* Parameters ALFA 71 S PI

Para-
meter

Description Parameter

Range

Default

01

02
03
04

Function Relay 1

1 = Cool
2 = Heat
3 = Alarm

Function Relay 2

(same as relay 1)

Function Relay 3

(same as relay 1)

Function PI-output

1 = Cool 
2 = Heat

1..3

1..3
1..3
1..2

1

2
3
1

05
06
07
08

Offset temperature sensor 1
Offset PI function (zone) 
P-band setting
I-time setting (0 means off)

-15.0..+15.0

C

-15.0..+15.0

C

0.0..20.0

C

0..99 Minutes

0.0
0.0
5.0

0

10

11

12
13
14
15
16
17
18
19

Switch on relay 2 by

0 = Temperature
1 = Time

Switch on relay 3 by

0 = Temperature
1 = Time

Switch on delay relay 2
Switch on delay relay 3
Switching differential relay 1
Setpoint offset relay 1
Switching differential relay 2
Setpoint offset relay 2
Switching differential relay 3
Setpoint offset relay 3

0..1

0..1

0..99 Minutes
0..99 Minutes
0.1..15.0

C

-15..+15

C

0.1..15.0

C

-15..+15

C

0.1..15.0

C

-15..+15

C

0

0

15
15

0.5
0.0
0.5
0.0
0.5
0.0

20
21
22

23
24

Switch on delay cooling
Switch off delay cooling
Parameter 20/21 in Sec. or Min.

0 = Seconds
1 = Minutes

Minimum on-time cooling
Minimum off-time cooling

0..99
0..99
0..1

0..99 Minutes
0..99 Minutes

0
0
0

0
0

25
26
27

Minimum set point
Maximum set point
Read-out above -10

C per 1

C

-50.0..+50.0

C

-50.0..+50.0

C

0 = No, 1 = Yes

-50
+50

0

30

31
32
33
34
35

36
37

Alarm type 

0 = None
1 = Absolute
2 = Relative

Minimum alarm set point
Maximum alarm set point
Time delay minimum alarm
Time delay maximum alarm
Function alarm relay

 

0 = Fail safe

alarm

1 = Control alarm

Reset alarm relay after recovering alarm
Reset alarm relay after manual reset

0..2

-50.0..+50.0

C

-50.0..+50.0

C

0..99 minutes
0..99 minutes
0..1

0= No, 1= Yes
0= No, 1= Yes

1

-50
+50

0
0
0

0
0

40
41

Start up delay after power failure
Forced relay function at sensor failure

0 = None 
1 = Cool
2 = Heat

0..99 Minutes
0..2

0
0

50
51

Duty Cycle control active
Duty Cycle cycle time

0= No, 1= Yes
5..240 Seconds

1

20

95
96
97
98
99

Software version
Production year
Production week
Serial number (x1000)
Serial number (units)

-
-
-
-
-

-
-
-
-
-

Содержание ALFA 71 S PI

Страница 1: ...anging setpoint Push the SET key and the setpoint appears in the display Release the SET key Now push the SET key again together with the UP or DOWN keys to change the setpoint A few seconds after releasing the keys the measured temperature shows again in the display Status of the Relays By pushing the hidden C key the display shows the status of the relays Each display segment shows the status of...

Страница 2: ...and H as indication for a open circuit sensor Reset Alarm When a error messages appears it can be resetted by pushing the SET key The function of this key depends on parameter P37 Technical details Type ALFA 71 S PI Thermostat Range 0 100 0 C display per 0 1 C Supply 12Vac 50 60Hz 5 10 Display 3 digit 7 segment display Relays Ry1 SPST NO 250V 8A cos 1 of 250V 5A cos 0 4 Ry2 SPST NO 250V 8A cos 1 o...

Страница 3: ...0 0 5 0 0 0 5 0 0 20 21 22 23 24 Switch on delay cooling Switch off delay cooling Parameter 20 21 in Sec or Min 0 Seconds 1 Minutes Minimum on time cooling Minimum off time cooling 0 99 0 99 0 1 0 99 Minutes 0 99 Minutes 0 0 0 0 0 25 26 27 Minimum set point Maximum set point Read out above 10 C per 1 C 50 0 50 0 C 50 0 50 0 C 0 No 1 Yes 50 50 0 30 31 32 33 34 35 36 37 Alarm type 0 None 1 Absolute ...

Страница 4: ...4 Dimensions Connections Address VDH Products BV Tel 31 0 50 30 28 900 Produktieweg 1 Fax 31 0 50 30 28 980 9301 ZS Roden Email info vdhproducts nl The Netherlands Internet www vdhproducts nl ...

Отзывы: