ECO II FEEDING rev.06

ECO II FEEDING

LED

MEANING

POWER ON

The CDM-1 module is correctly powered up.

CURRENT OVERLOAD

Turns on when the loop motor's current consumption 
exceeds the maximum current limit for the Over Current 
Delay. Refer to section 5.6 to fix this delay. When this 
type of alarm occurs, the system stops operating. The 
problem needs to be fix.

SAFETY SWITCH

Turns on when the drive unit's safety switch is reached.

FEED SWITCH

Turns on if the loop's proximity switch detects feed.  
Flashes during the proximity switch's bypass delay. Refer 
to section 5.6 for further information. 

FEEDER

Turns on when the feeder is running

ARROW KEYS:

Arrow keys are used to navigate within the different menus. They  are also used to

adjust a parameter value when it is flashing on the display.

ENTER / MODIFY BUTTON:

- To enter in a menu:

Pressing this key gives access to the selected menu.

- To modify a parameter:

Press the modify key once the desired parameter is selected. The parameter

starts flashing, which means that it can now be adjusted with the arrow keys.

Refer to section 4.2 for further information on the parameters’ adjustment.

BACK BUTTON

:

This key is used to return to the previous menu.

CDM-1 MODULES:

CDM-1 modules are used to drive feeder mo-

tors in a closed-loop feeding system.

Pilot Lights:

The following table gives the meaning

of each status LED of CDM-1 modules.

Manual Switch:

Select “On” or “Off” to manually start or

stop the feeder connected to the CDM-

1. Select “Auto” for the feeder to run in

automatic mode.

MANUAL SWITCH
ON  / OFF  / AUTO

51

ECO II FEEDING  rev.06

ECO II FEEDING

• Bin #

Select which ingredient is distributed to the selected drop.

* Available if blends & blend curves are disabled, and if more than one bin is enabled in the installation

setup (s. 5.3).

• Blend curve

Select which blend curve the drop uses.

* Available if a blend curve is enabled in the installation setup (s. 5.3).

• Bin %

Shows the constitution of the feed blend that is currently being delivered to

the selected drop. This value is displayed for information purpose only, it

cannot be modified.

* Available if blends and blend curves are enabled in the installation setup (s. 5.3).

• Real animal weight

Enter the real weight of the animals that are being served by the selected drop.

The dosage and feed type are automatically adjusted if the real weight differs

from the theoretical weigh. 

This value must frequently be posted 

for the pigs

to receive a feed type and dosage that suit their current weight.

• Dosage Correction (%)

This function allows adjusting feed dosages within a curve. This avoids modi-

fying each point individually when dosage corrections need to be made.

* Available if the “Continuous Feeding” option is disabled in the installation setup (s. 5.3).

• Feed during cycles #1-6

Select feed cycles that are used for the selected drop.

* Available if the “Active feed cycles in curve” and “Continuous Feeding” options are disabled in the installa-

tion setup (s. 5.3).

Содержание ECO II FEEDING

Страница 1: ...REV 06 M 890 00375 rev 06 TARGET ECO II FEEDING Complete Feed Weighing and Distribution System for Hogs USER S MANUAL...

Страница 2: ...l is complete accurate and up to date The information contained in it is however subject to change without notice due to further developments FOR CUSTOMER USE Enter the serial number located on the si...

Страница 3: ...y Step Guide 21 2 5 1 Connections 21 2 5 2 Installation Settings 22 2 5 3 Feed Distribution Settings 23 3 MOUNTING INSTRUCTIONS 24 3 1 Installing the Controller on the Wall 24 3 2 Connections 24 3 2 1...

Страница 4: ...r 38 Flexible auger 38 Mixer 32 Principle of operation 42 Scale valve 33 Template 65 Relay modules Communication test 44 ID numbers 42 Reset time of 31 S Scale Actual weight compensation Activation 31...

