* Adjustment sensors.

The temperature sensor can be adjusted by using the Sensor Offset parameter 06.
Indicates the Sensor e.g. 2

C to much, the Sensor Offset has to be decreased with 2

C.

* Error messages.

In the display of the 

ALFA 71 S PI

 the following error messages can appear:

LO

- Minimum alarm.

Solution E1:

HI

- Maximum alarm.

- Check if the sensor is connected correctly.

E1

- Sensor-1 failure.

- Check sensor  (1000

 at 25

C).

- Replace sensor.

EEE

- Settings are lost.

Solution EEE:
- Reprogram the settings.

-L-

- In case of sensor short-circuit the display alternates between error-code 

E..

  and 

-L-

, as indication for a short-circuit sensor.

-H-

- In case of open-circuit sensor the display alternates between error-code 

E..

 

 and 

-H-

, as indication for  a open circuit sensor.

Reset Alarm.

When a error-messages appears it can be resetted by pushing the 

SET

 key.  The

function of this key depends on parameter P37.

* Technical details.

Type

: ALFA 71 S PI Thermostat

Range

: 0/+100,0

C, display per 0,1

C

Supply

: 12Vac 50/60Hz (-5/+10%)

Display

: 3-digit 7-segment display

Relays

: Ry1= SPST(NO) 250V/8A (cos

=1) of 250V/5A (cos 

=0.4)

  Ry2= SPST(NO) 250V/8A (cos

=1) of 250V/5A (cos 

=0.4)

  Ry3= SPDT(NO/NC) 250V/8A (cos

=1) of 250V/5A (cos 

=0.4)

  Relays have one common (C).

Control

: By push buttons on front.

Front

: Polycarbonate IP65

Sensor

: SM 811/2m (PTC 1000

/25

C).

Analog output

: 0..10 Vdc Solid State output

Dimensions

: 35 x 77 x 71,5mm (HWD)

Panel cutout

: 28 x 70mm (HW)

Accuracy

: ± 0,5% of the range.

- Provided with memory protection during power failure.
- Connections with screw terminals on the back side.
- Equipped with sensor failure detection.
- Special versions on request available.

Содержание ALFA 71 S PI

Страница 1: ...anging setpoint Push the SET key and the setpoint appears in the display Release the SET key Now push the SET key again together with the UP or DOWN keys to change the setpoint A few seconds after releasing the keys the measured temperature shows again in the display Status of the Relays By pushing the hidden C key the display shows the status of the relays Each display segment shows the status of...

Страница 2: ...and H as indication for a open circuit sensor Reset Alarm When a error messages appears it can be resetted by pushing the SET key The function of this key depends on parameter P37 Technical details Type ALFA 71 S PI Thermostat Range 0 100 0 C display per 0 1 C Supply 12Vac 50 60Hz 5 10 Display 3 digit 7 segment display Relays Ry1 SPST NO 250V 8A cos 1 of 250V 5A cos 0 4 Ry2 SPST NO 250V 8A cos 1 o...

Страница 3: ...0 0 5 0 0 0 5 0 0 20 21 22 23 24 Switch on delay cooling Switch off delay cooling Parameter 20 21 in Sec or Min 0 Seconds 1 Minutes Minimum on time cooling Minimum off time cooling 0 99 0 99 0 1 0 99 Minutes 0 99 Minutes 0 0 0 0 0 25 26 27 Minimum set point Maximum set point Read out above 10 C per 1 C 50 0 50 0 C 50 0 50 0 C 0 No 1 Yes 50 50 0 30 31 32 33 34 35 36 37 Alarm type 0 None 1 Absolute ...

Страница 4: ...4 Dimensions Connections Address VDH Products BV Tel 31 0 50 30 28 900 Produktieweg 1 Fax 31 0 50 30 28 980 9301 ZS Roden Email info vdhproducts nl The Netherlands Internet www vdhproducts nl ...

Отзывы: