Sunny Island inverter connection
+
_
+
_
19
www.tesvolt.com
Position
A
Description/Note
Description
B
Battery connection
Conductor cross-section: 50 mm² ... 120 mm²
Cable diameter: 14 mm ... 25 mm
Tightening torque: 12 Nm
cabel DC –
cabel DC +
D
E
Cable for the control voltage
AC power cable
Sunny Island: Connection AC1 Loads/SunnyBoys Terminals
L and N, switching device: Connection X5 Terminals L and
N , conductor cross-section: 2.5 mm² ... 16 mm²
Sunny Island: Connection AC2 Gen/Grid Terminals L, NTT
and PE , switching device: Connection X3 Terminals L1, N
and PE, conductor cross-section: 10 mm² ... 16 mm²
C
Measuring cable for voltage
measurement
Sunny Island: Connection ExtVtg Terminals L and N,
switching device:: Connection X4 Terminals L1 and N,
conductor cross-section: 1.5 mm² ... 2.5 mm²