background image

1

User manual
ALFA 71 S PI
Thermostat.

0-100

C

VDH doc. 080350

Version: v1.0

Date: 07-03-2008

Software: ALFA71-S-PI 0-100

File: Do080350.WPD

Range: 0/+100,0

C

* Installation.

On the top side of the 

ALFA 71 S PI

 is shown how the sensors, power supply, relays and 0..10Vdc

Solid-State output has to be connected. After connecting the 

ALFA 71 S PI

 to the power supply, a self

test function is started. As this test is finished the measured temperature appears in the display.

* Control.

The 

ALFA 71 S PI

 thermostat can be controlled by four pushbuttons on the front.

These keys are:

SET

- view / change the setpoint.

UP

 

- increase the setpoint.

DOWN

- decrease the setpoint.

C

- hidden push button above the 

SET

 key and behind 

C

 symbol.

* Viewing setpoint.

By pushing the 

SET

 key the setpoint appears in the display. The decimal point of the last display starts

blinking.  A  few  seconds  after  releasing  the 

SET

  key  the  setpoint  disappears  and  the  measured

temperature is shown again in the display.

* Changing setpoint.

Push the 

SET

 key and the setpoint appears in the display. Release the 

SET

 key. Now push the 

SET

key again together with the 

UP

 or 

DOWN

 keys to change the setpoint. A few seconds after releasing

the keys the measured temperature shows again in the display.

* Status of the Relays.

By pushing the hidden 

C

 key the display shows the status of the relays. Each display segment shows

the status of the relay output, showing 0=off and 1=on. The code 110 means relay 1 and 2 are on and
relay 3 is off.

* Setting internal parameters.

Next to the adjustment of the setpoint, internal settings can be made like differential, sensor-offset,
setpoint range and the functions of the thermostat.
Push the 

DOWN

 key more than 10 seconds, to enter the 'Internal Programming Menu'. In the left

display  the  upper  and  lower  segment  are  blinking.  Over  the 

UP

  and 

DOWN

  keys  the  required

parameter can be selected (see table for the parameters).
If the required parameter is selected, the value can be read-out by pushing the 

SET

 key. Pushing the

UP

 or 

DOWN

 key to change the value of this parameter.

If after 20 seconds no key is pushed, the 

ALFA 71 S PI

 changes to the normal operation mode.

Содержание ALFA 71 S PI

Страница 1: ...anging setpoint Push the SET key and the setpoint appears in the display Release the SET key Now push the SET key again together with the UP or DOWN keys to change the setpoint A few seconds after releasing the keys the measured temperature shows again in the display Status of the Relays By pushing the hidden C key the display shows the status of the relays Each display segment shows the status of...

Страница 2: ...and H as indication for a open circuit sensor Reset Alarm When a error messages appears it can be resetted by pushing the SET key The function of this key depends on parameter P37 Technical details Type ALFA 71 S PI Thermostat Range 0 100 0 C display per 0 1 C Supply 12Vac 50 60Hz 5 10 Display 3 digit 7 segment display Relays Ry1 SPST NO 250V 8A cos 1 of 250V 5A cos 0 4 Ry2 SPST NO 250V 8A cos 1 o...

Страница 3: ...0 0 5 0 0 0 5 0 0 20 21 22 23 24 Switch on delay cooling Switch off delay cooling Parameter 20 21 in Sec or Min 0 Seconds 1 Minutes Minimum on time cooling Minimum off time cooling 0 99 0 99 0 1 0 99 Minutes 0 99 Minutes 0 0 0 0 0 25 26 27 Minimum set point Maximum set point Read out above 10 C per 1 C 50 0 50 0 C 50 0 50 0 C 0 No 1 Yes 50 50 0 30 31 32 33 34 35 36 37 Alarm type 0 None 1 Absolute ...

Страница 4: ...4 Dimensions Connections Address VDH Products BV Tel 31 0 50 30 28 900 Produktieweg 1 Fax 31 0 50 30 28 980 9301 ZS Roden Email info vdhproducts nl The Netherlands Internet www vdhproducts nl ...