TAC 2112, Manual
Installation
TAC AB, 1999-08-01
0-004-7459-3 (GB), 5:3(10)
Procedure for mounting controller in a panel:
1.
Make an opening in the panel as shown in the adjacent scale
drawing. The max. panel thickness is 5 mm.
138
92
+1
-0
+0,5
-0
2. Remove the backplate from the electronic part (see above).
Remove the terminal blocks from the backplate.
3.
Place the controller in the panel and lock it in position by
tightening the two locking screws. Seal the holes using the two
gaskets. It is not necessary to install the metal brace when
mounting panel.
4. Attach the terminal blocks to the pin on the back of the controller.
Note that the terminal blocks are “coded”, so they cannot be
interchanged.
It is also possible to use the backplate when fitting the controller in a
panel.