11
www.tesvolt.com
Position
A
Description/Note
Description
AC power cable
Connection AC2 Gen/Grid Terminals L, NTT and PE
Connection to the public mains grid via a 3-core cable
Conductor cross-section: 6 mm² … 16 mm²
B
Protective earthing
conductors
Connection AC1 Loads/SunnyBoys Terminal PE
Additional earth when the conductor cross-section of the AC power cable
is less than 10 mm². The conductor cross-section must be at least the
same as the conductor cross-section of the AC power cable.
Battery connection:
Conductor cross-section: 50 mm² ... 120 mm²
Cable diameter: 14 mm ... 25 mm
Tightening torque: 12 Nm
cabel DC –
cabel DC +
E
C
D
Battery temperature sensor
measuring cable
Connection BatTmp
Only Lead-acid batteries require connection of a battery temperature
sensor. The battery temperature sensor must be mounted in the middle of
the battery array, in the upper third of the battery cell.
F
Sunny Remote Control
data cable
Connection Display
G
Speedwire network cable
Connection ComETH
The Speedwire data module (SWDMSI-NR 10) must be installed in the
Sunny Island in order to connect the router/switch (see Installation
instructions for the Speedwire data module SWDMSI-NR 10).
The ComETH connection is located on the data module.
H
Data cable to Lithium-Ion
battery
ComSync In connection
Connection for the Lithium Ion Battery Management System
The communication bus must be connected to the
Lithium-Ion battery and the termination resistor must be
plugged into the ComSync Out connection.
SMA, SUNNY ISLAND and SUNNYPORTAL are registered trademarks of SMA Solar Technology AG in many countries.