TAC 2112, Manual
Functional Description
7:2 (22), 0-004-7459-3 (GB)
1999-08-01, TAC AB
Forced night setback
When the controller is in the “timed operation” operating mode and
the input X2 is connected to M (measurement neutral), the following
takes place:
•
The symbols on the left are displayed in the display window (the
moon flashes).
•
The supply temperature or the room temperature is reduced to the
setpoint for night setback.
Extended daytime operation
When the controller is in the “timed operation” operating mode and
input X1 is connected to M (measurement neutral), the following
takes place:
•
The symbols on the left are displayed in the display window (the
sun flashes).
•
The supply temperature or room temperature is controlled to the
setpoint for daytime operation.
Fixed night setback
When the controller is in the “fixed night setback” operating mode,
the following takes place:
•
The symbol on the left is displayed in the display window.
•
The supply temperature or room temperature is reduced to the
setpoint for night setback.
Fixed daytime operation
When the controller is in the “fixed daytime operation” operating
mode, the following takes place:
•
The symbol on the left is displayed in the display window.
•
The supply temperature or room temperature is controlled to the
setpoint for daytime operation.
Heating off (standby)
When the controller is in the “heating off” operating mode, the
following takes place:
•
The symbol on the left is displayed in the display window.
•
The setpoint of the supply controller is set to the lowest
permissible supply temperature (P 22).
•
The circulation pump stops irrespective of whether pump stop has
been selected or not. However, frost protection and pump exercise
remain operational.
Содержание 2112
Страница 1: ...TAC 2112 Manual 0 004 7459 3 GB 1999 08 01 T1 P1...
Страница 2: ......
Страница 62: ...TAC 2112 Manual Commissioning Protocol List of Parameters A 6 6 0 004 7459 3 GB 1999 08 01 TAC AB...
Страница 66: ...TAC 2112 Manual Index Index 4 4 0 004 7459 3 GB TAC AB 1999 08 01...
Страница 68: ...TAC 2112 Manual Reply form 1999 08 01 TAC AB...
Страница 69: ......
Страница 70: ...TAC AB J gershillgatan 18 SE 213 75 MALM SWEDEN 46 40 38 68 50 www tac se...