TAC 2112, Manual
Functional Description
7:18 (22), 0-004-7459-3 (GB)
1999-08-01, TAC AB
7.4 Clock
The controller contains a calendar clock with automatic transition
between daylight saving time and normal time and automatic
compensation for leap years.
The clock must be set manually after a power cut lasting more than
48 hours.
Daylight saving time periods
The times for transitions between daylight saving time and normal
time can be set using the
Daylight saving time period
parameter
(P 67).
P 67
Daylight saving time starts
Daylight saving time ends
0
No transition to daylight saving time
1
Last Sunday in Mar 02:00
Last Sunday in Sept. 03:00
2
Last Sunday in Mar 02:00
Last Sunday in Oct. 03:00
3
Date for daylight saving time period set using P 68–P 71
Parameters
P No. Parameter
Min.
Max.
Step
Default Comments
P 00
Current time
00:00
23:59
00:01
-
P 15
Set time
00:00
23:59
00:01
00:00
hour:minute
P 16
Set date
01.01
12.31
00.01
01.01
month.day
P 17
Set year
0
9999
1
1995
P 66
Time format 12/24 hours
12 h
24 h
12 h
24
h=hours
P 67
Daylight saving time period
0
3
1
1
1=Mar–Sept, 2=Mar–Oct
P 68
Daylight saving time starts
(date)
01.01
12.31
00.01
03.31
Only if P 67=3
P 69
Daylight saving time starts
(time)
00:00
23:59
00:01
02:00
Only if P 67=3
P 70
Daylight saving time ends
(date)
01.01
12.31
00.01
09.30
Only if P 67=3
P 71
Daylight saving time ends
(time)
00:00
23:59
00:01
03:00
Only if P 67=3
Содержание 2112
Страница 1: ...TAC 2112 Manual 0 004 7459 3 GB 1999 08 01 T1 P1...
Страница 2: ......
Страница 62: ...TAC 2112 Manual Commissioning Protocol List of Parameters A 6 6 0 004 7459 3 GB 1999 08 01 TAC AB...
Страница 66: ...TAC 2112 Manual Index Index 4 4 0 004 7459 3 GB TAC AB 1999 08 01...
Страница 68: ...TAC 2112 Manual Reply form 1999 08 01 TAC AB...
Страница 69: ......
Страница 70: ...TAC AB J gershillgatan 18 SE 213 75 MALM SWEDEN 46 40 38 68 50 www tac se...