Programming by console
Installer Manual -
TP8-64 BUS
5-36
COMMUNICATION WITH THE WIRELESS CONSOLES
Permits testing of the communication between the control panel and the wireless
consoles.
The test takes approx. 8 seconds and checks the correct data transmission/reception
of all the wireless consoles associated to the control panel (max. 4).
Communication issues
On the display are viewed the communication issues separately for all four wireless
consoles (T1, T2, T3 and T4):
z
Yes
Communication (TX/RX) without errors
z
No
Communication (TX/RX) with negative issue
z
- - -
No wireless console associated to this position
Commands available
+
EXIT
to quit the submenu
5.21.2
ZONE TEST
Permits testing of the correct functioning of the wired as well as the wireless detectors
and the inputs they are associated to.
On initiation of the test, the control panel disables both the general stand-by output
and that of the programs (detectors enabled).
On the display is viewed
Zones
followed by
- - -
for the entire duration of the test.
The control panel is waiting for signaling released by the zone inputs.
To verify correct functioning of the detectors and the inputs, pass by the detectors or
activate the contacts.
For every zone that is found open, the buzzer is activated on the consoles for approx.
2 seconds.
Test issue
After the test, pressing the arrow keys
yw
on the console, the zones that have been
found open are viewed in sequence.
Commands available
+
EXIT
to quit the submenu
5.21.3
INDOOR SIREN AND BATTERY TEST
On initiation of the test, the control panel reduces power supply voltage to 10.5V in
order to provoke the intervention of the battery.
The indoor sirens are activated while they are powered by battery.
The test takes 60 seconds and can be interrupted at any time by pressing the EXIT
key.
Test issue
After the test, if the battery voltage results too low, the battery LED becomes blinking.
Check the quality of the battery and if necessary, replace it.
Commands available
+
EXIT
to quit the submenu
5.21.4
OUTDOOR SIREN AND BATTERY TEST
On initiation of the test, the control panel reduces power supply voltage to 10.5V in
order to provoke the intervention of the battery.
The outdoor sirens are activated while they are powered by battery.
The test takes 60 seconds and can be interrupted at any time by pressing the EXIT
key.
Test issue
After the test, if the battery voltage results too low, the battery LED becomes blinking.
Check the quality of the battery and if necessary, replace it.
Commands available
+
EXIT
to quit the submenu
Radio
7
Con. consoles
Con. consoles
Waiting
T1 T2 T3 T4
Yes Yes --- ---
Test
2
Zones
Zones
- - -
Zones
Zone 025
Zones
Zone 026
Test
4
Outdoor sirens
Test
3
Indoor sirens
WARNING
During the test, the wireless indoor sirens work according to programming (see § 5.4), i.e. not active,
sounding, flashing, sflashing.
The sounding or flashing time, however, is irrelevant.
WARNING
During the test, the wireless outdoor sirens work according to programming (see § 5.4), i.e. not
active, sounding, flashing, sflashing.
The sounding or flashing time, however, is irrelevant.
Содержание TP8-64 BUS
Страница 4: ...IV Installer Manual TP8 64 BUS...
Страница 12: ...Index Installer Manual TP8 64 BUS 8...
Страница 16: ...Generalfeatures Installer Manual TP8 64 BUS 1 4...
Страница 32: ...Hardware Installer Manual TP8 64 BUS 2 16...
Страница 48: ...Input expansion modules Installer Manual TP8 64 BUS 2A 16...
Страница 54: ...Output expansion modules Installer Manual TP8 64 BUS 2B 6...
Страница 58: ...Console Installer Manual TP8 64 BUS 2C 4...
Страница 64: ...Keypoints Installer Manual TP8 64 BUS 2D 6...
Страница 70: ...Programming interfaces Installer Manual TP8 64 BUS 2E 6...
Страница 72: ...Telephone communicator with GSM module Installer Manual TP8 64 BUS 2F 2...
Страница 76: ...Wireless expansion modules Installer Manual TP8 64 BUS 2G 4 2G 2 2 DIP SWITCH SETTINGS TABLE 2 2G 2 3 CASING...
Страница 79: ...TP8 64 BUS Installer manual Wireless expansion modules 2G 7 2G 4 1 ELECTRONIC BOARD 2G 4 2 DIP SWITCH SETTINGS...
Страница 82: ...Wireless expansion modules Installer Manual TP8 64 BUS 2G 10...
Страница 88: ...Set up Installer Manual TP8 64 BUS 3 6...
Страница 93: ...TP8 64 BUS Installer Manual Set up 3 11 3 3 2 CONNECTION OF THE MODULES ON SENSOR BUS AND SIRENS BUS...
Страница 138: ...Programming by PC Installer Manual TP8 64 BUS 4 44...
Страница 176: ...Programming by console Installer Manual TP8 64 BUS 5 38...
Страница 180: ...Control by console Installer Manual TP8 64 BUS 6 4 OPERATIONS WITHOUT CODE...
Страница 192: ...Control by console Installer Manual TP8 64 BUS 6 16...
Страница 222: ...Technicalspecifications Installer Manual TP8 64 BUS 8 16...
Страница 223: ...TP8 64 BUS Installer Manual Protocols Appendix A A 1 APPENDIX A TRANSMISSION PROTOCOLS TP8 64 BUS...
Страница 224: ...Appendix A Protocols Installer Manual TP8 64 BUS A 2...
Страница 227: ...TP8 64 BUS Installer Manual Special procedures Appendix B B 1 APPENDIX B SPECIAL PROCEDURES TP8 64 BUS...
Страница 228: ...Appendix B Special procedures Installer Manual TP8 64 BUS B 2...
Страница 240: ...Appendix B Special procedures Installer Manual TP8 64 BUS B 14...
Страница 241: ...TP8 64 BUS Installer Manual Code management Appendix C C 1 APPENDIX C CODE MANAGEMENT TP8 64 BUS...
Страница 242: ...Appendix C Code management Installer Manual TP8 64 BUS C 2...
Страница 245: ...TP8 64 BUS Installer Manual Code management Appendix C C 5...
Страница 246: ...Appendix C Code management Installer Manual TP8 64 BUS C 6 TP8 64 BUS INSTALLER MANUAL...