Страница 5: ...atus 58 Relay assignment 32 Settings 32 Modules Communication test 44 Identification numbers 42 Relay assignment See Relay assignment Mortalities 53 54 Motors Location 9 10 Maximum current 37 Motor sp...

Страница 6: ...see Curves Creating the blends With a blend curve 48 Without a blend curve 45 Mixing see Mixer Buttons 26 C Calibration Scale 34 Card Memory card 63 CDM 1 Communication test 44 Led meaning 26 Manual...

Страница 7: ...ic device which takes in charge the whole feed distribution process for pigs The controller ensures fast and efficient feed distribu tion due to the simultaneous transportation of many different feed...

Страница 8: ...ted to a computer thus making it possible to centralize the management of information and diversify control strategies 69 ECO II FEEDING rev 06 ECO II FEEDING Proxy switches 1 2 3 4 5 6 7 8 20 21 22 2...

Страница 9: ...52 Min drop 53 Min drop 53 Max drop 53 Max drop 53 Min drop 54 Min drop 54 Max drop 54 Max drop 54 Min drop 55 Min drop 55 Max drop 55 Max drop 55 Min drop 56 Min drop 56 Max drop 56 Max drop 56 Min...

Страница 10: ...10 Min drop 10 Max drop 10 Max drop 10 Min drop 11 Min drop 11 Max drop 11 Max drop 11 Min drop 12 Min drop 12 Max drop 12 Max drop 12 Min drop 13 Min drop 13 Max drop 13 Max drop 13 Min drop 14 Min d...

Страница 11: ...on the table below then refer to the corresponding section to obtain detailed information about the chosen option Option 1 continuous feeding with blend curves and without feed blends Principle of Ope...

Страница 12: ...e the Continuous Feeding option section 5 3 Set the start time of each feed cycle section 6 2 Enable the Active Feed Cycles in Curve option section 5 3 Select active feed cycles according to the anima...

Страница 13: ...controller sends the ingredient and dosage that suit the drop s animal age These feed cycles are performed on a daily basis Refer to section 2 4 3 to get information about the drops filling process wh...

Страница 14: ...re or software of your controller The USB drive can also be used to make a backup of your controller settings or to copy these settings on another controller of the same type The classic memory stick...

Страница 15: ...roller damages and or fire If the Nema Code Letter is not available exclusively use the LRA ratings The room temperature where the controller is located must always remain between 32o and 104o F 0o an...

Страница 16: ...ed cycles dosage or AdLib distribution method Settings Disable the blend curve section 5 3 Enable feed blends section 5 3 Select blend ingredients section 6 1 1 Select the feed blend and dosage used b...

Страница 17: ...a minor lack of precision could occur on the amount of feed that is actually going to be delivered This situation is likely to occur after a power failure for instance 17 ECO II FEEDING rev 06 ECO II...

Страница 18: ...gain step 2 This process is repeated up until the maximum proximity switch detects feed meaning the drop is now full The controller then starts filling the empty drop that follows b Cycled Feed Distri...

Страница 19: ...Select an item Drop Min Prox Status On Drop Max Prox Status Off Bin 1 Qty 5 kg Bin 2 Qty 10 kg Bin 3 Qty 3 kg Bin 4 Qty 0 kg Bin auger 1 Receiving hopper prox sw On Mixer status On Mixing time remain...

Страница 20: ...3 No Yes 57 ECO II FEEDING rev 06 ECO II FEEDING 8 3 Current Status Select 7 Current status The following menu shows the ongoing operation of the feeding system Actual weight Current weight as measure...

Страница 21: ...DING 2 5 Step by Step Guide The following checklist guides the user through the installation process References to related sections of the manual are provided to directly step to the parameters adjust...

Страница 22: ...tely for each bin in use Used today Amount of feed that has been taken from the selected bin today Add new feed Enter the amount of feed that has been added to the selected bin The entered value flash...

