Pointmap Table for SZ1024N (See page 13 for Pointmap Table for SZ1022N)
NPT
NPA
UNITS
POINT DESCRIPTION
RANGE/VALUE
ADDITIONAL NOTES
ADI
1
#
DI2 control mode
0=cool lockout
See "Setup" (page 8).
1=monitor
2=service
ADI
2
#
DI3 control mode
0=filter service
See "Setup" (page 7).
1=external override
2=external timeclock
ADI
3
#
System mode
0=off,1=auto,
"System Switch" button on keypad.
3=cool, 2=heat
4=emergency heat
ADI
4
Day
Internal time clock "day"
0-6, mon to sunday
Day of Week.
ADI
5
Hours
Internal time clock "hours"
0-23
0-11 (AM), 12-23 (PM).
ADI
6
DegF (C)
Setpoint adjust limit from keypad
0-50 (0-28)
Limits keypad adjustment of occupied
heating and cooling setpoints. (See Note 5.)
ADI
7
DegF
Differential for compressor 1
0-50
ADI
8
DegF
Offset for compressor 1
0-50
ADI
9
DegF
Differential for compressor 2
0-50
ADI
10
DegF
Offset for compressor 2
0-50
ADI
11
DegF
Diff. for auxiliary heat 1
0-50
ADI
12
DegF
Offset for auxiliary heat 1
0-50
ADI
13
DegF
Diff. for auxiliary heat 2
0-50
ADI
14
DegF
Offset for auxiliary heat 2
0-50
ADI
15
DegF
Setpoint shift value
0-50
When DI2 is selected "Monitor", this is
number of degrees that the occupied
cooling setpoint is shifted up and the
heating setpoint is shifted down.
ADI
16
Seconds
Internal time clock "second"
0-59
ADI
17
Minutes
Internal time clock "minute"
0-59
ADI
18
DegF (C)
Occupied heating setpoint
40-90 (4-32)
Occupied heating setpoint must be less
than occupied cooling setpoint.
ADI
19
DegF (C)
Unoccupied heating setpoint
40-90 (4-32)
Unoccupied heating setpoint must be
less than unoccupied cooling setpoint.
ADI
20
DegF (C)
Occupied cooling setpoint
40-90 (4-32)
ADI
21
DegF (C)
Unoccupied cooling setpoint
40-90 (4-32)
ADI
22
DegF (C)
Room temperature
40-90 (4-32)
Read only. See Note 5.
ADI
23
DegF (C)
Discharge air low limit
0-150 (-18-65)
Discharge air high limit must be greater
than discharge air low limit.
ADI
24
DegF (C)
Discharge air high limit
0-150 (-18-65)
ADI
25
DegF (C)
Discharge air temperature
0-150 (-18-65)
Read only.
ADI
26
Minutes
Override period
0-255
Unoccupied override time allowed.
ADI
27
Seconds
Power on delay time
0-255
Time before control begins on powerup.
ADI
28
Minutes
Remaining override time
0-255
Read Only. Time remaining before the
override period expires.
ADI
29
DegF (C)
Current user setpoint adjust
-50-50 (-28-28)
Read Only. + or - amount the occupied
setpoint has been adjusted from actual
settings. (See Note 5.)
ADI
30
Minutes
Monday Occupied start time
0-1440
There are two occupied and two un-
for schedule A
occupied time periods allowed per day.
ADI
31
Minutes
Monday Occupied end time
0-1440
for schedule A
All times are measured in minutes from
ADI
32
Minutes
Monday Occupied start time
0-1440
midnight.
for schedule B
ADI
33
Minutes
Monday Occupied end time
0-1440
for schedule B
ADI
34
Tuesday
0-1440
ADI
35
Tuesday
0-1440
ADI
36
Tuesday
0-1440
ADI
37
Tuesday
0-1440
ADI
38
Wednesday
0-1440
ADI
39
Wednesday
0-1440
ADI
40
Wednesday
0-1440