4.1 UNIT WILL NOT START (DISPLAY IS NOT ILLUMINATED)
A.
One or more fuses at the main disconnect device are open (blown). Determine continuity
at each fuse. If continuity is not determined, replace the fuse. Then determine cause of
blown fuse.
B.
Control circuit transformer fuse is open (blown). Determine continuity at the control circuit
transformer fuse. If continuity is not determined, replace the fuse.
4.2 UNIT WILL NOT START (DISPLAY ILLUMINATED)
A.
Power supply is ON.
The operator can determine that electrical power supply to the unit
is “on” when the Display is illuminated. Even with the main power supply on, the unit is
prevented from operating by one of the following conditions:
1.
Water supply pressure inadequate.
The display shows
a Fault : System Safety screen. The unit is prevented
from operation without adequate water supply pressure
by the electrical panel mounted pressure switch.
Sufficient water supply pressure must be present to
close the switch. Refer to Section 2.3 for additional
information.
2.
Motor overload switch opened.
The electric motor is protected from overload
conditions by a set of thermal overload relays. These relays will open (trip). If
the overload relay is open, it must be reset before operation can continue. An
excessive flow condition must be isolated and corrected immediately.
3.
High temperature limit switch open.
The unit is
prevented from operations at temperatures exceeding
256°F by a “high temperature limit switch”. This switch
is installed in the To Process temperature sensor. If this
switch is open (due to a high temperature condition), the
unit cannot be started and must “cool down” before the
“high temperature limit switch” will automatically reset.
4.3
UNIT STOPS
A.
The operator should determine the main power supply to the unit is
ON
by an illuminated
Display. With the main power supply “on”, the unit will be prevented from starting by the
following conditions:
1.
Water supply pressure inadequate.
The display shows
a Fault : System Safety screen. The unit is prevented
from operation without adequate water supply pressure
by the electrical panel mounted pressure switch.
Sufficient water supply pressure must be present to
close the switch. Refer to Section 2.3 for additional
information.
System Fault Screen.
Indiacates a water supply or
a pump overload fault.
System Fault Screen.
Indiacates a water supply or
a pump overload fault.
High Temp Limit Fault
Screen.
Содержание Veteran VT LXG Series
Страница 2: ......
Страница 6: ...Page 6 THIS PAGE INTENTIONALLY BLANK ...
Страница 20: ...Page 20 THIS PAGE INTENTIONALLY BLANK ...
Страница 42: ...Page 42 THIS PAGE INTENTIONALLY BLANK ...
Страница 48: ...Page 48 THIS PAGE INTENTIONALLY BLANK ...
Страница 68: ...Page 68 THIS PAGE INTENTIONALLY BLANK ...
Страница 95: ...END 2021 TEMPTEK INC RE 20210323 ...
Страница 96: ......