Temperature Control Units : Veteran with LXG Series Instrument
Page: 47
TEMPTEK, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Email: [email protected]
If the plant water supply pressure exceeds 75 psi, the pressure relief valve
may leak. Static water supply pressure can be determined at the unit’s location
by reading the unit’s 0-160 PSI pressure gauges when the unit’s motor pump
is off. If the water supply pressure at the unit’s location exceeds 75 PSI, a
pressure reducing valve must be installed in the water supply line. The factory
recommended ‘regulated pressure out’ is 55 PSI. Refer to section 7.3 for
regulator installation drawing.
2.
Back flow prevention device in water supply line.
If a back flow prevention
device (check valve, pressure regulator, closed valve) is installed in the water
supply line, increased pressures from thermal expansion are unable to move
into the water supply line. This will increase the unit’s internal pressure causing
the pressure relief valve to leak. Refer to section 7.3 for regulator installation
drawing.
3.
Valve contamination.
The pressure relief valve may become contaminated with
water debris causing the valve not to close properly. If this is the case, flushing
the valve for a moment will cleanse the seat and allow it to work properly. If
flushing the valve does not remedy the leaking, the valve must be replaced.
4.
Extreme internal system pressure.
If the internal pressure in the unit is
elevated, the pressure relief valve will leak as a safety measure to dissipate
excessive pressure. If this is the case, the operator must determine why the
system internal pressure is excessive and correct the condition.
4.7 COOLING VALVE FAULT
A.
AVT
TM
FAULT.
When power is applied, the AVT
TM
valve begins
a ‘homing process’. The valve is turned forward and backward
across a limit switch to establish the valve position.
B.
If valve position cannot be established, a fault will be displayed.
Refer to section 5.3 for AVT
TM
service and repair instructions.
AVT Valve Fault Screen.
Содержание Veteran VT LXG Series
Страница 2: ......
Страница 6: ...Page 6 THIS PAGE INTENTIONALLY BLANK ...
Страница 20: ...Page 20 THIS PAGE INTENTIONALLY BLANK ...
Страница 42: ...Page 42 THIS PAGE INTENTIONALLY BLANK ...
Страница 48: ...Page 48 THIS PAGE INTENTIONALLY BLANK ...
Страница 68: ...Page 68 THIS PAGE INTENTIONALLY BLANK ...
Страница 95: ...END 2021 TEMPTEK INC RE 20210323 ...
Страница 96: ......