background image

R

2800 LAURA LANE •  MIDDLETON, WI 53562 •  (800) 288-9383 •  FAX (608) 836-9044 •  www.tcsbasys.com

10

3.Press the PROGRAM SETUP button until you reach the

screen # 15 which allows you to set the occupant setpoint
adjustment limits. Change this to +/-20°F (11.1°C). Press
the PROGRAM SETUP button once more to store the
change. Then press the SERVICE STATUS button once to
exit the programming. 

4. Press the FAN SWITCH button to access the fan mode and

change the mode to AUTO. Press the FAN SWITCH
button once more to store the change.  Press the SYSTEM
SWITCH button to access the system mode and change the
mode to AUTO. Press the SYSTEM SWITCH button once
more to store the change.  

5. Verify that the thermostat is operating in the occupied

mode by making sure that the top LED is lit. If not, press
the OVERRIDE button. The LED should light up. 

6. Take note of the current temperature reading. Press the

WARMER (up) button. The setpoint adjustment screen
should now be showing. Press the WARMER button until
the heating setpoint is greater than the current temperature
by at least five degrees. The fan will come on. The heating
stage(s) will sequence on after 30 seconds. 

7. Press the cooler (down) button until the heating setpoint is

one degree less than the current temperature. The heating
stage(s) will sequence off. The fan will turn off 30 seconds
after the last heating stage. 

8. Press the cooler button until the cooling setpoint is less

than the current temperature by at least five degrees. The
fan will come on.  The cooling stage(s) will sequence on
after 30 seconds. 

9. Press the warmer button until the cooling setpoint is greater

than the current temperature by one degree. The cooling
stage(s) will sequence off. The fan will turn off 30 seconds
after the last cooling stage.

10. Go back to programming step #15 and set the setpoint

adjust limit back to the desired value. Make any other
changes in programming, clock, and schedule. Set the fan
and system modes to their desired settings.

11. IF using remote sensors, verify that the reading is correct.

If not, see 

Wrong Temperature Display

in

“Troubleshooting” section.

TROUBLESHOOTING

No Display

Check for 24 VAC on terminals “+24” and “-24”. Check the
cable connecting the cover to the base for a good connection.

Fan Does Not Come On

The fan is on whenever the fan LED is on. If the fan should
be on, but the fan LED is off, check the fan and system
switch modes, and the unoccupied fan mode in programming.
If the fan is off but the fan LED is on, check wiring. Short
terminals “R” to “G” and see if the fan comes on. This is a
check for a mechanical relay failure. 

Heating or Cooling Does Not Come On

At least one stage of heating is on whenever the  heating LED
is on, and at least one stage of cooling is on whenever the
cooling LED is on. If heating or cooling should be on but the
heating or cooling LED is off, check the fan and system
switch modes. Also, check the heating and cooling setpoints,
offsets and differentials, and the room temperature to be sure
heating or cooling should be on. If using outdoor air heating
and cooling lockouts, or discharge air high and low limits,
check their values to be sure heating or cooling is allowed. If
heating or cooling is off, but the corresponding LED is on,
check the wiring. Short terminals “R” to “W1”, “W2”, “Y1”,
“Y2”, or “B/O” and see if the heating or cooling comes on.
This is a check for a mechanical relay failure. 

Wrong Temperature Display

If any of the temperatures is reading slightly high or low,
there are two adjustment pots located in the cover to adjust
them. “T1” is for the room temperature and “T2” is for the
discharge air temperature. If the temperature is at a minimum
or maximum reading, check the sensor dipswitch positions.
(See setup instructions.) Check for wiring problems (opens or
shorts). A remote 1000 

:

sensor should read 1080 to 1090 

:

at room temperature. The built-in sensor should read 108 to
109 

:

at room temperature. 

Service LED is On

If the service LED is on, it may be for monitoring purposes
or it may indicate a critical problem. The first monitoring
screen accessed by pressing the service status button will
display why the light is on.

Outputs Will Not Shut Off

First check the room temperature and the setpoints and
determine whether the output should be on. There are delays
and minimum on and off times for the fan and heating and
cooling stages. Also, check the service status menus to verify
that the outputs are on. Turning the system to “off” will
instantly turn all outputs off. The thermostat can be reset by
pressing the system switch button and the service status
button simultaneously.  

SERVICE SCREENS

Continually pressing the service status button allows more
extensive monitoring. The screens are shown at right. 

*SZ1022N*

V 1.2

Содержание SZ1022N

Страница 1: ...ut economizers z Fan interlock safety option z Filter service input and indication z Equipment monitoring inputs and indication z External time clock input z Energy management input for setpoint shift...

Страница 2: ...hielded wire is used and the installation environment is free of electrical noise Sensor wire should be kept at least five feet away from line voltage wiring The SZ1022N or SZ1024N accept two remote s...

Страница 3: ...in the cover shown above connected with ribbon cable must be set in order to lock the user out of the program and or to set the clock and schedule Use the guide below to set these dipswitches for you...

Страница 4: ...g Screen Press the program setup button to access the following screens Access Code Entry Screen Will appear if access code is required for programming Use 248 as the default If the wrong code is ente...

Страница 5: ...for heat stage 1 First stage is normally 0 offset Heat Stage 1 Differential Screen Enter a differential value for heat stage 1 Heat Stage 2 Offset Screen Enter an offset value for heat stage 2 This sc...

Страница 6: ...his screen only appears if compressor 2 is enabled Compressor Stage 2 Differential Screen Enter a differential value for compressor stage 2 This screen only appears if compressor stage 2 is enabled Au...

Страница 7: ...creen Setting Clock and Schedule The SZ1022N and SZ1024N clock and schedule may be set through the display and keypad or with a PC For more information on programming through the PC consult the softwa...

Страница 8: ...set DI3 to time clock and close the contact when you want the room occupied such as with a switch or wind up timer If each occupancy period is about the same theaters meetings another option is to se...

Страница 9: ...rential consideration and ramps the setpoint when going from the unoccupied mode to the occupied mode At the beginning of the occupied mode the occupied setpoint will be reached many times without the...

Страница 10: ...e fan is on whenever the fan LED is on If the fan should be on but the fan LED is off check the fan and system switch modes and the unoccupied fan mode in programming If the fan is off but the fan LED...

Страница 11: ...e following screens Service Screen This message may be followed by any or all of the following CHECK FILTER CHECK FAN DISCHARGE HIGH DISCHARGE LOW or CHECK DI2 Discharge Air Temperature Screen Shows d...

Страница 12: ...mode is allowed by factory default To lock out access to system switching see programming step 5 SETTING CLOCK SCHEDULE The ability to set the clock and schedule is allowed by factory default An acces...

Страница 13: ...e heating setpoint is shifted down ADI 19 Seconds Internal time clock second 0 59 ADI 20 Minutes Internal time clock minute 0 59 ADI 21 DegF C Occupied heating setpoint 40 90 4 32 Occupied heating set...

Страница 14: ...s 4 per hour setpoint ramp prior to oc cupancy for both heating and cooling BD 7 Require access code 0 No 1 Yes Programming access from keypad for programming BD 8 Require access code 0 No 1 Yes Clock...

Страница 15: ...eck DI2 NOTE 1 The Service status point represents general Check status If this is point is 1 the user can find out the actual failing condition by polling point 38 to 42 If this point is 0 points 38...

Страница 16: ...DegF C Occupied heating setpoint 40 90 4 32 Occupied heating setpoint must be less than occupied cooling setpoint ADI 19 DegF C Unoccupied heating setpoint 40 90 4 32 Unoccupied heating setpoint must...

Страница 17: ...e access code 0 No 1 Yes Clock Schedule access from keypad for clock schedule BD 9 Enable compressor 2 0 disable 1 enable Disable unused stages recommended BD 10 Enable auxiliary heat 1 0 disable 1 en...

Страница 18: ...is 1 then by polling point 38 to 42 the user can find out actual failing condition If this point is 0 then points 38 to 42 will be also 0 NOTE 2 All of the ADI and BD points support the override funct...

Страница 19: ...R 2800 LAURA LANE MIDDLETON WI 53562 800 288 9383 FAX 608 836 9044 www tcsbasys com 19...

Страница 20: ...R 2800 LAURA LANE MIDDLETON WI 53562 800 288 9383 FAX 608 836 9044 www tcsbasys com 20 Rev 0305...

Отзывы: