TAC 2112, Manual
Functional Description
7:8 (22), 0-004-7459-3 (GB)
1999-08-01, TAC AB
Criteria for automatic curve adjustment
The following criteria must be met for the automatic curve adjustment
to work:
•
A reference sensor is installed.
•
Automatic curve adjustment is on (P 27).
•
The controller is working under timed operation.
•
Daytime operation is on.
•
The pump is working, i.e. there is a heating requirement.
•
The return temperature limitation is not active.
Parameters
P No. Parameter
Min.
Max.
Step
Default Comments
P 27
Automatic curve adjustment
0 (off)
1 (on)
1
1 (on)
With reference sensor only
P 28
I time for curve adj. controller 1 min.
720 min. 1 min.
180 min. With reference sensor only
P 29
Max curve adjustment
0 °C
40 °C
1 °C
5 °C
With reference sensor only
7.3.5
Supply controller
Controller
The supply temperature is controlled by a PI controller (proportional
and integrating controller) of the “increase/decrease” type. The
setpoint for this controller is calculated on the basis of the following
parameters:
•
Operating mode
•
The reset curve for outdoor temperature compensation
•
Room temperature effect, if a reference sensor is fitted
•
Parallel shifting of the reset curve, if no reference sensor is fitted
•
Return temperature limitation
•
Remote setpoint control, SPC adjustment
•
Pump control
•
Night setback
•
Supplement during morning boost
Содержание 2112
Страница 1: ...TAC 2112 Manual 0 004 7459 3 GB 1999 08 01 T1 P1...
Страница 2: ......
Страница 62: ...TAC 2112 Manual Commissioning Protocol List of Parameters A 6 6 0 004 7459 3 GB 1999 08 01 TAC AB...
Страница 66: ...TAC 2112 Manual Index Index 4 4 0 004 7459 3 GB TAC AB 1999 08 01...
Страница 68: ...TAC 2112 Manual Reply form 1999 08 01 TAC AB...
Страница 69: ......
Страница 70: ...TAC AB J gershillgatan 18 SE 213 75 MALM SWEDEN 46 40 38 68 50 www tac se...