8.2.3 Installation steps
28
www.tesvolt.com
Step
1
Description/Note
Position the battery cabinet in the installation location, taking into account the requirements listed under point 5
2
Open the door to the battery cabinet using the included control cabinet key, which can be found
on the outside of the door.
3
Mount the APU on the upper slide rail and use screws to fix it in place at the four fastening points.
The two-pin plug for the e-stop connection to the APU must be plugged in upon delivery.
Until this is plugged in, the APU remains inactive.
4
Mount the battery modules in the slide rails provided – starting from the top to the bottom
5
Remove the side cover of the battery module’s ABO and carefully break out the area for the copper rails
along the pre-determined breaking points
6
Connect the DC copper rails, always bearing in mind that in the 48 V variant, the positive pole must touch the
positive pole and the negative pole must touch the negative pole. Tighten the 13 mm screws using 12 nm of torque.
7
Reattach the side covers of the ABO to the battery module.
8
Lay the communication cable for the BAT COM using the included patch cable. Start by running the cable
from the APU (BAT COM) to the BAT COM IN of the battery module installed below the APU. From there,
run the cable from the BAT COM OUT to the BAT COM IN of the next module, etc.
9
Plug in the rack balancing plugs. The plug with an internal bridge from 1 to 4 is plugged into Rack Balancing In.
The plug with an internal bridge from 1 to 2 is plugged into Rack Balancing Out.
10
Connect the DC cable from the Sunny Island to the APU (CHARGER). If you do not use pre-assembled cables
from TESVOLT, it is important that an earth leakage and short-circuit protected cable (such as NSGAFöU)
be used.
11
Connect the communication cable from the Sunny Island (ComSyncIn) to the APU (CAN SMA)
WARNING!
Installation and servicing may only be performed by qualified personnel. Only authorised TESVOLT personnel are
permitted to open the APU-Unit. Improper use or incorrect configuration may damage the APU-Unit.
Opening the APU voids the warranty.