b.
High drain back pressure.
Pressurized plant drain lines will prevent
flow to drain if the differential between the water supply pressure
and the drain line pressure is inadequate. The factory recommended
minimum differential is 20 psi. If the differential is less than the factory
recommendation, plant service personnel should take measures to
reduce drain line pressure.
4.
Instrument defective.
The instrument is designed and manufactured exclusively
by Advantage
.
The instrument is life-tested and found to be field reliable.
However, in the case where the instrument is determined to be defective,
the operator must remove the assembly according to instructions outlined in
section 5.8 and return the assembly to the factory. The instrument is not a field
serviceable component.
4.5
UNIT UNDERHEATS
A.
This is evidence by operations with To Process temperatures consistently below the
selected setpoint temperature.
1.
Process water leakage.
When the instrument engages the heater to elevate
process temperature, the input of heat into the process can be offset by a
defective AVT
TM
valve
.
If the AVT
TM
valve is defective, it may pass a larger than
required stream to drain, thus providing unwanted cooling. A defective AVT
TM
valve should be repaired immediately.
2.
Heater element failure.
A failed heater element will not input adequate heat
into the process to elevate the process water temperature. The operator must
check the amps at the heater contactor with the contactor energized. Zero amps
at the contactor indicate a failed heater or burnt wire connections. The operator
should remove the failed heater and replace with a new heater according to the
procedure outlined in section 5.2.
3.
Unit capacity too low.
This occurs when the process requires more heat than
the unit is capable of producing. The only option in such cases is to install a unit
with an adequate heater KW rating for the load.
4.
Instrument defective.
The instrument is designed and manufactured exclusively
by Advantage
.
The instrument is life-tested and found to be field reliable.
However, in the case where the instrument is determined to be defective,
the operator must remove the assembly according to instructions outlined in
section 5.8 and return the assembly to the factory. The instrument is not a field
serviceable component.
4.6 PRESSURE RELIEF VALVE LEAKS
A.
The unit has a 150 psi pressure relief valve mounted in the cooling cylinder. If the valve is
found to be leaking, the operator should check the following:
1.
Water supply pressure exceeds 75 psi.
The unit is designed to operate with
water supply
NOT
exceeding 75 psi. See section 2.3 paragraph B for specific
water supply pressure requirements at corresponding setpoint temperatures.
Содержание Veteran VT LXG Series
Страница 2: ......
Страница 6: ...Page 6 THIS PAGE INTENTIONALLY BLANK ...
Страница 20: ...Page 20 THIS PAGE INTENTIONALLY BLANK ...
Страница 42: ...Page 42 THIS PAGE INTENTIONALLY BLANK ...
Страница 48: ...Page 48 THIS PAGE INTENTIONALLY BLANK ...
Страница 68: ...Page 68 THIS PAGE INTENTIONALLY BLANK ...
Страница 95: ...END 2021 TEMPTEK INC RE 20210323 ...
Страница 96: ......