I/NET Configuration
Editing Configuration Profiles
4-7
Note:
Before performing the following step, consider the following:
If the link device is a 7802x or 7805x Tap, you can configure each
workstation on the host LAN to directly access the link. In this case,
we recommend that each workstation use the same system address to
access the link. This is especially important if you intend to assign a
Restore Host to the link. Refer to “Automatic DPU Restore” in
of TCON237, “I/NET 2000 System Technical Reference
Guide,” for more information about assigning Restore Hosts to links.
5.
Enter a number (0–99) for the
System Address
. This
number must be unique for each device in the system.
6.
Enter a name in the
Name
field.
7.
If the link device is a 7805x Tap, activate (
!
) the
Dial link
parameter. You may also set multiple links for the same
7805x Tap. This ability is termed “multi-link dial.” Refer to
the “Communication
”
chapter in
TCON237, I/NET 2000
Technical Reference Guide.
8.
Select
OK
to return to the Configuration editor.
9.
The link you defined displays in the list box. Repeat this
procedure for each link you wish to define (up to 16).
If necessary, you can delete the link definitions. To do so,
select the appropriate link in the list box and click
Delete
.
Link Type is NetPlus Router
NetPlus Routers must be directly connected to a PC to set their
initial configuration.
1.
Set the
Link type
to
NetPlus Router
.
2.
Select the serial port to which the NetPlus Router is
connected from the
Port or device
drop-down box.
3.
NetPlus Routers communicate at 19200 baud. Accordingly,
the
Baud rate
parameter is automatically set to 19200 and
cannot be changed.
4.
The Link Summary, TCP/IP parameters, and Workstation
Options are not applicable to this Link type. Skip to
.