V power protected by a 0 9A PTC fuse 9 Expansion The Expansion Port can be used for connecting a 60XiD Zone Expander see page 33 for details or an AV Module see page 42 for details X 10 Module Obsolete Speech Module or a Memory Module 10 External Sounder Connections These terminals are used for connecting to an external sounder unit 11 Load Defaults Button Press and hold this but...

Страница 13: ...ng to a PC via PC Com USB Com or Com IP for use with Ricochet Monitor Software 26 Cover Tamper Provides tamper protection for the control panel 27 Heartbeat LED Power Light Flashes steadily to indicate that the control panel is functioning correctly If the light is ON or OFF all the time then there could be a problem 28 Cover Tamper Disable Disables the lid tamper 29 Flash Programming Port For upg...

Страница 14: ... These terminals are used for connecting to an external sounder unit see page 34 for details 10 Auxiliary Fault Connections These terminals can be used for monitoring the tamper loop of an auxiliary device see page 34 for details 11 Loudspeaker Connections These terminals can be used for connecting up to one 16 or two 8 loudspeakers see page 34 for details 12 Panel Outputs Outputs 1 2 are 500mA ve...

Страница 15: ...r 7 seconds with power already on the panel to restore just the Engineer code to the factory setting of 1234 See page 53 for full details Loading the factory defaults can take up to 30 seconds to complete Loading defaults will only be possible if the NVM has not been locked see page 71 for details 21 Expansion The Expansion Port can be used for connecting a 60XiD Zone Expander see page 33 for deta...

Страница 16: ...e used for connecting up to one 16Ω or two 8Ω loudspeakers see page 34 for details 10 Auxiliary 12V Power These terminals are for connecting devices that require 12V power protected by a 1A fuse 11 Panel Outputs Outputs 1 2 are 500mA ve applied outputs 3 4 are 500mA ve applied and output 5 is a clean contact relay see page 35 for wiring details These outputs are all fully programmable see page 83 ...

Страница 17: ...tory setting of 1234 See page 53 for full details Loading the factory defaults can take up to 60 seconds to complete Loading defaults will only be possible if the NVM has not been locked see page 71 for details 21 Heartbeat LED Power Light Flashes steadily to indicate that the control panel is functioning correctly If the light is ON or OFF all the time then there could be a problem see page 48 fo...

Страница 18: ...by Period 12 Hrs 12 Hrs Maximum Recharge Time 72 Hrs 72 Hrs Premier Elite 48 88 168 Current Current Consumption 125mA Maximum Current Available 0 75A charge 1 0A 0 3A charge 1 9A Rated Output Battery Arrangement Battery Charge Rated Output Amps 12h 24h 30h 60h 1 x 7Ah 0 3A 0 458A 0 166A 0 108A 1 x 17Ah 0 3A 1 29A 0 583A 0 441A 0 158A 0 75A 1 0A 0 583A 0 441A 0 1588A Standby and Recharge Times EN50...

Страница 19: ...d inside the control panel to provide continued operation in the event of an AC mains failure otherwise two 12V 7Ah batteries can be connected All other wiring MUST be carried out before the battery is connected to the control panel Connect the red battery lead to the positive terminal of the battery and then connect the black battery lead to the negative terminal The panel will only become live w...

Страница 20: ... when using standard 7 0 2 alarm cable is 250m for each branch when using the star parallel configuration When using a daisy chain series configuration the maximum distance will depend on the number of devices connected on the chain The more devices that are connected the shorter the distance to the last device this is due to voltage drop in the cable Whichever method of wiring configuration is us...

Страница 21: ...ulses from Panel No connection LED B N A Data pulses from devices on Network Out Network Out not Connected LED C Expander Online Flashes address number when in Engineering all expanders flash as one until first connected No power 8 32XP w On Flashing Off RX Normal Operation Fault No connection on T wire TX Fault Normal Operation No connection on T wire Incorrectly addressed RKP On Off RX Normal Op...

Страница 22: ...Installation Premier Elite Series Installation Manual 22 INS176 15 Figure 1 Network Connections 250m without additional power supply Figure 2 Network Connections 1km with additional power supply ...

Страница 23: ...nmapped Unmapped 8 Unmapped Unmapped Address Zones Network 3 4 5 Zones Network 6 7 8 1 8 Unmapped Unmapped The zones inside the keypads are not seen by the system until they have been mapped to a zone number see page 80 for details 88 168 only 640 only Keypad Output The remote keypad has one programmable output which can be used to drive auxiliary devices such as LED s sounders or relays etc Wire ...

Страница 24: ...32XP W take 4 address slots on the network Premier Elite 8XP W take one address To enable all of the advanced functionality and diagnostics capability V2 the following are minimum requirements Wintex Version 6 2 or later Ricochet Monitor 0 2 18 or later Premier Elite Series V2 xx or later Premier Elite 32XP W 8 W Expanders V2 xx or later System Design Considerations To ensure correct setup and ope...

Страница 25: ...N Legacy Mode OFF Ricochet Switch 3 ON Impaq Contact W Wired Input 2 will report as Tamper default OFF input 2 will report as an Alarm Switch 4 Walk test 12 Address Switch Used to assign the address of the receiver on the premier network 13 RF LED Flashes when transmitting or receiving RF data 14 Tamper Disable Disables the lid and rear tamper 15 Engineer s Keypad LED s Red LED flashes constantly ...

Страница 26: ...expander into place ensuring that all four pillars clip into the four locating holes on the local expander Zone Numbering The table below shows the zone allocation when the expanders are installed Configuration Panel Zones Expander Zones 8XE Zones 1 to 8 9 to 16 8XE Tampers 1 to 8 Tampers 1 to 8 Expander Zones The expander has eight programmable zones see page 32 for wiring details Each zone is al...

Страница 27: ...d 100m between devices When the jumper is set to the DAISY position the network data signals are boosted between the expander and the previous device This mode will allow expanders on the network to be connected up to 250m apart and MUST only be selected if the expander has one device connected to the network IN connections Star wiring example Daisy chain wiring example Combined Wiring example Zon...

Страница 28: ...dressed as a keypad and will occupy a keypad slot on the network The unit must have a unique address which must not conflict with keypad or any other iProx Module on the same network The following table shows the addressing Address DIL 1 DIL 2 DIL 3 DIL 4 1 On or off Off Off Off 2 4 3 1 2 Off On Off Off 2 4 3 1 3 Off Off On Off 2 4 3 1 4 Off Off Off On 2 4 3 1 5 On Off Off On 2 4 3 1 6 Off On Off ...

Страница 29: ...mper Output The tamper switch on the output module is connected to the tamper output at the top of the module If monitoring of the lid tamper is required this output must be connected to a suitable input on the control panel or zone expander RM8 Relay Module The Premier Elite RM8 Relay Module is compatible with any control panels that have a plug on RedCARE Dualcom footprint Features 8 relay outpu...

Страница 30: ...Unmapped 5 Unmapped Unmapped Unmapped Unmapped Unmapped Unmapped Unmapped Unmapped 6 Unmapped Unmapped Unmapped Unmapped Unmapped Unmapped Unmapped Unmapped 7 Unmapped Unmapped Unmapped Unmapped Unmapped Unmapped Unmapped Unmapped 8 Unmapped Unmapped Unmapped Unmapped Unmapped Unmapped Unmapped Unmapped Expander OP16 Outputs Address Outputs Network 1 Outputs Network 2 Outputs Network 3 Outputs Net...

Страница 31: ...mapped Unmapped Unmapped Unmapped Unmapped Unmapped Unmapped 4 Unmapped Unmapped Unmapped Unmapped Unmapped Unmapped Unmapped Unmapped 5 Unmapped Unmapped Unmapped Unmapped Unmapped Unmapped Unmapped Unmapped 6 Unmapped Unmapped Unmapped Unmapped Unmapped Unmapped Unmapped Unmapped 7 Unmapped Unmapped Unmapped Unmapped Unmapped Unmapped Unmapped Unmapped 8 Unmapped Unmapped Unmapped Unmapped Unmap...

Страница 32: ...g 4 Wires Zone wiring should be programmed as Double Pole EOL see Zone Wiring page 60 When using this configuration no more than 10 detectors can be connected to each zone Triple End Of Line TEOL Use this wiring configuration when connecting PIR devices with that require Anti Mask and Fault detection Several zone wiring programming options are available for this Triple EOL is illustrated below See...

Страница 33: ... table shows the maximum number of biscuits that can be connected at the end of a single cable run using standard 4 core alarm cable Cable Length Maximum Number of Biscuits 100m 30 200m 15 400m 7 800m 3 If a different type of cable is used the distances should be re calculated e g if 7 0 4mm cable is used a single run of 200m would support 30 devices on the end as the resistance of the cable is ha...

Страница 34: ...nd is rated at 500mA Normally connected to strobe ve on the sounder where applicable connect the strobe ve to 12V For EN50131 INCERT installations the Bell Aux Tamper must be wired to a zone Grade 2 Installation Grade 3 Installation The Aux Fault relay should be programmed as Fault Grade 3 Installation Using a Zone Aux Fault Wire the Sounder Tamper Relay to these terminals Zone Wire the Sounder Fa...

Страница 35: ...e page 84 for details The table below shows the electrical characteristics for each output Terminal Max Current Operation 1 100mA Switched 0V 2 100mA Switched 0V 3 100mA Switched 0V 4 100mA Switched 0V 5 100mA Switched 0V 6 100mA Switched 0V 7 100mA Switched 0V 8 100mA Switched 0V L M N A 12V applied Line Fault R R N A 0V applied to reset DC N A 12V Power unfused DC N A 0V Power Control Panel Line...

Страница 36: ...a remote power supply that has a voltage free output for the following three conditions AC Mains Fail Battery Fail 12V Fail and Tamper When the Auxiliary Input is programmed as PSU Monitor the system will respond as follows Tamper 12V Fail Battery Fail A C Fail Resistance Response Closed Closed Closed Closed 0R No Faults Closed Closed Closed Open 2K2 AC Fail Closed Closed Open Closed 4K7 Battery F...

Страница 37: ...p press down gently until the pillars snap into the holes 12 W 24 W 48 64 W Connection Carefully lift the control panel PCB and fix the COM unit into the space provided with the connection lead attached The red lead should be positioned on the uppermost pin of the COM unit The control panel end of the connector should be attached with the red lead on the left most pin of the digi modem connector S...

Страница 38: ...er Elite Speech Module it will not function with a COM300 Only the first four Digi Channels are used by the Premier Elite Speech Module The Premier Elite Speech Module is supported by the following Texecom control panels Premier Elite all models factory built V3 and later fitted with a DTMF decoder It is not possible to enable earlier versions of control panel to function with the Premier Elite Sp...

Страница 39: ...ed from the internet For Premier Elite ComGSM this means they can be used for both alarm reporting and upload download via IP GPRS If a data number is also available it is possible to use upload download via the data number GSM instead of the IP address SIM cards can have two different phone numbers Voice Number used for voice calls and SMS Data Number used for GSM data calls Upload Download Eithe...

Страница 40: ...thod cannot provide information on the availability signal strength and interference status of all radio Base Stations in the surrounding area The signal strength reading is indicated on the Com GSM unit by use of LED s and can also be read from the keypad in the Setup Modules menu of UDL Digi Options When you have identified the point of the strongest signal make a note of this point and use it w...

Страница 41: ...p off outputs s 5678 op off 4s turn PC output 4 off and report back status Pulse Outputs On op on outputs p 5678 op on p pulse PC output 2 on Pulse Outputs Off op off outputs p 5678 op off p pulse PC output 2 off Send Message mess message 5678 mess How Are You Displays How Are You on all keypads System Status status 5678 status Armed 1 8 or A P Alarm 1 8 or A P Output 1 8 Mains OK or Fault Battery...

Страница 42: ...m an IT professional before attempting to install the module The ComIP module is designed to be fitted inside the control panel and is powered via the harness connection A suitable network cable should be fed into the control panel to allow connection the module PCB Layout 5 way harness connection to control panel ComIP Status LEDs Network status LED Left RJ45 network Connection Network status LED...

Страница 43: ...are assigned for the host section The default mask is 255 255 255 0 8 bits ComWiFi The ComWiFi module allows the Premier Premier Elite control panels to be connected to either a Local Area Network LAN or Wide Area Network WAN The internet is considered to be a WAN Once the control panel is connected to a network the following functions can be achieved Control the alarm system using the Texecom mob...

Страница 44: ...tion of the ComWiFi and you will be advised to return the unit to factory settings Initial Module Setup These steps MUST be carried out FIRST Connect the ComWiFi onto the comport of the control panel using the lead provided Using a Wi Fi enabled computer tablet or mobile device scan for new wireless networks Select the Com WiFi network Enter the network key password texecom2015 and press connect O...

Страница 45: ... so that they can use WiFi or hardwired connections to access the Internet and other resources on the network IP addresses will be assigned from a pool for a lease time and can change from device day to day for example when you leave your home and lose WiFi connection there is no guarantee when you return that you will be given the same address it may be in use by something else If you allow the w...

Страница 46: ...ollow the instructions to automatically assign and IP address and then disable DHCP and overtype the IP address with the one you have chosen that is outside the DHCP pool In the web browser on a PC on the same network you should now be able to connect to the ComWiFi with the new IP address you have given it This will prove the settings have been accepted Port Forwarding WARNING Care should be take...

Страница 47: ...gs onto a Com port on the control panel PC Com The PC Com has two connectors The 9 way D type connector is for connection to a serial port on a computer and the Molex connector plugs onto a Com port on the control panel Connecting a Computer The 12 24 48 88 168 640 all support local uploading and downloading between the control panel and a PC running Wintex UDL software Uploading and Downloading c...

Страница 48: ...nal Test the internal sounder external sounder and strobe as described on page 131 Replace the lid and secure with the lid screw supplied Press 0 followed by YES to leave the programming menu the system will return to normal The display will be showing that there is a Mains Power Off condition Switch on the AC mains supply to the control panel The normal banner message if programmed will now be di...

Страница 49: ...rectly see page 91 for details Check that the account numbers are programmed correctly see page 91 for details Check that the dial attempts are not programmed as zero see page 91 for details Check that the reporting areas have been programmed correctly see page 78 for details Check that the reporting options have been programmed correctly see page 78 for details Communicator dials but does not com...

Страница 50: ...hen the system is not fully armed The alarm engineer has logged into the programming menu and is working on site this message will clear when the engineer logs off or the system is armed ains o e e a There has been an AC Mains failure a h a l e a There is a fault with the ATS Alarm Transmission System o a h aila le e a There are no ATS Alarm Transmission System paths available o a e y e a The Stan...

Страница 51: ...nu but still remain Logged onto the system zones and tampers still disabled press R and the display will show Alarm Engineer Working On Site To log the Engineer off the system press 0 followed by YES and the system will revert to its normal condition The table below shows the menu options available Key Menu Option Page 1 Zone Setup 54 2 Area Programming 61 3 Global Options 69 4 Keypad Setup 79 5 E...

Страница 52: ...Type not always available y User Options not always available y User Config y User Time Lock y User Text not always available y Door Control y Add TAG Enable Texecom Connect will only appear if an ARC is programmed with the Connect Protocol The menu numbers following will increment by one step So Digi Options becomes 5 and so on Key Main Menu Key Sub Menu 9 Engineer Utils 0 View Event Log 1 Do Bel...

Страница 53: ...ng an item can only be pasted into an item of the same type and cannot be used once another option is selected i e Zone programming information cannot be pasted into Timers etc Log Off Engineer Whenever the Engineer Programming menu is exited by pressing R twice the display will look like this la Enginee o ing on i e 37 3 e This message will remain on the display until the Engineer logs out of the...

Страница 54: ... 4 anel 4 En y E i Zone 4 anel 4 a d I E E E I Zone 4 eas I Zone anel En y E i Zone 4 anel 4 En y E i Zone 4 eas E E I E Zone 4 hi e ilen Zone 4 hi e hi e Zone 4 i U E K K U E U E Zone 4 es e o e es n Zone 4 es e o e es y y R y R R n 3 n n y y n n y y n 2 y R y Zone eas Zone eas E H n A A A C P Zone eas IJK n 7 y y R n y R y n y y ...

Страница 55: ...n go to the menu as in Fig 1 press R and then n if a device is already learnt the display will look like Fig 2 if not then it will look like Fig 3 Zone ea n ee Fig 3 Deleting Devices To delete devices from the expander is the same as learning them choose the zone you wish to delete and follow the procedure to learn the device when the screen shows Learning press R Learning Devices Zone anel o Used...

Страница 56: ...least 15 minutes and the test all devices Access the Learn Menu using the Omit Hot key From any top level engineering menu pressing the key will take you to the Ricochet learn menu above IMPORTANT In all cases when entering the Learn menu the next available free Zone will be chosen to learn a device too It will not be possible to learn a device to a Zone that already has a device learned too it Th...

Страница 57: ... the system area is disarmed and will cause an Intruder alarm when the system area is armed The panel will also report a 24 Hour Alarm to the Alarm Receiving Centre when using Contact ID reporting 7 PA Audible Normally used for monitoring Panic or hold up alarms This zone type will cause a Panic alarm if it is activated when the system area is armed or disarmed 8 PA Silent Normally used for monito...

Страница 58: ...e duration of the Forced Entry timer Zones without this attribute will respond as normal Zone Attributes 2 Select attributes by pressing keys 1 to 8 a letter on the display means the attribute is selected a Dot on the display means the attribute is not selected The following attributes are available D DOUBLE KNOCK Zones with this attribute will only cause an alarm if it is activated twice within t...

Страница 59: ... Custom zone with this attribute will activate both the internal and external sounders even if they are not enabled above W WARNING REQ If the zone remains Active for the duration of the Warning Delay timer see page 70 a warning tone will occur every 30 seconds for 3 minutes or until a code is entered or R is pressed If MONITOR 24Hr is enabled an internal alarm will occur after the Warning Delay C...

Страница 60: ...s devices will operate on the system This option only appears in the menu after a device has been learned to the zone and replaces the wiring type options Always Awake o This mode should only be used on devices which are required to signal at all times and is the default setting for Contacts Shock sensors Hybrid o Hybrid mode is used to control the reporting functions for devices When in the mode ...

Страница 61: ...ne will be heard If the area is not disarmed before this timer expires the 2nd Entry Delay timer will start 4 2nd Entry Dly When the area Entry Delay 1 or 2 timer expires this timer will start and an Internal alarm will occur If the area is still not disarmed before this timer expires an Intruder alarm will then occur 5 Bell Delay This timer controls the delay between an Intruder alarm occurring i...

Страница 62: ... 2 The 24 has 2 Area Arm Suites the 48 64 has 4 Area Arm Suites the 88 has 8 Area Arm Suites the 168 has 16 Area Arm Suites Any number of areas can be assigned to each suite Areas assigned to an Area Arm Suite will be armed when the suite is selected making it easier for the user to select multiple areas if required Example Area Arm Suites could be useful in a domestic situation where the user wan...

Страница 63: ...uite 2 Keypad 3 Area Arm Suite 3 etc When a User code is entered at a keypad one of the Area Arm Suites is selected depending on which keypad was used and the areas contained within that suite arm using the arming mode for that suite the keypad sounder will also follow the areas defined by the suite Area Suite Text E o elec ea og a ing ea og a ing ea i e e ea og a ing i e s UI E i e ea UI E Edi e ...

Страница 64: ...sed and the Exit Settle timer has expired 3 Timed Exit Default for All Areas The suite will arm after the programmed Exit Time has expired If an Exit Terminator zone is activated at any point during the exit mode any remaining exit time is cancelled and the area will arm immediately 4 Instant The suite will arm instantly 5 Deferred The suite will arm after the programmed Exit Time has expired Howe...

Страница 65: ...eset following a Confirmed alarm Areas Assigned to Confirmed Reset will respond as follows The assigned areas can only be reset using an Engineer code If Anti code Reset is enabled option 13 the assigned areas can also be reset using the Anti code Areas not assigned to Confirmed Reset can only be reset with any User code that is valid for those areas providing that Alarms Eng Reset option 13 is al...

