Pointmap Table for SZ1022N (continued)
NPT
NPA
UNITS
POINT DESCRIPTION
RANGE/VALUE
ADDITIONAL NOTES
BD
21
Remote DI2 request
0=off, 1=on
BD
22
Remote DI3 request
0=off, 1=on
BD
23
Remote override request
0=off, 1=on
This is a permanent override.
BD
24
Remote Fan request
0=off, 1=on
BD
25
Heat stage 1 relay status
0=off, 1=on
Read only.
BD
26
Heat stage 2 relay status
0=off, 1=on
Read Only
BD
27
Cool stage 1 relay status
0=off, 1=on
Read only.
BD
28
Cool stage 2 relay status
0=off, 1=on
Read only.
BD
29
Fan relay status
0=off, 1=on
Read only.
BD
30
Stage 3 relay status
0=off, 1=on
Read only.
BD
31
Time clock relay status
0=off, 1=on
Read only.
BD
32
DI1 status
0=off, 1=on
Read only.
BD
33
DI2 status
0=off, 1=on
Read only.
BD
34
DI3 status
0=off, 1=on
Read only.
BD
35
Override status
0=off, 1=on
Read only.
BD
36
Device’s occupied status
0=Occupied
Read only.
1=Unoccupied
BD
37
Service status
0=OK, 1= fail
Read only. See Note 1.
BD
38
Fan interlock status
0= OK,
Read only. DI1 Fan Proving.
1= Fan interlock fail
BD
39
Filter service status
0=OK,
Read only. DI3 Filter Status.
1=Check filter
BD
40
Discharge air high limit
0=OK,
Read only. Discharge air function.
1= Above high limit
BD
41
Discharge air low limit
0=OK,
Read only. Discharge air function.
1= Below low limit
BD
42
DI2 service status
0=OK,
Read only. DI2 Service.
1= Check DI2
NOTE 1: The Service status point represents general Check status. If this is point is 1, the user can find out the actual failing
condition by polling point 38 to 42. If this point is 0, points 38 to 42 will also be 0.
NOTE 2: All of the ADI and BD points support the override function. The value overridden will be stored permanently, so the
status attribute will never have any override active status. Because none of these points support the override release
function, the controller will acknowledge the override release function but never release the value. The controller will
respond with NAK error N10 if the value for the override command is outside the limits for that point. Points that are
Read Only can not be overridden. The controller will acknowledge the override command, but the actual change will
never happen.
NOTE 3: All of the points in this map can be adjusted through the keypad except Read Only points and BD points 15 through 24.
In the case of loss of communications for 15 minutes (i.e., if the controller is not addressed for 15 minutes), the
controller will revert BD points 15 through 24 to zero value (make them all local requests).
NOTE 4: Communications are disabled when programming mode or clock/schedule mode is entered via the keypad. Entering
programming mode via the keypad can be disabled.
NOTE 5: If the temperature in programming step #4 is set to be displayed in degrees Fahrenheit, the values of ADI 7, ADI 21
through ADI 28 and ADI 32 will be Fahrenheit values. If the temperature is set to be displayed in degrees Celsius,
these ADI values will be in Celsius.