TAC 2112, Manual
Functional Description
7:16 (22), 0-004-7459-3 (GB)
1999-08-01, TAC AB
7.3.12
Reduced daytime operation (optimised stop)
In systems with a reference sensor, the controller can determine
whether a transition to night operation can take place earlier than the
time set. The controller calculates a new transition time on the basis
of the deviation in room temperature.
The curve below is used when calculating reduced daytime operation.
10
30
-10
0
5
-5
10 15 20
-15
25
-20
-25
P 41
y1
(minutes)
of excess temperature
y0
P 42
Optimisation time per degree
Damped
in the room
Curve for reduced daytime operation
The time by which daytime operation is reduced is calculated as:
t = (y-value from curve) • (room tempe dead zone room - setpoint room)
Example
Setpoint room=20
°
C
Dead zone room=1
°
C
Room temperature=21
°
C
Damped outdoor temperature=10
°
C
The above results in an excess temperature in the room of
21+1–20=2
°
C. The y-value of the curve at +10
°
C is 30 minutes,
which gives an optimisation time of 60 minutes (2 × 30).
The function for reduced daytime operation is blocked when the
equipment is delivered by setting the stop times in the curve to
0 minutes.
Parameters
P No. Parameter
Min.
Max.
Step
Default Comments
P 41
Opt. time at –10°C (y0)
0 min.
240 min. 1 min.
0 min.
P 42
Opt. time at +10°C (y1)
0 min.
240 min. 1 min.
0 min.
Содержание 2112
Страница 1: ...TAC 2112 Manual 0 004 7459 3 GB 1999 08 01 T1 P1...
Страница 2: ......
Страница 62: ...TAC 2112 Manual Commissioning Protocol List of Parameters A 6 6 0 004 7459 3 GB 1999 08 01 TAC AB...
Страница 66: ...TAC 2112 Manual Index Index 4 4 0 004 7459 3 GB TAC AB 1999 08 01...
Страница 68: ...TAC 2112 Manual Reply form 1999 08 01 TAC AB...
Страница 69: ......
Страница 70: ...TAC AB J gershillgatan 18 SE 213 75 MALM SWEDEN 46 40 38 68 50 www tac se...