TAC 2112, Manual
Functional Description
TAC AB, 1999-08-01
0-004-7459-3 (GB), 7:13(
22
)
7.3.10
Variable night setback
To ensure that the heating installation is able to reset the room
temperature after a night setback in the event of a low outdoor
temperature, the controller uses what is known as variable night
setback. This means that the magnitude of the setback is a function of
the damped outdoor temperature according to the curve below.
0%
100%
-10
0
5
-5
10 15 20
-15
25
-20
-25
x1
P 34
P 33
x0
Damped
Curve for variable night setback
At the outdoor temperature x0, night setback does not take place at
all, but then increases gradually as the outdoor temperature rises.
If points x0 and x1 are set to the same level, full night setback is
attained irrespective of the outdoor temperature.
Note that the parameters P 33 and P 34 also affect the morning boost
function.
Parameters
P No. Parameter
Min.
Max.
Step
Default Comments
P 33
Outdoor temp., 0% night setb. –30 °C
P 34
1 °C
–10 °C
Affects morning boost
P 34
Outd. temp., 100% night setb. P 33
20 °C
1 °C
10 °C
Affects morning boost
7.3.11 Morning
heating
The time for the transition to daytime operation is optimised, which
means that the controller increases the supply of heat before the set
time so that the correct room temperature is attained at the set time.
Output K2 is set during the heating time.
Содержание 2112
Страница 1: ...TAC 2112 Manual 0 004 7459 3 GB 1999 08 01 T1 P1...
Страница 2: ......
Страница 62: ...TAC 2112 Manual Commissioning Protocol List of Parameters A 6 6 0 004 7459 3 GB 1999 08 01 TAC AB...
Страница 66: ...TAC 2112 Manual Index Index 4 4 0 004 7459 3 GB TAC AB 1999 08 01...
Страница 68: ...TAC 2112 Manual Reply form 1999 08 01 TAC AB...
Страница 69: ......
Страница 70: ...TAC AB J gershillgatan 18 SE 213 75 MALM SWEDEN 46 40 38 68 50 www tac se...