Using in Series/Parallel Operation
130
Operation
1. Turn on the power switch in orde of slave, then master.
2. After all power is turned on, wait approximately 2 seconds before operating.
3. The HX-S-G2 power supply whose M/B CONTROL Connector IN is not connected to another HX-S-G2 Series
power supply is the Master unit (#1 in the previous page).
4. After the POWER switch has been turned ON, the output voltage will be displayed on the Master unit’s Number
Display (voltage) and the model name and the total power capacity will be displayed on the Master unit's Number
Display (current).
If there is discrepancy in total power capacity (the total power capacity of this time is different from that of the
previous time), the error code "E011" is displayed on the Number Display (voltage) and detected total power
capacity blinks in the bottom. After checking the total power capacity, hold down the "FUNC" key for more than 2
seconds and approve the detected number of devices to change to the measurement display mode.
5. The voltage measurement is displayed on the Number Display (voltage) of the master, and the current
measurement is displayed on the Number Display (current) of the master.
Total current value is displayed in the bottom Number Display.
Select power display with the "Display" key to display total power values.
Slaves, when operating normally, will display bars as
shown on the right.
!
CAUTION
Error Codes
1. Error Codes & Display List for Master Unit
Place
Items
No. Display
(Voltage)
No. Display
(Current)
Content
WDT
E001
-
Malfunction of CPU
OHP
E003
OHP
Over Heating Protection triggered
OVP
E004
OUP
Over Voltage Protection Function triggered
OCP
E005
OCP
Over Current Protection Function triggered
BST
E006
-
Slave error (Displayed only on the Master during
Parallel Operation)
P_ERR
E007
-
Internal rectification voltage or voltage for control
circuit is abnormal
BST_NRDY
Phase interruption detection
E008
-
Slave input voltage error
Detect the phase interruption of input power.
Device Detection Error
E009
-
No. of parallel devices cannot be detected
Max. Device No. OVER
E010
-
More than 11 parallel devices are connected
Device No. Disagreement
E011
-
Discrepancy in total power capacity between previous
time and this time
TRIP
E012
Shdn
TRIP function triggered
Models of different voltages
mixed
E013
-
Models of different voltages connected
Communication Error
E100
-
Data cannot be received normally
E2P Error
E110
-
Initialization error during startup
2. Error Displays for Slave Units
In the event an alarm is triggered by a Slave while the Master is functioning normally;
The Sla
ve that detected the alarm will display the error code on the Number Display (voltage) and the alarm
type on the Number Display (current).
Error code "E006" is displayed on the Number Display (voltage) of the Master unit.
(When alarm is triggered by a Slave and Master is functioning normally)
Содержание HX-S-01000-12G2
Страница 165: ...Special Loads 165 This page is blank...
Страница 169: ...Maintenance 169 This page is blank...
Страница 211: ...Specifications 211 External Diagrams 1 HX S 030 200G2 F I...
Страница 212: ...Specifications 212 2 HX S 030 400G2 F I...
Страница 213: ...Specifications 213 3 HX S 060 100G2 F I...
Страница 214: ...Specifications 214 4 HX S 060 200G2 F I...
Страница 215: ...Specifications 215 5 HX S 0120 50G2 F I...
Страница 216: ...Specifications 216 6 HX S 0120 100G2 F I...
Страница 217: ...Specifications 217 7 HX S 0400 15G2 F I...
Страница 218: ...Specifications 218 8 HX S 0400 30G2 F I...
Страница 219: ...Specifications 219 9 HX S 0500 12G2 F I...
Страница 220: ...Specifications 220 10 HX S 0500 24G2 F I...
Страница 221: ...Specifications 221 11 HX S 01000 6G2 F I...
Страница 222: ...Specifications 222 12 HX S 01000 12G2 F I...
Страница 223: ...Specifications 223...
Страница 239: ......