5.10 Communication Test
Verify if communication can be established between the main controller and its exter-
nal modules. The message “found” is displayed if communication is correct; the message
“????” is displayed if the controller cannot communicate with the chosen module. In
this case, make sure the module is properly identified with its jumpers or dip switches
(refer to the wiring diagram).
Select
11. Installation *
8. Communication test
* Accessible from the installer mode (s. 5.2).
• Select the module that needs to be
tested then press Enter. The communi-
cation status between the main
controller and this module is displayed.
5.11 Version
This menu displays the version number of
your controller. This piece of information is
useful to get technical support that is
adapted to your specific controller.
Select
11. Installation *
9. Version
* Accessible from the installer mode (s. 5.2).
Main Menu
10.
Alarm acknowledge
11.
Installation
Installation
7.
Scale calibration
8.
Communication test
Scale calibration
Exit: Press BACK
Change: Press Modify
Press to Select an item
Module ID
5
Communication status
found
Main Menu
10.
Alarm acknowledge
11.
Installation
Installation
8.
Communication test
9.
Version
Exit: Press BACK
Eco II Feeding
SETTINGS V. X.X
PCXX
33
ECO II FEEDING rev.06
ECO II FEEDING
• Valve Module ID:
Select on which relay panel the scale valve is connected; the relay panel is
identified by its ID number (ID #4 to ID #19). Tables are available at the end of
this manual to write down the identification number of each module.
• Valve Output #:
Select on which relay the scale valve is connected (relay1-16). If the output is
connected to relays 17-32 of a 32 output relay panel, select on which relay of
the second 16-relay strip the output is connected; i.e., relay 17=1, relay 18=2...
relay 32=16. Refer to section 5.9 for further information
• Receiving Hopper’s Proximity Sensor ID
Select on which PSM-8 module the receiving hopper’s proximity switch is
connected; the PSM-8 module is identified by its ID number (ID #20 to ID #44).
Tables are available at the end of this manual to write down the identification
number of each module.
• Receiving Hopper’s Proximity Sensor’s Input Number
Select on which input of the PSM-8 module the receiving hopper’s proximity
sensor is connected (input 1-8).
• Hopper Empty Delay
Select the time period that is required for feed to evacu-
ate from the receiving hopper from the moment the
proximity sensor stops detecting feed.
Hopper
Empty
Delay