background image

R

2800 LAURA LANE •  MIDDLETON, WI 53562 •  (800) 288-9383 •  FAX (608) 836-9044 •  www.tcsbasys.com

9

STAGE OUTPUT PARAMETERS

The SZ1022N will control up to two stages each of heating
and cooling, with a fifth stage that may be assigned as a third
stage for either. The SZ1024N will control up to two
compressor stages, and up to two stages of auxiliary heat. It is
recommended that all unused stages be disabled. 

For each stage, you may specify an offset and a differential
value. This allows you to adjust the operation of the
thermostat to fit your equipment to the building load. The
offset value is the amount away from the setpoint a stage will
turn off. By assigning a stage a value other than zero, you
“anticipate” that the residual heat or cooling in the duct or the
other stages will bring the temperature back to setpoint. In
most cases, the first stage is set to zero. The differential value

is the difference between the on and off points. This value
depends on the load and on the equipment size. If the
equipment is large for the load, you may want to make this
value as high as 5 to prevent equipment cycling. If the
equipment is small compared to the load, or if tight control is
desired, you may want to make this value as low as 1. 

The fact that the stages are configurable allows unused stages
to be set to activate physical alarms if desired. 

The SZ1022N and SZ1024N also have a P+I option. Without
enabling this option, stages turn on and off based on
temperature vs. setpoint alone, as described above. By
enabling this option, you allow a time factor to be added. This
is useful when you are forced to have a large differential due
to equipment size. At times when the building load is low, the
temperature could potentially sit a few degrees off setpoint
for some time. With the time factor added, the thermostat
would compensate for this, turning on the equipment even
though the temperature had not reached the limits described
above. 

DI2 COOL LOCKOUT

DI2 may be set as cool lockout for operation with
economizers. An outdoor temperature switch may be wired in
such that when DI2 is closed, the second and third stages of
cooling are disabled.  

SMART RECOVERY

“Smart Recovery” may be enabled to insure occupant comfort
while saving money. It takes the building load into

Heat

Setpoint

Cool

Setpoint

ON

ON

ON

OFF

OFF

OFF

OFF

Differential

Differential

Offset

Offset

Differential

Differential

consideration and ramps the setpoint when going from the
unoccupied  mode to the occupied mode. At the beginning of
the occupied mode, the occupied setpoint will be reached,
many times without the need for the second stage to come on.
This feature is automatically disabled when DI3 is set to
external time clock. 

AUXILIARY OUTPUT

An auxiliary relay output is available to output a signal based
on the occupancy status. It is commonly used with an
economizer minimum position control, or to signal an outdoor
air damper to open in occupied times in lieu of an economizer.
It may also be used for lighting or hot water heaters. Keep in
mind that although it is an isolated relay (separate common
terminal), it is rated at 2A@24 VAC. For loads that exceed this,
use an external relay. It may be set to be open (N.O.) or closed
(N.C.) when the thermostat is operating in the occupied mode,
and will be the opposite during the unoccupied mode. 

BUILT-IN DELAYS

The SZ1022N and SZ1024N have delays built into the
programming sequences to protect equipment. The fan has a
minimum on and off time of 30 seconds. When the fan is in
AUTO or COOL mode, it will come on 30 seconds before the
heating or cooling stages are allowed to sequence on, and
remain on for 30 seconds after the heating or cooling stages
sequence off. Each stage has a minimum on and off time of
two minutes. There is a minimum of two minutes between
when one stage turns on until the next stage is allowed to turn
on, as well as when one stage turns off until the next stage is
allowed to turn off.

DELAY ON POWERUP

The SZ1022N and SZ1024N have an adjustable delay on
powerup. When several thermostats are used at one location,
and the power goes out, most thermostats turn all of the units
back on at the same time on regain of power, creating a peak.
The thermostat allows you to set a value, in seconds, where
no outputs are allowed to turn on for that length of time on
powerup. Setting each unit to a different delay allows you to
soft start your system, and thus prevent this peak.

Checkout & Troubleshooting         

CHECKOUT

Note:

The fan has a minimum on and off time of 30 seconds.

The heating and cooling stages have a minimum on and off
time of 2 minutes. 

You may verify the status of heating and cooling stages and
fan in monitoring screens 5, 6, and 7, which are accessed by
pressing the SERVICE STATUS button. 

1. Verify all wiring prior to powering the thermostat.
2. Turn power on. The thermostat will display a momentary

screen with the model number , and then the main
monitoring screen with the time, day, and current
temperature. 

Содержание SZ1022N

Страница 1: ...ut economizers z Fan interlock safety option z Filter service input and indication z Equipment monitoring inputs and indication z External time clock input z Energy management input for setpoint shift...

Страница 2: ...hielded wire is used and the installation environment is free of electrical noise Sensor wire should be kept at least five feet away from line voltage wiring The SZ1022N or SZ1024N accept two remote s...

Страница 3: ...in the cover shown above connected with ribbon cable must be set in order to lock the user out of the program and or to set the clock and schedule Use the guide below to set these dipswitches for you...

Страница 4: ...g Screen Press the program setup button to access the following screens Access Code Entry Screen Will appear if access code is required for programming Use 248 as the default If the wrong code is ente...

Страница 5: ...for heat stage 1 First stage is normally 0 offset Heat Stage 1 Differential Screen Enter a differential value for heat stage 1 Heat Stage 2 Offset Screen Enter an offset value for heat stage 2 This sc...

Страница 6: ...his screen only appears if compressor 2 is enabled Compressor Stage 2 Differential Screen Enter a differential value for compressor stage 2 This screen only appears if compressor stage 2 is enabled Au...

Страница 7: ...creen Setting Clock and Schedule The SZ1022N and SZ1024N clock and schedule may be set through the display and keypad or with a PC For more information on programming through the PC consult the softwa...

Страница 8: ...set DI3 to time clock and close the contact when you want the room occupied such as with a switch or wind up timer If each occupancy period is about the same theaters meetings another option is to se...

Страница 9: ...rential consideration and ramps the setpoint when going from the unoccupied mode to the occupied mode At the beginning of the occupied mode the occupied setpoint will be reached many times without the...

Страница 10: ...e fan is on whenever the fan LED is on If the fan should be on but the fan LED is off check the fan and system switch modes and the unoccupied fan mode in programming If the fan is off but the fan LED...

Страница 11: ...e following screens Service Screen This message may be followed by any or all of the following CHECK FILTER CHECK FAN DISCHARGE HIGH DISCHARGE LOW or CHECK DI2 Discharge Air Temperature Screen Shows d...

Страница 12: ...mode is allowed by factory default To lock out access to system switching see programming step 5 SETTING CLOCK SCHEDULE The ability to set the clock and schedule is allowed by factory default An acces...

Страница 13: ...e heating setpoint is shifted down ADI 19 Seconds Internal time clock second 0 59 ADI 20 Minutes Internal time clock minute 0 59 ADI 21 DegF C Occupied heating setpoint 40 90 4 32 Occupied heating set...

Страница 14: ...s 4 per hour setpoint ramp prior to oc cupancy for both heating and cooling BD 7 Require access code 0 No 1 Yes Programming access from keypad for programming BD 8 Require access code 0 No 1 Yes Clock...

Страница 15: ...eck DI2 NOTE 1 The Service status point represents general Check status If this is point is 1 the user can find out the actual failing condition by polling point 38 to 42 If this point is 0 points 38...

Страница 16: ...DegF C Occupied heating setpoint 40 90 4 32 Occupied heating setpoint must be less than occupied cooling setpoint ADI 19 DegF C Unoccupied heating setpoint 40 90 4 32 Unoccupied heating setpoint must...

Страница 17: ...e access code 0 No 1 Yes Clock Schedule access from keypad for clock schedule BD 9 Enable compressor 2 0 disable 1 enable Disable unused stages recommended BD 10 Enable auxiliary heat 1 0 disable 1 en...

Страница 18: ...is 1 then by polling point 38 to 42 the user can find out actual failing condition If this point is 0 then points 38 to 42 will be also 0 NOTE 2 All of the ADI and BD points support the override funct...

Страница 19: ...R 2800 LAURA LANE MIDDLETON WI 53562 800 288 9383 FAX 608 836 9044 www tcsbasys com 19...

Страница 20: ...R 2800 LAURA LANE MIDDLETON WI 53562 800 288 9383 FAX 608 836 9044 www tcsbasys com 20 Rev 0305...

Отзывы: