R
W1 W2 Y1 Y2
Time Clock
Output
Packaged Unit/Heat Pump Terminations
1
For communication wiring, use
twisted, shielded 18 AWG.
Must be run separately
2
Dry momentary contact.
Must not be powered.
3
24 VAC transformer. See
powering instructions.
4
Dry contact. Must not be powered.
1
3
4
4
G
4
5
Sensor input wiring 18 AWG,
twisted, shielded pair.
5
5
Zone/Return
Air Temp
Discharge
Air Temp
When multiple TCS devices are
using a single transformer, the
polarity of the power wiring must
be maintained because all TCS
devices are half-wave rectified
and have common return paths.
N2 Bus
6
Up to nominal 28 VAC from
equipment transformer .
6
2
R
2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com
2
Wiring
The SZ1022N and SZ1024N use standard terminal
designations for wiring. See diagram below.
REMOTE SENSOR WIRING
Use 18 AWG shielded twisted-pair grounded at the sensor
mounting location. Sensor wiring runs of up to 250 feet are
attainable if properly shielded wire is used and the installation
environment is free of electrical noise. Sensor wire should be
kept at least five feet away from line voltage wiring.
The SZ1022N or SZ1024N accept two remote sensors.
Consult the TS Series Temperature Sensor Submittal Data
sheet for a complete listing of packaging and application
styles. When using TCS/Basys Controls three-wire sensors,
use the black and red leads and either clip or twist off the
white lead. Make sure that the dip switches are set for the
sensors you are using.
POWERING THE SZ1022N AND SZ1024N
The SZ1022N and SZ1024N are powered from 24 VAC +/-
20%.
Caution:
Do not connect to 120 VAC.
If wiring for communications, dedicated power must be used
to power the SZ1022N and SZ1024N. Several “S” Series
thermostats may be powered from the same transformer,
provided that the transformer has sufficient power. (SZ1020
Series thermostats require 8 VA @ 24 VAC.)
When the SZ1022N or SZ1024N are used as stand-alone
thermostats without communications, the unit transformer
may be used to power it. To do this, install a jumper between
the “R” and “+24” terminals. The “24-” terminal must then
be connected to the common side of the unit transformer.