switch. Follow proper lockout procedures
before proceeding.
b.
Once the electrical power supply is
disengaged, reverse any two power leads
of the power cord at the fused disconnect
terminals.
c. Note:
The operator must reverse the
power leads at the disconnect only
and not at the power entry terminals
on the unit’s electrical panel
. The unit’s
internal electrical system wiring is phased
correctly at the factory and must not be
altered in the field.
3
.
To visually verify pump rotation, start the unit and
observe the pressure gauges. The To Process
pressure will indicate 35-50 PSI more than
the From Process pressure. In this state, the
pump rotation is correct (clockwise). If this is
not evident the unit is not correctly phased and
should be corrected as outlined in step 2.
C.
Process Flow Adjustments
1.
The operator must determine and set proper
water flow rate for the most efficient and trouble
free operation.
a.
Water flow rate through the process is
determined by the pressure losses in
the process loop. Generally, higher flow
rates result in turbulent flow achieving
maximum temperature control and lower
maintenance.
b.
If the flow rate exceeds the motor HP capacity, the electric motor will
draw excessive amps. This is a result of the process loop’s ability to
flow water at a greater rate than can be provided by the pump. This will
eventually result in tripping the thermal motor overload relay (overload
relays open) and the unit will shut down and illuminate the Safety and
Alarm lights on the display.
2.
If an excessive flow situation is encountered and the motor overload circuit has
tripped, the operator must manually reset the overload relay before operations
can continue. This is done by opening the electrical panel cover and identifying
the overload relay.
DO NOT
reverse power leads at the
unit’s power entry.
WARNING:
To correct phase ... switch power leads at the disconnect switch only.
Remove shaft cover to view the
motor shaft.
Correct rotation is clockwise when
viewed from the rear of the motor.
Содержание Veteran VT LXG Series
Страница 2: ......
Страница 6: ...Page 6 THIS PAGE INTENTIONALLY BLANK ...
Страница 20: ...Page 20 THIS PAGE INTENTIONALLY BLANK ...
Страница 42: ...Page 42 THIS PAGE INTENTIONALLY BLANK ...
Страница 48: ...Page 48 THIS PAGE INTENTIONALLY BLANK ...
Страница 68: ...Page 68 THIS PAGE INTENTIONALLY BLANK ...
Страница 95: ...END 2021 TEMPTEK INC RE 20210323 ...
Страница 96: ......