Operation                         

UNOCCUPIED SETBACK

The SZ1022N and SZ1024N operate  in either an occupied or
unoccupied mode. During the occupied mode, the occupied
heating and cooling setpoints will be maintained, and the fan
will operate according to its occupied setting. During the
unoccupied mode, the unoccupied heating and cooling
setpoints will be maintained, and the fan will operate
according to its unoccupied setting. The occupied LED will
be lit when the unit is operating in the occupied mode.

The occupied schedule may be set utilizing the internal time
clock or DI3 may be used with an external time clock,
whereas when DI3 is closed, the unit is in the occupied mode.
The Smart Recovery function is disabled when DI3 is used
for external time clock.

OVERRIDE

A timed override is available on the face or through
momentary contacts. The amount of time the unit will be
overridden is set from 0 to 255 minutes in the programming.
This override only activates when the thermostat is operating
in the unoccupied mode. Both the software and the service
button allows you to view the time remaining in the override
mode. If the occupant desires to return the thermostat to
unoccupied operation before that time interval is up, they may
press the button on the face or the momentary contact again. 

Continuous override is available through the DI3 contact or
the software. If DI3 is set to external override, the unit will be
in the occupied mode whenever the DI3 contact is closed.
When using this option, the timed override may still be
activated. 

The software allows you to override the thermostat by putting
the override parameter into the remote mode, and thus
disabling the timed override.

SETBACK AND OVERRIDE APPLICATIONS

In most applications, it is desired to maintain a regular
schedule, and allow timed override with the button on the
face or with a remote momentary contact. 

To allow a regular schedule, and also automatically override
with the use of occupancy or light sensor, set DI3 to override
and set it up so that the contact is closed when you want the
override.  

For applications where a room might not be used on a regular
schedule, such as conference rooms, set DI3 to time clock
and close the contact when you want the room occupied, such
as with a switch or wind-up timer. If each occupancy period
is about the same, (theaters, meetings) another option is to set
the DI3 to time clock, and use the timed override button to
put the unit in occupied mode. 

To make the unit always occupied, set DI3 to time clock and
short the DI3 terminal to ground. 

DISCHARGE AIR TEMPERATURE SENSING

The SZ1022N and SZ1024N accept a remote discharge air
sensor (TS1002) for monitoring purposes.  (See setup
instructions for dipswitch placement for this option.) 

Choose YES in programming screen #32 only if you are
using a discharge air sensor and you want to enable the
discharge air temperature high and low limit functions. If NO
is chosen, the discharge air is still monitored. 

When the function is enabled, a HIGH LIMIT and LOW
LIMIT are entered in steps #33 and #34. If the HIGH LIMIT
is reached, the fan and heating stages will be turned off and
will remain off until the discharge air temperature falls 3°
below that limit. If the LOW LIMIT is reached, the fan and
cooling stages will be turned off and will remain off until the
discharge air rises 3° above that limit. When either limit is
reached, the service LED will be on until normal operation
resumes.     

The discharge air span is 0 to 150 °F (-17.8 to 65.6 °C).

FAN PROVING

The SZ1022N and SZ1024N allow DI1 to be set for fan
proving to protect equipment on fan failure. To utilize this,
input a pressure or current switch which tells when the fan is
running. If the thermostat closes its fan contact, and the DI1
is not closed after thirty seconds, the system will go to OFF,
disabling all outputs, the fan LED will turn off, and the
service LED will be lit until the system is manually reset by
switching the system to a mode other than OFF.  

DI2 SETPOINT SHIFT

The SZ1022N and SZ1024N allow DI2 to be set for setpoint
shift for energy demand setback. This is enabled by setting
DI2 to the MONITOR mode. A digital contact that closes
when setback is needed should be wired into DI2. You may
specify a number of degrees such that, when the thermostat is
operating in the occupied mode, and DI2 is closed, the
heating setpoint will be lowered this number of degrees, and
the cooling setpoint will be raised this number of degrees.
The fan will continue to operate according to its occupied
setting. If you are using DI2 as monitor for another purpose,
make sure to set this value to zero.

Содержание SZ1022N

Страница 1: ...ut economizers z Fan interlock safety option z Filter service input and indication z Equipment monitoring inputs and indication z External time clock input z Energy management input for setpoint shift...

Страница 2: ...hielded wire is used and the installation environment is free of electrical noise Sensor wire should be kept at least five feet away from line voltage wiring The SZ1022N or SZ1024N accept two remote s...

Страница 3: ...in the cover shown above connected with ribbon cable must be set in order to lock the user out of the program and or to set the clock and schedule Use the guide below to set these dipswitches for you...

Страница 4: ...g Screen Press the program setup button to access the following screens Access Code Entry Screen Will appear if access code is required for programming Use 248 as the default If the wrong code is ente...

Страница 5: ...for heat stage 1 First stage is normally 0 offset Heat Stage 1 Differential Screen Enter a differential value for heat stage 1 Heat Stage 2 Offset Screen Enter an offset value for heat stage 2 This sc...

Страница 6: ...his screen only appears if compressor 2 is enabled Compressor Stage 2 Differential Screen Enter a differential value for compressor stage 2 This screen only appears if compressor stage 2 is enabled Au...

Страница 7: ...creen Setting Clock and Schedule The SZ1022N and SZ1024N clock and schedule may be set through the display and keypad or with a PC For more information on programming through the PC consult the softwa...

Страница 8: ...set DI3 to time clock and close the contact when you want the room occupied such as with a switch or wind up timer If each occupancy period is about the same theaters meetings another option is to se...

Страница 9: ...rential consideration and ramps the setpoint when going from the unoccupied mode to the occupied mode At the beginning of the occupied mode the occupied setpoint will be reached many times without the...

Страница 10: ...e fan is on whenever the fan LED is on If the fan should be on but the fan LED is off check the fan and system switch modes and the unoccupied fan mode in programming If the fan is off but the fan LED...

Страница 11: ...e following screens Service Screen This message may be followed by any or all of the following CHECK FILTER CHECK FAN DISCHARGE HIGH DISCHARGE LOW or CHECK DI2 Discharge Air Temperature Screen Shows d...

Страница 12: ...mode is allowed by factory default To lock out access to system switching see programming step 5 SETTING CLOCK SCHEDULE The ability to set the clock and schedule is allowed by factory default An acces...

Страница 13: ...e heating setpoint is shifted down ADI 19 Seconds Internal time clock second 0 59 ADI 20 Minutes Internal time clock minute 0 59 ADI 21 DegF C Occupied heating setpoint 40 90 4 32 Occupied heating set...

Страница 14: ...s 4 per hour setpoint ramp prior to oc cupancy for both heating and cooling BD 7 Require access code 0 No 1 Yes Programming access from keypad for programming BD 8 Require access code 0 No 1 Yes Clock...

Страница 15: ...eck DI2 NOTE 1 The Service status point represents general Check status If this is point is 1 the user can find out the actual failing condition by polling point 38 to 42 If this point is 0 points 38...

Страница 16: ...DegF C Occupied heating setpoint 40 90 4 32 Occupied heating setpoint must be less than occupied cooling setpoint ADI 19 DegF C Unoccupied heating setpoint 40 90 4 32 Unoccupied heating setpoint must...

Страница 17: ...e access code 0 No 1 Yes Clock Schedule access from keypad for clock schedule BD 9 Enable compressor 2 0 disable 1 enable Disable unused stages recommended BD 10 Enable auxiliary heat 1 0 disable 1 en...

Страница 18: ...is 1 then by polling point 38 to 42 the user can find out actual failing condition If this point is 0 then points 38 to 42 will be also 0 NOTE 2 All of the ADI and BD points support the override funct...

Страница 19: ...R 2800 LAURA LANE MIDDLETON WI 53562 800 288 9383 FAX 608 836 9044 www tcsbasys com 19...

Страница 20: ...R 2800 LAURA LANE MIDDLETON WI 53562 800 288 9383 FAX 608 836 9044 www tcsbasys com 20 Rev 0305...

Отзывы: