10 Decommissioning
1.
34
www.tesvolt.com
WARNING!
Risk of electric shock, due to the auto-scheduled discharge of the energy storage
system. Please wait 15 minutes after switching off the storage system.
WARNING!
Remove the on/off switch plug from the BMS-Unit unit switch connector to
prevent the unit from being unintentionally switched on again! Apply the
supplied "REMOVE before commissioning" sticker to the APU-Unit unit switch
connector to prevent the unit from being unintentionally switched on again.
E.IA. .ENG-
TS
A.6
Stop the Sunny Island (press and hold the
Start/Stop button on the Sunny Island until
the inverter LED lights up orange).
2. Switch off the Sunny Island (press and hold the
Switch-off button on the Sunny Island until an
audio signal tone is emitted).
3, Switch off the battery (press the green
illuminated pushbutton switch on the door of
the battery cabinet, the green LED must go
out).
REMOVE BEFORE
START OPERATION