TAC 2112, Manual
Functional Description
TAC AB, 1999-08-01
0-004-7459-3 (GB), 7:11(
22
)
Parameters
P No. Parameter
Min.
Max.
Step
Default Comments
P 13
Return temperature, heating
0 °C
120 °C
0,3 °C
-
Step=0,1 at 2–55 °C
P 43
Return limitation on/off
0
2
1
0 (off)
1=heating, 2=heat.+dom.h.w.
P 44
Return limit., heating, P band 10 °C
200 °C
0,5 °C
20 °C
Not if P 43=0
P 45
Curve point x0
-30 °C
P 48
1 °C
-10 °C
Not if P 43=0
P 46
Curve point y0
P 49
120 °C
1 °C
70 °C
Not if P 43=0
P 47
Curve point x1
P 46
40 °C
1 °C
10 °C
Not if P 43=0
P 48
Curve point y1
10 °C
P 47
1 °C
40 °C
Not if P 43=0
7.3.8
Remote heating control (SPC)
The heating can be remote-controlled by connecting an external
2–10 V DC control voltage to the SPC input.
In systems with a reference sensor, the setpoint for the room
temperature is affected, and in systems without a reference sensor, the
setpoint for the supply temperature is affected. The effect of the
control voltage on the setpoint is shown in the illustration below.
-40
0
5
7
8
6
9
10
4
3
2
+40
Effect on
setpoint (°C)
SPC signal
(V)
P 81
The effect of the SPC signal on the setpoint
The effect of the control voltage on the setpoint can be adjusted by
means of the
SPC effect at +10 V
parameter (P 81).
When the equipment is delivered, the SPC signal has no effect due to
the fact that the
SPC effect at +10 V
parameter is set to zero.
Parameters
P No. Parameter
Min.
Max.
Step
Default Comments
P 80
Current SPC effect
(-1)•P 81 P 81
0,1°C
-
P 81
SPC effect at +10 V
0 °C
40 °C
1 °C
0 °C
Содержание 2112
Страница 1: ...TAC 2112 Manual 0 004 7459 3 GB 1999 08 01 T1 P1...
Страница 2: ......
Страница 62: ...TAC 2112 Manual Commissioning Protocol List of Parameters A 6 6 0 004 7459 3 GB 1999 08 01 TAC AB...
Страница 66: ...TAC 2112 Manual Index Index 4 4 0 004 7459 3 GB TAC AB 1999 08 01...
Страница 68: ...TAC 2112 Manual Reply form 1999 08 01 TAC AB...
Страница 69: ......
Страница 70: ...TAC AB J gershillgatan 18 SE 213 75 MALM SWEDEN 46 40 38 68 50 www tac se...