background image

© COPYRIGHT 2016 ENTERGIZE, LLC.  ALL RIGHTS RESERVED.      

P/N 71969 3220-2345  REV 00=E

1

SET CLOCK, YEAR, MONTH, DAY

1. 

Press ▲/ ▼ to select 12 / 24 Hr mode, then press 

Next

2. Press ▲/ ▼to select hou

r

, then press 

Next

.  

3. 

Press ▲/▼to select minutes, then press 

Next

4. Press ▲/ ▼ to select current yea

r

, then press 

Next

5. 

Press ▲/ ▼ to select current month, press 

Next

.

6. 

Press ▲/ ▼ to select the calendar day numbe

r. 

7. Press 

Done

 to complete operation. 

note: Select 

More >

 

Clock

, to access after setup. 

ACCESS SERVICE MENUS

1. 

Hold lower right and left keys for fi

 

ve seconds. 

2. 

Press 

Next

 

or

 

Go Back

 

to select a Service Menu.

3. 

Press ▲/ ▼ to select option. 

4. 

Press 

Done

 when complete. 

CONFIGURE SERVICE MENUS

The following Service Menus (SM) commonly require 

confi

 

guration. Please verify that these are set for your 

specifi

 

c application.

 

additional confi

 

guration may be 

required. refer to

 T

able 2 for all available Service Menus. 

• 

SM 100 = Programmable or nonprogrammable

•  SM 1

10 = System

 T

ype

• 

SM 121 = number of fan Speeds

• 

SM 130 = reversing 

v

alve

• 

SM 135 = W1 heat output no or nc

• 

SM 170 = remote Sensors

• 

SM 265 = Single or dual Setpoint operation

WIRE TERMINAL DESIGNATIONS

1. 

connect wires for appropriate system type (

T

able 1). 

WARNING: DISCONNECT POWER BEFORE BEGINNING INSTALLATION.

•  CAUTION: Use copper wire only. Insulate or wire-nut all unused leads.

•  Use care to avoid electrostatic discharge to thermostat 

•  CAUTION: Do not connect unused wires together

•  ALL ELECTRICAL LOADS MUST BE CONNECTED TO TERMINAL C 

  (24 VAC).

TABLE 1. TERMINAL BLOCK  

Fan Coil (Conventional) 

Heat Pump

C

24 VAC, Unswitched side 

C

24 VAC, Unswitched side 

W1

Stage 1 Heat

B/O

Reversing Valve

W2

Stage 2 Heat

AUX

Auxiliary Heat (Stage 2 or 3)

G

FAN High

G

FAN High

A

FAN Medium

A

FAN Medium

E

FAN Low

E

FAN Low

Y1

Stage 1 Cool

Y1

Compressor Stage 1

Y2

Stage 2 Cool

Y2

Compressor Stage 2

RH

24 VAC Power for heating, 

switched side

RH

24 VAC Power for heating, 

switched side

RC

24 VAC Power for cooling, 

switched side

RC

24 VAC Power for cooling, 

switched side

SC

Sensor Common

SC

Sensor Common

S1

Indoor Remote Sensor

S1

Indoor Remote Sensor

S2

Occupancy Sensor

S2

Occupancy Sensor

S3

Seasonal Changeover Switch

OPEN=Cooling in Summer

CLOSED=Heating in Winter

S3

NA

▲ 

!

24 VAC Switched Side

OPEN= Summer CLOSED = Winter

C

WI
Y1

G
A

E

RH

RC
SC

S1
S2
S3

OCC Sensor

Aquastat

FAN LO

FAN MED

FAN HIGH

Cool Valve

Heat Valve

Sensor Common

Remote Sensor

24 VAC Unswitched

24 VAC

TYPICAL FAN COIL 

WIRING DIAGRAM

5

4

1

3

2

QUICK START GUIDE 

PERFORMANCE PRO MULTI-FAN

OCCUPANCY THERMOSTAT

NOTE: 

Display of 

Clock is not 

available when 

for non-

programmable 

operation. 

Service 

Menu

Current 

option

FAN HIGH
FAN MED 
FAN LOW 

1. 

Press the 

Fan

 button to 

select speed/operation.

2. 

Press 

Done

 when complete.

fan Speed is noted as 

follows:

on = continuous fan operation

AUTO = Fan Cycles with Heating 

and Cooling

FAN SPEED 

SELECTION

6

Содержание T8532OCC

Страница 1: ...ectrostatic discharge to thermostat CAUTION Do not connect unused wires together ALL ELECTRICAL LOADS MUST BE CONNECTED TO TERMINAL C 24 VAC TABLE 1 TERMINAL BLOCK Fan Coil Conventional Heat Pump C 24 VAC Unswitched side C 24 VAC Unswitched side W1 Stage 1 Heat B O Reversing Valve W2 Stage 2 Heat AUX Auxiliary Heat Stage 2 or 3 G FAN High G FAN High A FAN Medium A FAN Medium E FAN Low E FAN Low Y1...

Страница 2: ...F 18 to 49 C MENU FEATURE OPTIONS STD DEFAULT DESCRIPTION COMMENTS 100 Schedule Format 0 3 1 Select the schedule format on the T8000 Series Menu not available on non programmable thermostats NOTE Set the clock before changing to non progammable 0 nonprogrammable 1 programmable 2 5 1 1 schedule 3 5 2 schedule 101 Daylight Saving Time 0 1 0 Select daylight saving time as it follows standard format i...

Страница 3: ...etpoint thermostat will Heat to when in Setback mode Off sets Heating to 45F Setback 0 Off 50 82 F 11 27 C 320 Setback High Off 58 90 F 78 F Temperature setpoint thermostat will Cool to when in Setback mode Off sets Cooling to 150F in Setback 0 Off disabled 58 90 F 11 32 C 325 Occupied Sensor Operation 0 1 1 0 Disabled 1 Occupancy Operation ON 326 Occupied Timer Duration 30 min 1 2 4 6 8 16 20 24 ...

Страница 4: ...nd 502 501 Intermittent Fan On Time 1 60 minutes 5 minutes 502 Intermittent Fan Off Time 0 60 minutes 25 minutes A selection of 0 will result in continuous Fan 520 Default Display Icons 0 4 0 Select icons that will be displayed in the Default Display screen 0 Time Temp SP 1 Time Temp 2 Time only 3 Temp only 4 No Display 530 Revision displayed 540 Factory Default Reset 0 1 0 When Enable is selected...

Отзывы: