© COPYRIGHT 2016 ENTERGIZE, LLC. ALL RIGHTS RESERVED.
P/N 71969 3220-2345 REV 00=E
1
SET CLOCK, YEAR, MONTH, DAY
1.
Press ▲/ ▼ to select 12 / 24 Hr mode, then press
Next
.
2. Press ▲/ ▼to select hou
r
, then press
Next
.
3.
Press ▲/▼to select minutes, then press
Next
.
4. Press ▲/ ▼ to select current yea
r
, then press
Next
.
5.
Press ▲/ ▼ to select current month, press
Next
.
6.
Press ▲/ ▼ to select the calendar day numbe
r.
7. Press
Done
to complete operation.
note: Select
More >
Clock
, to access after setup.
ACCESS SERVICE MENUS
1.
Hold lower right and left keys for fi
ve seconds.
2.
Press
Next
or
Go Back
to select a Service Menu.
3.
Press ▲/ ▼ to select option.
4.
Press
Done
when complete.
CONFIGURE SERVICE MENUS
The following Service Menus (SM) commonly require
confi
guration. Please verify that these are set for your
specifi
c application.
additional confi
guration may be
required. refer to
T
able 2 for all available Service Menus.
•
SM 100 = Programmable or nonprogrammable
• SM 1
10 = System
T
ype
•
SM 121 = number of fan Speeds
•
SM 130 = reversing
v
alve
•
SM 135 = W1 heat output no or nc
•
SM 170 = remote Sensors
•
SM 265 = Single or dual Setpoint operation
WIRE TERMINAL DESIGNATIONS
1.
connect wires for appropriate system type (
T
able 1).
WARNING: DISCONNECT POWER BEFORE BEGINNING INSTALLATION.
• CAUTION: Use copper wire only. Insulate or wire-nut all unused leads.
• Use care to avoid electrostatic discharge to thermostat
• CAUTION: Do not connect unused wires together
• ALL ELECTRICAL LOADS MUST BE CONNECTED TO TERMINAL C
(24 VAC).
TABLE 1. TERMINAL BLOCK
Fan Coil (Conventional)
Heat Pump
C
24 VAC, Unswitched side
C
24 VAC, Unswitched side
W1
Stage 1 Heat
B/O
Reversing Valve
W2
Stage 2 Heat
AUX
Auxiliary Heat (Stage 2 or 3)
G
FAN High
G
FAN High
A
FAN Medium
A
FAN Medium
E
FAN Low
E
FAN Low
Y1
Stage 1 Cool
Y1
Compressor Stage 1
Y2
Stage 2 Cool
Y2
Compressor Stage 2
RH
24 VAC Power for heating,
switched side
RH
24 VAC Power for heating,
switched side
RC
24 VAC Power for cooling,
switched side
RC
24 VAC Power for cooling,
switched side
SC
Sensor Common
SC
Sensor Common
S1
Indoor Remote Sensor
S1
Indoor Remote Sensor
S2
Occupancy Sensor
S2
Occupancy Sensor
S3
Seasonal Changeover Switch
OPEN=Cooling in Summer
CLOSED=Heating in Winter
S3
NA
▲
!
24 VAC Switched Side
OPEN= Summer CLOSED = Winter
C
WI
Y1
G
A
E
RH
RC
SC
S1
S2
S3
OCC Sensor
Aquastat
FAN LO
FAN MED
FAN HIGH
Cool Valve
Heat Valve
Sensor Common
Remote Sensor
24 VAC Unswitched
24 VAC
TYPICAL FAN COIL
WIRING DIAGRAM
5
4
1
3
2
QUICK START GUIDE
PERFORMANCE PRO MULTI-FAN
OCCUPANCY THERMOSTAT
NOTE:
Display of
Clock is not
available when
for non-
programmable
operation.
Service
Menu
Current
option
FAN HIGH
FAN MED
FAN LOW
1.
Press the
Fan
button to
select speed/operation.
2.
Press
Done
when complete.
fan Speed is noted as
follows:
on = continuous fan operation
AUTO = Fan Cycles with Heating
and Cooling
FAN SPEED
SELECTION
6