TAC 2112, Manual
Functional Description
7:10 (22), 0-004-7459-3 (GB)
1999-08-01, TAC AB
Parameters
P No. Parameter
Min.
Max.
Step
Default Comments
P 07
Room temperature
0 °C
45 °C
0,1 °C
-
With reference sensor only
P 08
Calculated SP, room temp.
–35 °C
70 °C
0,1 °C
-
With reference sensor only
P 09
Setpoint room, day
5 °C
30 °C
0,5 °C
21 °C
With reference sensor only
P 10
Setpoint room, night
5 °C
30 °C
0,5 °C
18 °C
With reference sensor only
P 30
Control effect room, day
0,5
20
0,5
2
With reference sensor only
P 31
Control effect room, night
0,5
50
0,5
10
With reference sensor only
P 32
Dead zone, room
0 °C
5 °C
0,1 °C
0,3 °C
With reference sensor only
7.3.7
Return temperature limitation
The return water temperature can be limited by the controller. The
magnitude of this limitation is determined by a separate reset curve
with the max. return temperature as a function of the damped outdoor
temperature. The reset curve is based on two curve points as depicted
below.
30
40
50
60
70
80
-10
0
5
-5
10 15 20
-15
25
-20
-25
x1
y0
y1
P 46
P 47
P 48
P 45
x0
Damped
Reset curve for return temperature limitation
Limitation controller
The limitation of the return temperature is controlled by a controller
using the following data:
P band:
10–200
°
C
I time:
3 minutes
Dead zone:
1
°
C
The output signal from the controller has an effect on the setpoint for
the supply temperature.
The limitation controller has no effect in the operating modes
“heating off” and “manual control”.
Содержание 2112
Страница 1: ...TAC 2112 Manual 0 004 7459 3 GB 1999 08 01 T1 P1...
Страница 2: ......
Страница 62: ...TAC 2112 Manual Commissioning Protocol List of Parameters A 6 6 0 004 7459 3 GB 1999 08 01 TAC AB...
Страница 66: ...TAC 2112 Manual Index Index 4 4 0 004 7459 3 GB TAC AB 1999 08 01...
Страница 68: ...TAC 2112 Manual Reply form 1999 08 01 TAC AB...
Страница 69: ......
Страница 70: ...TAC AB J gershillgatan 18 SE 213 75 MALM SWEDEN 46 40 38 68 50 www tac se...