TAC 2112, Manual
Functional Description
7:14 (22), 0-004-7459-3 (GB)
1999-08-01, TAC AB
Without reference sensor
Without a reference sensor, the heating time varies with the damped
outdoor temperature according to the curve below.
20
120
-10
0
5
-5
10 15 20
-15
25
-20
-25
P 38
P 37
y0
(minutes)
Heating time
y1
P 39
Damped
360
Curve for morning heating
10
-10
0
5
-5
10 15 20
-15
25
-20
-25
P 36
0
(°C)
Morning boost
P 34
P 33
Damped
x1
x0
Curve for morning boost
The morning heating can be blocked by setting the
Max. heating time
parameter (P 37) to 0 hours.
Note that the parameters P 33 and P 34 also affect the function for
variable night setback.
With reference sensor
The controller automatically calculates an appropriate starting time
using a reference sensor so that the correct temperature is achieved at
the set time for daytime operation. This calculation is adaptive (self-
adjusting).
During the heating time, the controller controls towards the setpoint
for daytime operation with night control effect and with a fixed
supplement to the supply setpoint. This addition is shown by the
Max.
morning boost
parameters (P 36).
The heating time is calculated according to the following:
t = (y-value from curve) × (room temperature - day setpoint, room)
If a reference sensor has been installed, the y-value from the curve
shows the heating time per degree the temperature deviates from the
day setpoint.
Содержание 2112
Страница 1: ...TAC 2112 Manual 0 004 7459 3 GB 1999 08 01 T1 P1...
Страница 2: ......
Страница 62: ...TAC 2112 Manual Commissioning Protocol List of Parameters A 6 6 0 004 7459 3 GB 1999 08 01 TAC AB...
Страница 66: ...TAC 2112 Manual Index Index 4 4 0 004 7459 3 GB TAC AB 1999 08 01...
Страница 68: ...TAC 2112 Manual Reply form 1999 08 01 TAC AB...
Страница 69: ......
Страница 70: ...TAC AB J gershillgatan 18 SE 213 75 MALM SWEDEN 46 40 38 68 50 www tac se...