Страница 23: ...eparately for each drop section 8 1 Set the clock outputs start stop times if applicable section 7 0 Select the feed distribution method Continuous Cycled section 5 3 Blends Ingredients Selection with...

Страница 24: ...f the first type use the NC terminal as shown on the wiring diagram For an alarm of the second type use the NO terminal 53 ECO II FEEDING rev 06 ECO II FEEDING 8 MONITORING FUNCTIONS 8 1 Animal Invent...

Страница 25: ...t an item Select Time clock 1 Start Time 1 12 00A Stop Time 1 12 00A Start Time 2 12 00A Stop Time 2 12 00A Start Time 3 12 00A Stop Time 3 12 00A Start Time 12 12 00A Stop Time 12 12 00A 25 ECO II FE...

Страница 26: ...M 1 modules Manual Switch Select On or Off to manually start or stop the feeder connected to the CDM 1 Select Auto for the feeder to run in automatic mode MANUAL SWITCH ON OFF AUTO 51 ECO II FEEDING r...

Страница 27: ...nd Select which feed blend is distributed to the selected drop Available if blends are enabled and if blend curves are disabled in the installation setup s 5 3 Main Menu 3 Bin information 4 Drop setti...

Страница 28: ...I FEEDING 6 2 Feeding Schedule The feeding schedule is composed of many feed cycles up to 6 feed cycles can be each day Refer to the installation setup chapter to enable the proper number of feed cycl...

Страница 29: ...ll be sent in a cycle never exceeds the capacity of the drop Feed during cycles 1 6 Select what feed cycles are used for each point of the curve Available if the Active feed cycles in curve option is...

Страница 30: ...1 Settings 2 Scale settings Installation Exit Press BACK Change Press Modify Press to Select an item Time Display AM PM Number of bins 4 Number of loops 2 Number of blend curves 4 Use blends Yes Numbe...

Страница 31: ...06 ECO II FEEDING Number of feed cycle s Select the largest number of feed cycles that can be performed in a day Adjustable from 1 to 6 cycles Available if the Continuous Feeding option is disabled a...

Страница 32: ...strip the output is connected i e relay 17 1 relay 18 2 relay 32 16 Refer to section 5 9 for further information Accessible if a mixer is enabled sec 5 3 Main Menu 10 Alarm acknowledge 11 Installatio...

Страница 33: ...larm acknowledge 11 Installation Installation 8 Communication test 9 Version Exit Press BACK Eco II Feeding SETTINGS V X X PCXX 33 ECO II FEEDING rev 06 ECO II FEEDING Valve Module ID Select on which...

Страница 34: ...hown when the calibration is completed Main Menu 10 Alarm acknowledge 11 Installation Installation 6 Relay assignments 7 Scale calibration Scale calibration Exit Press BACK Change Press Modify Press t...

Страница 35: ...d loop systems Refer to section 5 3 to enable the proper loop type and to set the number of loops in use Graphics illustrating both systems are shown in section 2 3 Simultaneous feed batches transit U...

Страница 36: ...as fill auger Yes Flex auger Module ID 4 Flex auger Output 5 Prox switch Module ID 20 Prox switch Output 6 41 ECO II FEEDING rev 06 ECO II FEEDING Drops Min Max Proximity Switches Module ID Select on...

Страница 37: ...s to Select an item Select Drop 1 Loop 1 Distance from feed entry 1 Module ID 4 Output 7 Has Prox switches Yes Min Prox switch module ID 27 Min Prox switch Input 1 Max Prox switch module ID 27 Max Pro...

Страница 38: ...nected input 1 8 39 ECO II FEEDING rev 06 ECO II FEEDING 5 7 Bin Settings This section describes how to customize the bins for your particular application The controller can monitor up to 4 bins Refer...

Страница 39: ...nected input 1 8 39 ECO II FEEDING rev 06 ECO II FEEDING 5 7 Bin Settings This section describes how to customize the bins for your particular application The controller can monitor up to 4 bins Refer...

Страница 40: ...s to Select an item Select Drop 1 Loop 1 Distance from feed entry 1 Module ID 4 Output 7 Has Prox switches Yes Min Prox switch module ID 27 Min Prox switch Input 1 Max Prox switch module ID 27 Max Pro...

Страница 41: ...as fill auger Yes Flex auger Module ID 4 Flex auger Output 5 Prox switch Module ID 20 Prox switch Output 6 41 ECO II FEEDING rev 06 ECO II FEEDING Drops Min Max Proximity Switches Module ID Select on...

Страница 42: ...d loop systems Refer to section 5 3 to enable the proper loop type and to set the number of loops in use Graphics illustrating both systems are shown in section 2 3 Simultaneous feed batches transit U...

Страница 43: ...hown when the calibration is completed Main Menu 10 Alarm acknowledge 11 Installation Installation 6 Relay assignments 7 Scale calibration Scale calibration Exit Press BACK Change Press Modify Press t...

Страница 44: ...larm acknowledge 11 Installation Installation 8 Communication test 9 Version Exit Press BACK Eco II Feeding SETTINGS V X X PCXX 33 ECO II FEEDING rev 06 ECO II FEEDING Valve Module ID Select on which...

Страница 45: ...strip the output is connected i e relay 17 1 relay 18 2 relay 32 16 Refer to section 5 9 for further information Accessible if a mixer is enabled sec 5 3 Main Menu 10 Alarm acknowledge 11 Installatio...

Страница 46: ...06 ECO II FEEDING Number of feed cycle s Select the largest number of feed cycles that can be performed in a day Adjustable from 1 to 6 cycles Available if the Continuous Feeding option is disabled a...

Страница 47: ...1 Settings 2 Scale settings Installation Exit Press BACK Change Press Modify Press to Select an item Time Display AM PM Number of bins 4 Number of loops 2 Number of blend curves 4 Use blends Yes Numbe...

Страница 48: ...ll be sent in a cycle never exceeds the capacity of the drop Feed during cycles 1 6 Select what feed cycles are used for each point of the curve Available if the Active feed cycles in curve option is...

Страница 49: ...I FEEDING 6 2 Feeding Schedule The feeding schedule is composed of many feed cycles up to 6 feed cycles can be each day Refer to the installation setup chapter to enable the proper number of feed cycl...

Страница 50: ...nd Select which feed blend is distributed to the selected drop Available if blends are enabled and if blend curves are disabled in the installation setup s 5 3 Main Menu 3 Bin information 4 Drop setti...

Страница 51: ...M 1 modules Manual Switch Select On or Off to manually start or stop the feeder connected to the CDM 1 Select Auto for the feeder to run in automatic mode MANUAL SWITCH ON OFF AUTO 51 ECO II FEEDING r...

Страница 52: ...t an item Select Time clock 1 Start Time 1 12 00A Stop Time 1 12 00A Start Time 2 12 00A Stop Time 2 12 00A Start Time 3 12 00A Stop Time 3 12 00A Start Time 12 12 00A Stop Time 12 12 00A 25 ECO II FE...

Страница 53: ...f the first type use the NC terminal as shown on the wiring diagram For an alarm of the second type use the NO terminal 53 ECO II FEEDING rev 06 ECO II FEEDING 8 MONITORING FUNCTIONS 8 1 Animal Invent...

Страница 54: ...eparately for each drop section 8 1 Set the clock outputs start stop times if applicable section 7 0 Select the feed distribution method Continuous Cycled section 5 3 Blends Ingredients Selection with...

Страница 55: ...tely for each bin in use Used today Amount of feed that has been taken from the selected bin today Add new feed Enter the amount of feed that has been added to the selected bin The entered value flash...

Страница 56: ...DING 2 5 Step by Step Guide The following checklist guides the user through the installation process References to related sections of the manual are provided to directly step to the parameters adjust...

Страница 57: ...3 No Yes 57 ECO II FEEDING rev 06 ECO II FEEDING 8 3 Current Status Select 7 Current status The following menu shows the ongoing operation of the feeding system Actual weight Current weight as measure...

Страница 58: ...Select an item Drop Min Prox Status On Drop Max Prox Status Off Bin 1 Qty 5 kg Bin 2 Qty 10 kg Bin 3 Qty 3 kg Bin 4 Qty 0 kg Bin auger 1 Receiving hopper prox sw On Mixer status On Mixing time remain...

Страница 59: ...gain step 2 This process is repeated up until the maximum proximity switch detects feed meaning the drop is now full The controller then starts filling the empty drop that follows b Cycled Feed Distri...

Страница 60: ...a minor lack of precision could occur on the amount of feed that is actually going to be delivered This situation is likely to occur after a power failure for instance 17 ECO II FEEDING rev 06 ECO II...

Страница 61: ...ed cycles dosage or AdLib distribution method Settings Disable the blend curve section 5 3 Enable feed blends section 5 3 Select blend ingredients section 6 1 1 Select the feed blend and dosage used b...

Страница 62: ...roller damages and or fire If the Nema Code Letter is not available exclusively use the LRA ratings The room temperature where the controller is located must always remain between 32o and 104o F 0o an...

Страница 63: ...re or software of your controller The USB drive can also be used to make a backup of your controller settings or to copy these settings on another controller of the same type The classic memory stick...

Страница 64: ...controller sends the ingredient and dosage that suit the drop s animal age These feed cycles are performed on a daily basis Refer to section 2 4 3 to get information about the drops filling process wh...

Страница 65: ...e the Continuous Feeding option section 5 3 Set the start time of each feed cycle section 6 2 Enable the Active Feed Cycles in Curve option section 5 3 Select active feed cycles according to the anima...

Страница 66: ...on the table below then refer to the corresponding section to obtain detailed information about the chosen option Option 1 continuous feeding with blend curves and without feed blends Principle of Ope...

Страница 67: ...10 Min drop 10 Max drop 10 Max drop 10 Min drop 11 Min drop 11 Max drop 11 Max drop 11 Min drop 12 Min drop 12 Max drop 12 Max drop 12 Min drop 13 Min drop 13 Max drop 13 Max drop 13 Min drop 14 Min d...

Страница 68: ...52 Min drop 53 Min drop 53 Max drop 53 Max drop 53 Min drop 54 Min drop 54 Max drop 54 Max drop 54 Min drop 55 Min drop 55 Max drop 55 Max drop 55 Min drop 56 Min drop 56 Max drop 56 Max drop 56 Min...

Страница 69: ...ted to a computer thus making it possible to centralize the management of information and diversify control strategies 69 ECO II FEEDING rev 06 ECO II FEEDING Proxy switches 1 2 3 4 5 6 7 8 20 21 22 2...

Страница 70: ...ic device which takes in charge the whole feed distribution process for pigs The controller ensures fast and efficient feed distribu tion due to the simultaneous transportation of many different feed...

Страница 71: ...see Curves Creating the blends With a blend curve 48 Without a blend curve 45 Mixing see Mixer Buttons 26 C Calibration Scale 34 Card Memory card 63 CDM 1 Communication test 44 Led meaning 26 Manual...

Страница 72: ...atus 58 Relay assignment 32 Settings 32 Modules Communication test 44 Identification numbers 42 Relay assignment See Relay assignment Mortalities 53 54 Motors Location 9 10 Maximum current 37 Motor sp...

Страница 73: ...r 38 Flexible auger 38 Mixer 32 Principle of operation 42 Scale valve 33 Template 65 Relay modules Communication test 44 ID numbers 42 Reset time of 31 S Scale Actual weight compensation Activation 31...

Страница 74: ...REV 06 M 890 00375 rev 06 TARGET ECO II FEEDING Complete Feed Weighing and Distribution System for Hogs USER S MANUAL...

Отзывы: