TAC 2112, Manual
Functional Description
7:20 (22), 0-004-7459-3 (GB)
1999-08-01, TAC AB
Circulation pump
The alarm is triggered immediately when the input for the pump alarm
is activated (U3).
Parameters
P No. Parameter
Min.
Max.
Step
Default Comments
P 82
Alarm, pump
0
1
1
-
0=no alarm, 1=alarm
P 83
Alarm, supply temp.
0
1
1
-
0=no alarm, 1=alarm
7.7 Memory
backup
All parameters set (setpoints, weekly program, etc.) are stored
permanently in the controller. They remain in the controller’s memory
even after a long lasting power cut.
However, the time, date and year (P 15, P16, and P 17) must be reset
after a power cut of more than 48 hours.
7.8
Adjustment of sensor inputs
The value from the outdoor and reference sensors can be parallel-
shifted between –5
°
C and +5
°
C in steps of 0,25
°
C.
Parameters
P No. Parameter
Min.
Max.
Step
Default Comments
P 77
Adjustment, outdoor sensor
–5 °C
5 °C
0,25 °C
0 °C
P 78
Adjustment, reference sensor –5 °C
5 °C
0,25 °C
0 °C
With reference sensor only