Pointmap Table for SZ1022N (See page 16 for Pointmap Table for SZ1024N)
NPT
NPA
UNITS
POINT DESCRIPTION
RANGE/VALUE
ADDITIONAL NOTES
ADI
1
#
DI2 control mode
0=cool lockout
See Setup (page 8).
1=monitor
2=service
ADI
2
#
DI3 control mode
0=filter service
See Setup (page 7).
1=external override
2=external time clock
ADI
3
#
Occupied Fan mode
0=on, 1=cool, 2=auto
Fan Switch button on keypad.
ADI
4
#
System mode
0=off,1=auto,2=heat
System Switch button on keypad.
3=cool
ADI
5
Day
Internal time clock day
0-6, mon to sunday
Day of Week.
ADI
6
Hours
Internal time clock hours
0-23
0-11 (AM), 12-23 (PM).
ADI
7
DegF (C)
Setpoint adjust limit from keypad
0-50 (0-28)
Limits keypad adjustment of occupied
heating and cooling setpoints. See note 5.
ADI
8
DegF
Differential for cool stage 1
0-50
ADI
9
DegF
Offset for cool stage 1
0-50
ADI
10
DegF
Differential for cool stage 2
0-50
ADI
11
DegF
Offset for cool stage 2
0-50
ADI
12
DegF
Differential for heat stage 1
0-50
ADI
13
DegF
Offset for heat stage 1
0-50
ADI
14
DegF
Differential for heat stage 2
0-50
ADI
15
DegF
Offset for heat stage 2
0-50
ADI
16
DegF
Differential for stage 3
0-50
Stage 3 can do either Heating or Cooling.
ADI
17
DegF
Offset for stage 3
0-50
ADI
18
DegF
Setpoint shift value
0-50
When DI2 is selected Monitor, this is
number of degrees that the occupied
cooling setpoint is shifted up and the
heating setpoint is shifted down.
ADI
19
Seconds
Internal time clock second
0-59
ADI
20
Minutes
Internal time clock minute
0-59
ADI
21
DegF (C)
Occupied heating setpoint
40-90 (4-32)
Occupied heating setpoint must be less
than occupied cooling setpoint.
ADI
22
DegF (C)
Unoccupied heating setpoint
40-90 (4-32)
Unoccupied heating setpoint must be
less than unoccupied cooling setpoint.
ADI
23
DegF (C)
Occupied cooling setpoint
40-90 (4-32)
ADI
24
DegF (C)
Unoccupied cooling setpoint
40-90 (4-32)
ADI
25
DegF (C)
Room temperature
40-90 (4-32)
Read only. See Note 5.
ADI
26
DegF (C)
Discharge air low limit
0-150 (-18-65)
Discharge air high limit must be greater
than discharge air low limit.
ADI
27
DegF (C)
Discharge air high limit
0-150 (-18-65)
ADI
28
DegF (C)
Discharge air temperature
0-150 (-18-65)
Read only.
ADI
29
Minutes
Override period
0-255
Unoccupied override time allowed.
ADI
30
Seconds
Power on delay time
0-255
Time before control begins on powerup.
ADI
31
Minutes
Remaining override time
0-255
Read Only. Time remaining before the
override period expires.
ADI
32
DegF (C)
Current user setpoint adjust
-50-50, (28-28)
Read Only. + or - amount the occupied
setpoint has been adjusted from actual
settings. (See Note 5.)
ADI
33
Minutes
Monday Occupied start time
0-1440
There are two occupied and two un-
for schedule A
occupied time periods allowed per day.
ADI
34
Minutes
Monday Occupied end time
0-1440
for schedule A
All times are measured in minutes from
ADI
35
Minutes
Monday Occupied start time
0-1440
midnight.
for schedule B
ADI
36
Minutes
Monday Occupied end time
0-1440
for schedule B
ADI
37
Tuesday
0-1440
ADI
38
Tuesday
0-1440
ADI
39
Tuesday
0-1440