Страница 66: ...are omitted for that area are logged in the event log Areas not assigned to Log Part Omit will never log the zones that are omitted in the event log when the area is part armed 25 Multi Knock Area Areas assigned to Multi Knock Area will respond as follows Zones with the Double Knock attribute will use the multiple knock value set up in system options for zone activations see page 74 for details Ar...

Страница 67: ...t Each area can be programmed for Engineer or User reset following any Fault Areas Assigned to Faults Eng Reset will respond as follows The assigned areas can only be reset using an Engineer code If Anti code Reset is enabled option 13 the assigned areas can also be reset using the Anti code Areas not assigned to Faults Eng Reset can be reset with any User code that is valid for those areas 36 No ...

Страница 68: ...s 8 independent control timers for each of the 4 Area groups These may be configured to switch on and off at different points of the day and operate on different days of the week see page 75 for programming details Area Text E o elec ea og a ing ea og a ing ea e ea og a ing i e s e o ea Edi e e o ea ecep ion Edi e y 7 y 4 y n Text may be assigned to each of the areas on the system This allows the ...

Страница 69: ...tor in that area is activated the timer is restarted If the timer is allowed to expire i e no detectors in the assigned area are activated the area will arm itself 10 Menu Time Out This timer controls the length of time that a user can remain in a menu before the system automatically returns to the normal day mode 11 Pulse Period 1 This timer controls how long any output with the Pulse Period 1 at...

Страница 70: ... a second different PA zone is activated within this time window the Confirmed PA output will activate When this timer expires the Confirmed PA output will no longer activate 35 Seismic Timer 1 36 Seismic Timer 2 37 Seismic Timer 3 Reserved for future use System Config E o elec lo al p ions lo al p ions ys e i e s lo al p ions ys e on ig on ig a ion o ell e ail on ig a ion is Unloc ed on ig a ion ...

Страница 71: ...indow the area that the zone is assigned to can still be armed However this fault will be indicated to the user when they try to arm the area View Act Fault If a zone with the Activity attribute is not activated during the Activity Delay time window the area that the zone is assigned to cannot be armed This situation can only be overcome by activating the zone 15 Hide Exit Errors If a user tries t...

Страница 72: ... second 34 EN50131 Enabled Keypad display blanking is enabled i e the keypad will only display the time date and the banner message If information is available to be viewed i e AC Mains Fail Line Fault System Faults etc the keypad will bleep every 30 seconds and display System Alerts this information can only be viewed after a valid user code has been entered The keypad display will then blank aga...

Страница 73: ...e hold up timer is started See Global System Timers for Confirmed PA Timer the confirmed alarm will generate if one of the following happens another PA Zone activated or a tamper from a device multi action PA or a global tamper within the timer period No Conf Hold Up No confirmed hold up will be generated 51 Max Log msgs 3 Log events from individual sources are limited to 3 No Max Log msgs Log eve...

Страница 74: ...o correction 100 50 6 Quick Count Set the number of 10milli Second pulses that are required within 30 Seconds in order for a zone with the Quick Response attribute to activate 7 Modem Level When using a Com2400 this option allows adjustment to the attenuation of the modem Modem Level 2 1 0 7 6 5 4 3 Attenuation dB 4 2 0 2 4 6 8 10 8 Language Selection Various languages are available for the contro...

Страница 75: ...r faults L Panel Lid Tamper The control panel lid tamper is monitored for faults B Battery Faults The battery is monitored for faults Control Timers E o elec lo al p ions lo al p ions ys e i e s on ol i e a is n a 3 lo al p ions on ol i e s on ol i e a is n a 3 on ol i e a is n a i e a n ays i e a n ays on ol i e a is a i e a ays i e a ays on ol i e a is a 34 y 4 y y 1 y y 1 y The 48 has 4 control...

Страница 76: ...ully armed 6 Part Arm Banner This 16 character message is displayed above the time and date whenever the control panel is part armed 7 Printer Header This 16 character header will be printed whenever a log printout is taken from the control panel or a Short Message Service SMS text message is sent to a mobile phone Part Arm Text E o elec lo al p ions lo al p ions ay e E ening e o ay Edi e ed i e E...

Страница 77: ...lo al p ions lo al p ions ys e i e s lo al p ions pea e ones pea e ones E En y ones E i e ones E En y ones y 8 y n n y The speaker output on the control panel can be programmed so that certain types of tones are not generated When deselected Fire Alarms Fault Service Entry Exit and Chime tones will not be heard Select tones by pressing keys 1 to 8 a letter on the display means the tone is selected...

Страница 78: ...ding key the appropriate number of times to select a character on the same key press to move the cursor along Custom O P Text E o elec lo al p ions lo al p ions s o e s o e Edi e o s c i e Edi e lo al p ions ys e i e s s o 3 e y 9 y 3 n y Text may be assigned to Custom Outputs 1 to 4 to allow indication on the keypads display when the output is active see page 89 for details Outputs 1 2 are silent...

Страница 79: ...K 3 p ions K eas K 3 apping Z Z K 3 eas K 3 eas K 3 eas K 3 apping Z Z K 3 apping Z Z K 3 apping Z Z isa led is ilen K 3 ol e e el 4 K 3 ol e e el 4 K 3 ol e e el K 3 E o nds En y ones E i e ones E En y ones is ilen y R y n 2 y n y y n y n y R y n y R n n y R y K 3 eas K 3 eas E H n A A A C P K 3 eas IJK ...

Страница 80: ...pressed the Keypad PA Delay timer starts if a User code is entered before the timer expires no PA alarm will occur If a User code is not entered before the timer expires a PA alarm will occur see page 69 for details Q Quick Arm is Enabled Pressing the Area or Part keys will Arm or Part Arm the areas that the keypad is assigned to without the need to enter a User code first O Info LED Output The In...

Страница 81: ...lec E pande e p Edi e In ecep ion Edi e E p eas E p I o Used E p eas E p eas E p eas E p I ilia y a pe E p ol e ol e 4 E p e E p ol e ol e E p I o Used E p ol e ol e 4 E p E o nds En y ones E i e ones E En y ones y 3 n n R y R y R y R y y n n n 2 y y y y n E eas E eas E H n A A A C P E eas IJK ...

Страница 82: ... to silence the Internal sounders following an Intruder alarm and would be used in conjunction with Audio Verification units apply 0V to silence Global Omit Key Normally wired to a key switch When the key switch is activated all zones with the Omit attribute assigned to the same area as the expander will be omitted 0V removed for omit Local Omit Key Normally wired to a key switch When the key swit...

Страница 83: ... 3 ys e pen ea i e la ea i e la igi p 3 Zone ype igi p 3 Use ype igi p 3 on ol i e igi p 3 on ol igi p 3 4 on ol igi p 3 i e on ol 7 igi p 3 ode En e ed igi p 3 Zone i ic igi p 3 Zone ala igi p 3 oo on ol igi p 3 oo on ol 4 igi p 3 ys e pen igi 3 In e ed I p 3 Ho se Uni p 3 Ho se Uni p 3 Ho se Uni p 3 Ho se Uni 4 Edi e p 3 In ecep ion Edi e y 1 y 3 n 0 1 2 3 4 5 6 7 y y y n y n y y n y y y y y y y...

Страница 84: ...d on the control panel and deactivates when mains is detected 02 Aux Fuse Blown This output type activates when the Auxiliary fuse F1 fails and deactivates when the system is reset 03 Bell Tamper This output type activates when the control panel Bell tamper or an expander input programmed as Bell tamper is activated causing a Tamper alarm on the system and deactivates when the Tamper alarm is rese...

Страница 85: ...e operates when Custom Output 4 Stage B activates and deactivates when Custom Output 4 Stage B deactivates 37 Custom4 Stage AB This output type operates when Custom Output 4 Stage A or B activates and deactivates when Custom Output 4 Stage A deactivates 38 Com 1 Fault This output type activates when whatever is connected to Com Port 1 stops communicating with the control panel and deactivates when...

Страница 86: ...s when the alarm is reset 09 PA Silent This output type activates when a zone programmed as PA Silent or a keypad PA 1 3 causes a silent PA alarm in the selected area and deactivates when the alarm is reset 10 Duress This output type activates when a User code with the Duress attribute causes a silent PA alarm in the selected area and deactivates when the alarm is reset 11 Fire Alarm This output t...

Страница 87: ...ancelled 45 Auto Arming This output type activates when the selected area Auto Arms and deactivates when the selected area is disarmed 46 Time Arming This output type activates for 5 minutes prior to the selected area being armed using the Control Timers 47 1st Code Entered This output type activates for 30 seconds when a User code with the Dual Code attribute is entered for the selected area 48 2...

Страница 88: ...e causes a Tamper alarm and deactivates when the tamper is reset This output will work if the zone is armed or disarmed MimicLat This output type activates when the selected zone is activated and deactivates when the next time the zone is activated This output will work if the zone is armed or disarmed Omitted This output type activates when the selected zone is omitted and deactivates when the zo...

Страница 89: ... output see system outputs 22 27 and 32 37 page 85 for details Custom Output 1 4 Stage A Will activate when switches 1 or 2 and 3 and 4 are active Custom Output 1 4 Stage B Will activate when switches 5 or 6 and 7 and 8 are active UUUCustom Output 1 4 Stage AB Will activate when switches 1 or 2 and 3 and 4 are active OR switches 5 or 6 and 7 and 8 are active Example Switch 1 is programmed as Zone ...

Страница 90: ... communicator has been fitted to the control panel This option can be used to send a test call to the Alarm Receiving Centre or to initiate a remote Upload Download call to one of the programmed call back numbers MSN Pre Dial No E o elec U igi p ions 3 44 3 U igi p ions ese igi U igi p ions e ial o y 2 y y When a ComISDN is connected to an extension of an ISDN line with more than 1 number the dire...

Страница 91: ...m Digi E o elec U igi p ions econda y o U igi p ions ese igi o ocol isa led cco n e ialling e p s o ocol isa led o ocol as o a o ocol isa led 3 87 34 7 3 cco n e 34 ialling e p s ialling e p s 3 U igi p ions og a igi 3 i a y o 3 87 34 7 3 y 3 y 2 n 2 y y n y n y y n y y 3 y n y ...

Страница 92: ...ier Elite Series Installation Manual 92 INS176 15 epo ing on epo ing on 3 epo ing on es o ing on es o ing on pen close on pen close on on ig Use ea cc Use ea cc n 23 y y n es o ing on 3 23 y pen lose on 3 23 y n y y n n y y ...

Страница 93: ...ies Installation Manual UDL Digi Options INS176 15 93 epo s io i y l o al la o al la epo eas epo eas epo eas on ig Use ea cc Use I I Use I I y epo eas E HIJK epo eas JK E H n A C P epo eas E H JK n 1 y y n n y y n n y y ...

Страница 94: ...Texecom Connect Each area can also have its own account number see page 96 81 for details Dialling Attempts This is the number of times the communicator will try to dial the Alarm Receiving Centre or Pager telephone number The number of dialling attempts is limited to 9 If this value is set to 0 the communicator will never dial out The following option is only displayed if the Fast Format protocol...

Страница 95: ...is line is displayed if there is no ARC configured for Texecom Connect Found an ARC to do the setup call The setup call is being initialized Trying to connect to the server IP connection is established with the server Sent all the required details to the server Waiting for server to reply Reply received successfully from server Access code displayed This means the IP connection is not available fo...

Страница 96: ... 6 digits In order for the control panel to use the area account numbers the area account Config option must be enabled see page 94 for details Area Accounts 640 E o elec U igi p ions U igi p ions ese igi ea cco n U igi p ions ea cco n s ea cco n 3 ea cco n 34 y 6 y 2 n y When using Fast Format Contact ID or SIA each area can have its own account number to identify events Account Numbers A to H I ...

Страница 97: ...elec U igi p ions U igi p ions ese igi all ac o ings e i ed U igi p ions U p ions 3 87 34 7 3 all ac o U ass o d is all ac o 3 Edi e 3 Edi e 3 ings e i ed ings e i ed ialling e p s ialling e p s ialling e p s 3 U p ions ended all e ea all e ea n y 3 n y y 6 n y n n y y n y y y y y n y 5 y ...

Страница 98: ... is selected a Dot on the display means the option is not selected The following UDL options are available A DL Attended The system will not allow the remote downloading computer access without user authorisation first M Man Call Back The system will not use the automatic call back feature The user must instruct the panel to call back the remote downloading computer The Auto Call Back feature oper...

Страница 99: ...s 3 3 3 e p od le ial e p s 3 en e i en e ec 3 3 78 34 3 ode e p g ode peed 4 3 H 3 3 78 34 3 ode peed 48 ode peed ad e ial o 34 ad U 34 7 3 8 ignal 8 d E 4 o o as all o aaaaaaa E 3 ccess n a e ass o d e p a a hi on I I Use a e y 7 y y N n y N y N y y n 5 y y y n y n y n y n y es o elec o o 3 8 3 e p I a a olling dd ess N y n o I d ess y N o o Enc yp ed o s Enc yp ed o s N y n Enc yp ion Key N y ...

Страница 100: ...ial out AV Re Dial Delay This is the amount of delay that the AV Module uses between re dialling telephone numbers Setup IP Module ComIP Details Com1 2 or 3 Select the ComPort you wish to programme IP details for ComIP Address This is the IP Address of the IP Module Must be entered as 192 168 0 100 use the key to insert the ComIP Port This is the Port number of the IP Module ComIP Gateway This is ...

Страница 101: ...Unit Standard Serial PC Modem 6 Radio Pad Paknet RP9 Radio Pad 7 GSM Module GSM Module Mobile Phone 8 Crestron System Crestron Home Automation System 9 SIP Serial IP Protocol 10 RadioPlus Serial Wireless Receiver 11 Inovonics Radio Inovonics Serial Wireless Receiver 12 WebWayOne Emizon WebWayOne Emizon UDP Module 13 X 10 Control X 10 Home Automation Module 14 IRIS IP Chiron IRIS Serial TCP IP Modu...

Страница 102: ...ork Netmask Subnet Mask A netmask defines the number of bits taken from the IP address that are assigned for the host section The default mask is 255 255 255 0 8 bits Automatically Assigned IP Address DHCP DHCP Dynamic Host Configuration Protocol is by far the most common method for routers to assign devices IP addresses so that they can use connections to access the Internet and other resources o...

Страница 103: ...L Digi Options UDL Options This should be setup before connecting o Enter the IP Address of the ComIP into the Host Address field o Enter the port number from the panel into the Host Port field Click ADD You have now configured Wintex for a local connection to the control panel To access the panel do the following In Wintex click on Connect Scroll down and choose Click via Network 192 168 0 100 on...

Страница 104: ...he Registration page complete all details including the Account Number you now have and press Register Site Name Site Summary User Name Password Email Address Push Notification Account Number Texecom App Server Information Primary IP Address 54 88 92 200 Port Number 10001 Secondary IP Address 52 28 12 230 Port Number 10001 Polling Time 15 Minutes Poll Timer MUST be set ARC Settings Reporting Optio...

Страница 105: ... following Enter Engineers Mode Press then y Global Options Press then y again Monitor Hardware Press n Press n again to toggle ATS Path Faults OFF Press y Press N twice then y Press y a and to ATS Path Faults Press n y to turn off Exit Engineers Mode If the ComIP misses its polling in a 1 hour time window the server will send notification directly to the app Do NOT do this on an EN50131 system or...

Страница 106: ...ss DHCP DHCP Dynamic Host Configuration Protocol is by far the most common method for routers to assign devices IP addresses so that they can use WiFi or hardwired connections to access the Internet and other resources on the network IP addresses will be assigned from a pool for a lease time and can change from device day to day for example when you leave your home and lose WiFi connection there i...

Страница 107: ...Name click on Scan and then select the Wi Fi network This is the name of the wireless router SSID that is connected to the internet Enter the router password if required Enter the chosen IP address for example 192 168 0 25 Enter the subnet mask usually 255 255 255 0 but can be found on the router Enter the Gateway IP address the router Enter the DNS Server details usually same as the router Click ...

Страница 108: ...o you by the DDNS provider Texecom Mobile App s Texecom mobile apps can be used to access the system either remotely or locally The apps are supported on iOS Android devices and can be downloaded from the respective app stores All three apps are configured identically for access Detailed information regarding all of the app settings can be found in the Help file and instructions provided with the ...

Страница 109: ...ss N twice Press then y twice Global Options System Timers Scroll to Poll IP Every Press n and then enter a value 15 minutes 015 The polling time is controlled by the server and may be changed Enable Digi Dial All Numbers Test Call To test the settings initialize a Push Notification and update the IP address in the App a test call should be carried out Please ensure the Digi is Enabled Dial All Nu...

Страница 110: ...nd type the IP address 10 10 100 254 into the address bar You will need to enter the user name and password that you have setup previously Click on Restore on the left side of the screen Click on OK to restore factory settings All user data including the user name and password will be set back to default and you should start the process again from the beginning of this manual The Restore process c...

Страница 111: ...nterference and can confirm the availability of a GPRS service at the proposed site Where a Nokia Net Mon phone is available and a Vodafone SIM Card is fitted it may be used in the same manner as the CS2366 Radio Test Set Alternatively a Vodafone mobile phone may be used to locate the point of strongest signal The signal strength indicator is normally a bar or line at the side of the display on th...

Страница 112: ... control panel need s an IP address so that it can connect to a local network Ensure that the customer has filled in the Customer IT Survey Form provided by EMIZON This will give you the information you need to set up the IP data on the control see page 100 Setup IP Module Connect the Ethernet cable between the Ethernet port on the TCD unit and the Network router Commissioning Now that the program...

Страница 113: ...y alarm Messages for set and unset include who where time and date all recorded Serial Panel Connection Connect the 05 0246 connector cable to the Texecom onto Com Port 1 Com port 2 usually has a local PC or other peripheral equipment connected WebWay SPT Texecom T Red Com Port 1 R Green RTN Blue Connect the WebWay PWR and to any relevant Power 12V 24V and Ground 0V terminals The Texecom panel con...

Страница 114: ...dio Pad and Com Port Options If the SMS call centre is utilised the engineer should enter the appropriate number and it should be configured under SMS Call Centre 1 2 The SMS centre telephone number is used to send SMS text messages to mobile phones Default 07860980480 Com IP Details if the panel is being programmed with a laptop on com port 2 and the WebWay is connected to com port 1 the SPT will...

Страница 115: ... 080176196135 Secondary No Leave blanks as the IRIS System will receive the secondary number from the Monitoring Centre Secure Apps platform Account Number Enter in the account number from the Monitoring Centre 4or 6 digits Dialler Attempts Leave as the default 3 Report options The Reporting Options will change depending on the alarm format selected please set up the various reporting option for t...

Страница 116: ...2 BA Alarm Restore Restore 132 BH Omit Omit Reinstate 573 BB Reinstate Omit Reinstate 573 BU 04 24Hr Audible Alarm Tamper 133 BA Alarm Restore Restore 133 BH Omit Omit Reinstate 572 BB Reinstate Omit Reinstate 572 BU 05 24Hr Silent Alarm Tamper 133 BA Alarm Restore Restore 133 BH Omit Omit Reinstate 572 BB Reinstate Omit Reinstate 572 BU 06 Audible PA Alarm Priority Alarm 123 PA Alarm Restore Rest...

Страница 117: ...ate Omit Reinstate 570 UU 15 Keyswitch Latching Alarm Open Close 409 OP Alarm Restore Open Close 409 CL Omit Omit Reinstate 570 UB Reinstate Omit Reinstate 570 UU 16 Security Key Alarm Open Close 421 DK Alarm Restore Open Close 421 DG Omit Omit Reinstate 570 UB Reinstate Omit Reinstate 570 UU 17 Omit Key Alarm Omit Reinstate Alarm Restore Omit Reinstate Omit Omit Reinstate 570 UB Reinstate Omit Re...

Страница 118: ...rted Alarm Not Reported Keypad No Restore Not Reported 33 Exit Error Arming Failed Alarm Open Close 457 EE 00 Restore Open Close 457 00 34 Entry Started Alarm Not Reported Restore Not Reported 35 Area Arm Suite Alarm Open Close Suite No 1 8 Restore Open Close 36 Armed with Line Fault Alarm Not Reported User No Restore Not Reported 37 Open Close Full Arm Alarm Open Close 401 OP User No Restore Open...

Страница 119: ...S User No Restore Not Reported 60 Panel Box Tamper Alarm Tamper 145 TA 00 Restore Restore 145 TR 00 61 Bell Tamper Alarm Tamper 145 TA Device ID Restore Restore 145 TR Device ID 62 Auxiliary Tamper Alarm Tamper 145 TA Device ID Restore Restore 145 TR Device ID 63 Expander Tamper Alarm Tamper 145 TA Device ID Restore Restore 145 TR Device ID 64 Keypad Tamper Alarm Tamper 145 TA Keypad No Restore Re...

Страница 120: ...Tamper 145 TA 000 Restore Restore 145 TR 88 Communication Port Alarm Maintenance 000 Restore Restore 000 89 TAG System Exit Batt OK Alarm Not Reported Zone No Restore Not Reported Zone No 90 TAG System Exit Batt LOW Alarm Not Reported Restore Not Reported 91 TAG System Entry Batt OK Alarm Not Reported Restore Not Reported 92 TAG System Entry Batt LOW Alarm Not Reported Restore Not Reported 93 Micr...

Страница 121: ... Not Reported 112 CIE Reset Alarm Maintenenace 305 RR 000 Restore Not Reported 000 113 Remote Command Via Com Port 114 User Added Alarm Not Reported Restore Not Reported 115 User Deleted Alarm Not Reported Restore Not Reported 116 Confirmed PA Alarm Priority Alarm 129 HV Zone No Restore Not Reported 117 User Ack Alarm Not Reported Restore Not Reported 118 Power Unit Failures Alarm Maintenance Alar...

Страница 122: ...work EXP 1 2 3 4 5 6 7 8 1 11 21 31 41 51 61 71 81 2 12 22 32 42 52 62 72 82 3 13 23 33 43 53 63 73 83 4 14 24 34 44 54 64 74 84 5 15 25 35 45 55 65 75 85 6 16 26 36 46 56 66 76 86 7 17 27 37 47 57 67 77 87 8 18 28 38 48 58 68 78 88 Reset ID Reset ID is transmitted as follows Device ID Panel RR 00 Engineer 01 Anti Code 02 RedCARE 03 Keyswitch 04 User 05 Wintex 07 Expander ID is transmitted as foll...

Страница 123: ...e p Use s En e Use En e Use ode 34 Use ype anage Use ype o In Use Use oc ed y i e Edi e lai e Edi e Use a e is llo ing o es hange n ode Use oo l Use oo l o es ys e es ys e es s o o an o E E E Use Use e o e c i a e e ice dd o Use e I po I I esen o I I esen o dd o Use e I po I I esen o I I esen o y y y O A R 1 2 y y y 2 y y 2 y 5 y y n y y 2 1 2 y 5 y n y n Use ea Use ea A C P Zone eas IJK ...

Страница 124: ...g etc In addition the User type also determines which options the user can access i e Setup Users etc The following User types are available 0 Engineer Engineers can arm disarm omit zones silence alarms and reset their assigned areas In addition Engineers can access the Programming Menu and all User menu options Engineers can also change their own User codes and assign new users to the system The ...

Страница 125: ...Disarming Disarming Disarming Disarming Disarming Omitting Omitting Omitting Omitting Omitting Omitting Omitting Omitting Eng Reset Local Arming Local Disarm Disarm First Disarm First Disarm First Disarm First Disarm First Disarm First Disarm First Disarm First User Options 2 User Menu User Menu User Menu User Menu User Menu User Menu User Menu User Menu Eng Program Vacation Door Strike Door Strik...

Страница 126: ...te PC option allowing them to initiate a call to a remote upload download PC C Duress Code The selected user will activate any outputs programmed as Duress whenever their codes are entered O Open Close The selected user will report open disarm and close arm events to an Alarm Receiving Centre every time they arm or disarm User Config This menu will only be displayed if a Custom User type is select...

Страница 127: ...em can have a Premier Elite SmartKey a TAG and a code or any combination of them This section only deals with Premier Elite SmartKey learning and routeing all other user programmable options can be found in INS467 Premier Elite Series 8 32XP W Installation Manual Great care should be taken when using large numbers of Premier Elite SmartKey only one Premier Elite SmartKey per expander can be used b...

Страница 128: ...g is the Mandatory Event log which records only events defined as mandatory by EN50131 The System Log records the last 500 48 1000 88 or 2000 168 events The Alarm Log records the last 32 alarm events The Mandatory Log records the last 500 mandatory events Event Log Hotkeys When viewing the system log there are 9 hotkeys available These hotkeys allow certain events to be found easier without the ne...

Страница 129: ...een changed DEFAULTS LOADED The factory default values have been loaded into memory DEFERRED The arming mode was deferred for area DOOR Door has been opened by a user with Door Control DOWNLOAD START An Upload Download has been initiated DOWNLOAD END The Upload Download has finished DURESS User has entered a Duress Code at a keypad Engineer Reset A reset has been performed using an Engineers code ...

Страница 130: ...d RKP LOST Keypad has been lost from the network RKP LOCKED Keypad has been locked out from too many invalid key presses Site Data Changed Site Data has been changed e g zone has been changed Supervision Fault A Radio device has failed to poll back to the panel within the Supervision Time System Over Voltage The control panel Bell Fuse has failed TAG User has presented their Prox TAG Test Call Pas...

Страница 131: ...ode if a Texecom bell box is connected Do Walk Test 24 48 64 88 168 Enginee U ils o al es al es eas E H E Zones ha need es ing a e Zone 7 on oo Zone o nge I E o elec Enginee U ils Enginee U ils ie E en og y 2 y y C A N Any of the zones on the system can be walk tested to ensure that they operate correctly A walk test can only be performed when the system or area is disarmed Once a zone has been ac...

Страница 132: ...over a period of days Pressing the A key will firstly show the zones that still need testing pressing the A key a second time will display the zones that have not been activated that day to view zones that have not been activated for 3 days type in 003 the maximum number of days that can be recalled is 255 pressing the A key a third time will revert back to the standard walk test display View Zone...

Страница 133: ... be tested 4 View Version No This option allows the control panel software version and serial number to be viewed Confirm Devices Enginee U ils on i e ices e K E p e K 3 E p e K 3 E p e E o s as K e E o s 4 as K ess E again o on i E o elec Enginee U ils Enginee U ils ie E en og y 5 y y y A R y This option allows the networks to be viewed to see what devices are connected and whether there are any ...

Страница 134: ... supply to be viewed The status indications shown have the following codes H Healthy A Active T Tamper F Fault S Secure M Masked The PSU status shows the following codes A AC Mains Fail 1 Battery 1 Fault 2 Battery 2 Fault F Mains Fuse Blown T PSU Box Tamper Set System Time Enginee U ils e ys e i e En e ne i e En e ne i e 4 E o elec Enginee U ils Enginee U ils ie E en og y 8 y y The control panel h...

Страница 135: ...ume level of speakers that are connected to the control panel keypads and expanders Pressing the CHIME key will cause the speaker that is being programmed to generate the exit tone at the selected volume level Default NVM Data E o elec Enginee U ils Enginee U ils e a l a a ess E ese anel p s ess E ese Keypad p s Keypad p s lease ai Enginee U ils ie E en og y y 3 y y This option allows various part...

Страница 136: ... zone has failed soak test A test failure will not prevent the user arming the system and will be cleared when the engineers code is entered At the end of the soak test all zones that have passed the test will be returned to normal operation Soak Test Areas 640 E o elec Enginee U ils Enginee U ils oa es eas oa es eas oa es eas E H Enginee U ils ie E en og y y y A C P oa es eas When an area is sele...

Страница 137: ...grammed ID will show here y y Configuring Radio devices NOT V2 Systems Up to 32 wireless devices can be learnt on to the system this can be any combination of detectors mag contacts and remote FOBs The number of remote FOBs is limited to the maximum number of devices the expander can accept Wireless devices can then be mapped on to the system along with conventional detectors The top line on the d...

Страница 138: ... chosen device cannot see either of the devices O The chosen device can see the ODD device s E The chosen device can see the EVEN device s B The chosen device can see BOTH devices Example Zone hoc _ E In this example Zone 9 can see the devices as detailed below use the scroll key to view information about other devices Display _ E Device 1 2 3 4 5 6 7 8 Can see On the 32XP W there are 16 windows t...

Страница 139: ...ics Menu Enginee U ils ie E en og E o elec Enginee U ils y Zone hoc a s aaa pd Zone hoc Zone hoc C Zone o icoche C O Use icoche o icoche Use icoche o connec ed Zone hoc C Zone hoc h since sg C C Use icoche Use icoche C Use icoche ogon a K C C R E o e ase n no n ey o s y P e o e ices 8 H y N N ...

Страница 140: ...will be put back to their originally programmed state Use the number keys to toggle Areas On or Off Use the key or enter the Zone number to select the zone required Use the C key to enable the zone in the Signalling Test A will be shown on the screen indicating the zone is selected and can be used for the signalling test Pressing n will arm the system as an engineer The engineer s code can then us...

Страница 141: ...enu will only be shown when creating a new site in the app or when you have connected to a site following an upgrade to V3 01 firmware Use of the Encryption key is in addition to the other requirements to make the app s function and is optional Programming the Control Panel Not V4 see above The encryption key is entered into a dedicated menu The following procedure should be followed noting the us...

Страница 142: ...amming Part Arms Alter Part Arms E o elec l e a s E o elec Zone e p o a Zone is o a Zone is o a Zone is o a Zone is C n y Each area on the system can have up to 3 Part Arms When Part Arm 1 2 or 3 is selected pre programmed zones are omitted to allow access to certain parts of the building ...

Страница 143: ...in the case of the W panels place the jumper on Fit for Commission position Wait for at least 15 minutes and the test all devices Access the Learn Menu using the Omit Hot key From any top level engineering menu pressing the B key will take you to the Ricochet learn menu above Menu B Ricochet Learn Menu E o elec B E o elec ea n icoche IMPORTANT In all cases when entering the Learn menu the next ava...

Страница 144: ...may be used The R Rkey is used to access the Delete option Follow the flow diagram below to delete devices from the system E o elec ea n icoche y y ea n e ice Zone E ele e e ice Zone E n n U R R R R N N y y If all devices are deleted from the system the following will be shown ll e ices ele ed Pressing the Nkey will return you to the Ricochet learn menu pressing the Rkey will enter the Learn devic...

Страница 145: ...x Premier Elite 24 Metal Current Current Consumption 95mA Maximum Current Available 0 75A charge 1 0A 0 3A charge 1 9A Rated Output Battery Arrangement Battery Charge Rated Output Amps 12h 24h 30h 60h 1 x 7Ah 0 3A 0 48A 0 19A 0 13A 0 021A 1 x 17Ah 0 3A 1 32A 0 61A 0 47A 0 18A 0 75A 1 0A 0 61A 0 47A 0 18A Standby and Recharge Times EN50131 1 Grade 1 Grade 2 Grade 3 Minimum Standby Period 12h 12h 30...

Страница 146: ...ndent power outputs according to EN50131 6 Aux 12V Bell Strobe Network 1 2 Battery DC DC 1 0A 1 0A 1 0A 1 6A 1 0A Standby Current 125mA Output Voltage Range 13 0V to 13 9V Maximum Ripple Voltage 0 5V pk pk Battery type sealed lead acid up to 18Ah Maximum recharge time 72h Battery Low Voltage Signal 9 5V Power Output Fault signal 10 5V with mains present Deep Discharge protection 8 6V Over voltage ...

Страница 147: ... or adjustments available on the control panel Optional Functions Where optional functions described in EN50131 3 are provided it is the installers responsibility to ensure these are programmed correctly In addition any optional functions may only be provided at the correct access levels as described in EN50131 1 Additional Functions Where additional functions not described in EN50131 3 are provid...

Страница 148: ...urrent Consumption Quiescent Alarm Nothing Connected 65mA 65mA Network 4 wire standard 7 0 2 alarm cable up to 250m Star Daisy Chain or any combination of the two Bank 1 Outputs Outputs 1 to 8 Bank 2 Outputs Outputs 1 to 8 100mA switched to 0V 100mA switched to 0V Environmental Operating Temperature 10 C 14 F to 55 C 131 F Storage Temperature 20 C 4 F to 60 C 140 F Maximum Humidity 95 non condensi...

Страница 149: ...n the European Union For proper recycling return this product to your local supplier upon the purchase of equivalent new equipment or dispose of it at designated collection points For more information see www recyclethis info Warranty All Texecom products are designed for reliable trouble free operation Quality is carefully monitored by extensive computerised testing As a result the control panel ...

Страница 150: ...Notes Premier Elite Series Installation Manual 150 INS176 15 Notes ...

Страница 151: ...Premier Elite Series Installation Manual Notes INS176 15 151 Notes ...

Страница 152: ...Lancashire BB4 4PW England Technical Support UK Customers Tel 08456 300 600 Calls charged at local rate from a BT landline Calls from other networks may vary International Customers Tel 44 1706 233875 Email techsupport texe com Texecom Limited 2017 INS176 15 ...

Отзывы: