background image

R

2800 LAURA LANE •  MIDDLETON, WI 53562 •  (800) 288-9383 •  FAX (608) 836-9044 •  www.tcsbasys.com

16

Pointmap Table for SZ1024N (See page 13 for Pointmap Table for SZ1022N)

NPT

NPA

UNITS

POINT DESCRIPTION

RANGE/VALUE

ADDITIONAL NOTES

ADI

1

#

DI2 control mode

0=cool lockout 

See  "Setup" (page 8).

1=monitor 
2=service

ADI

2

#

DI3 control mode

0=filter service

See "Setup" (page 7).

1=external override
2=external timeclock

ADI

3

#

System mode

0=off,1=auto,

"System Switch" button on keypad.

3=cool, 2=heat
4=emergency heat

ADI

4

Day

Internal time clock "day"

0-6, mon to sunday

Day of Week.

ADI

5

Hours

Internal time clock "hours"

0-23

0-11 (AM), 12-23 (PM).

ADI

6

DegF (C)

Setpoint adjust limit from keypad

0-50 (0-28)

Limits keypad adjustment of occupied
heating and cooling setpoints. (See Note 5.)

ADI

7

DegF

Differential for compressor 1

0-50

ADI

8

DegF

Offset for compressor 1

0-50

ADI

9

DegF

Differential for compressor 2

0-50

ADI

10

DegF

Offset for compressor 2 

0-50

ADI

11

DegF

Diff. for auxiliary heat 1

0-50

ADI

12

DegF

Offset for auxiliary heat 1

0-50

ADI

13

DegF

Diff. for auxiliary heat 2

0-50

ADI

14

DegF

Offset for auxiliary heat 2 

0-50

ADI

15

DegF

Setpoint shift value

0-50

When DI2 is selected "Monitor", this is
number of degrees that the occupied
cooling setpoint is shifted up and the
heating setpoint is shifted down.

ADI

16

Seconds

Internal time clock "second"

0-59

ADI

17

Minutes

Internal time clock "minute"

0-59

ADI

18 

DegF (C)

Occupied heating setpoint 

40-90 (4-32)

Occupied heating setpoint must be less
than occupied cooling setpoint.

ADI

19 

DegF (C)

Unoccupied heating setpoint

40-90 (4-32)

Unoccupied heating setpoint must be 
less than unoccupied cooling setpoint.

ADI

20 

DegF (C)

Occupied cooling setpoint

40-90 (4-32)

ADI

21 

DegF (C)

Unoccupied cooling setpoint

40-90 (4-32)

ADI

22 

DegF (C)

Room temperature

40-90 (4-32)

Read only.  See Note 5.

ADI

23 

DegF (C)

Discharge air low limit

0-150 (-18-65)

Discharge air high limit must be greater
than discharge air low limit.

ADI

24 

DegF (C)

Discharge air high limit

0-150 (-18-65)

ADI

25 

DegF (C)

Discharge air temperature

0-150 (-18-65)

Read only.

ADI

26

Minutes

Override period

0-255

Unoccupied override time allowed.

ADI

27

Seconds

Power on delay time

0-255

Time before control begins on powerup.

ADI

28

Minutes

Remaining override time

0-255

Read Only. Time remaining before the 
override period expires.

ADI

29

DegF (C)

Current user setpoint adjust

-50-50 (-28-28)

Read Only. + or - amount the occupied
setpoint has been adjusted from actual
settings. (See Note 5.)

ADI

30

Minutes

Monday Occupied start time

0-1440

There are two occupied and two un-

for schedule A

occupied time periods allowed per day.

ADI

31

Minutes

Monday Occupied end time

0-1440

for schedule A

All times are measured in minutes from

ADI

32

Minutes

Monday Occupied start time

0-1440

midnight.

for schedule B

ADI

33

Minutes

Monday Occupied end time

0-1440

for schedule B

ADI

34

Tuesday

0-1440

ADI

35

Tuesday

0-1440

ADI

36

Tuesday

0-1440

ADI

37

Tuesday

0-1440

ADI

38

Wednesday

0-1440

ADI

39

Wednesday

0-1440

ADI

40

Wednesday

0-1440

Содержание SZ1022N

Страница 1: ...ut economizers z Fan interlock safety option z Filter service input and indication z Equipment monitoring inputs and indication z External time clock input z Energy management input for setpoint shift...

Страница 2: ...hielded wire is used and the installation environment is free of electrical noise Sensor wire should be kept at least five feet away from line voltage wiring The SZ1022N or SZ1024N accept two remote s...

Страница 3: ...in the cover shown above connected with ribbon cable must be set in order to lock the user out of the program and or to set the clock and schedule Use the guide below to set these dipswitches for you...

Страница 4: ...g Screen Press the program setup button to access the following screens Access Code Entry Screen Will appear if access code is required for programming Use 248 as the default If the wrong code is ente...

Страница 5: ...for heat stage 1 First stage is normally 0 offset Heat Stage 1 Differential Screen Enter a differential value for heat stage 1 Heat Stage 2 Offset Screen Enter an offset value for heat stage 2 This sc...

Страница 6: ...his screen only appears if compressor 2 is enabled Compressor Stage 2 Differential Screen Enter a differential value for compressor stage 2 This screen only appears if compressor stage 2 is enabled Au...

Страница 7: ...creen Setting Clock and Schedule The SZ1022N and SZ1024N clock and schedule may be set through the display and keypad or with a PC For more information on programming through the PC consult the softwa...

Страница 8: ...set DI3 to time clock and close the contact when you want the room occupied such as with a switch or wind up timer If each occupancy period is about the same theaters meetings another option is to se...

Страница 9: ...rential consideration and ramps the setpoint when going from the unoccupied mode to the occupied mode At the beginning of the occupied mode the occupied setpoint will be reached many times without the...

Страница 10: ...e fan is on whenever the fan LED is on If the fan should be on but the fan LED is off check the fan and system switch modes and the unoccupied fan mode in programming If the fan is off but the fan LED...

Страница 11: ...e following screens Service Screen This message may be followed by any or all of the following CHECK FILTER CHECK FAN DISCHARGE HIGH DISCHARGE LOW or CHECK DI2 Discharge Air Temperature Screen Shows d...

Страница 12: ...mode is allowed by factory default To lock out access to system switching see programming step 5 SETTING CLOCK SCHEDULE The ability to set the clock and schedule is allowed by factory default An acces...

Страница 13: ...e heating setpoint is shifted down ADI 19 Seconds Internal time clock second 0 59 ADI 20 Minutes Internal time clock minute 0 59 ADI 21 DegF C Occupied heating setpoint 40 90 4 32 Occupied heating set...

Страница 14: ...s 4 per hour setpoint ramp prior to oc cupancy for both heating and cooling BD 7 Require access code 0 No 1 Yes Programming access from keypad for programming BD 8 Require access code 0 No 1 Yes Clock...

Страница 15: ...eck DI2 NOTE 1 The Service status point represents general Check status If this is point is 1 the user can find out the actual failing condition by polling point 38 to 42 If this point is 0 points 38...

Страница 16: ...DegF C Occupied heating setpoint 40 90 4 32 Occupied heating setpoint must be less than occupied cooling setpoint ADI 19 DegF C Unoccupied heating setpoint 40 90 4 32 Unoccupied heating setpoint must...

Страница 17: ...e access code 0 No 1 Yes Clock Schedule access from keypad for clock schedule BD 9 Enable compressor 2 0 disable 1 enable Disable unused stages recommended BD 10 Enable auxiliary heat 1 0 disable 1 en...

Страница 18: ...is 1 then by polling point 38 to 42 the user can find out actual failing condition If this point is 0 then points 38 to 42 will be also 0 NOTE 2 All of the ADI and BD points support the override funct...

Страница 19: ...R 2800 LAURA LANE MIDDLETON WI 53562 800 288 9383 FAX 608 836 9044 www tcsbasys com 19...

Страница 20: ...R 2800 LAURA LANE MIDDLETON WI 53562 800 288 9383 FAX 608 836 9044 www tcsbasys com 20 Rev 0305...

Отзывы: