Master connection
13
www.tesvolt.com
Position
A
Description/Note
Description
AC power cable
Connection AC2 Gen/Grid Terminals L, NTT and PE Connection to the public
mains grid via a 3-core cable to external conductor L1
Conductor cross-section: 6 mm² … 16 mm²
B
Protective earthing
conductor
Connection AC1 Loads/SunnyBoys Terminal PE
Additional earth when the conductor cross-section of the AC-power cable
is less than 10 mm². The conductor cross-section must be at least the
same as the conductor cross-section of the AC power cable.
Battery connection
Conductor cross-section: 50 mm² … 120 mm²
Cable diameter: 14 mm … 25 mm
Tightening torque: 12 Nm
cabel DC –
cabel DC +
E
C
D
Battery temperature sensor
measuring cable
Connection BatTmp
Only Lead-acid batteries require connection of a battery temperature
sensor. The battery temperature sensor must be mounted in the middle
of the battery array, in the upper third of the battery cell.
F