TAC 2112, Manual
Day-to-day Usage
TAC AB, 1999-08-01
0-004-7459-3, 4:3(6)
4.5
Setting the time schedule for
daytime/night operation
4.5.1
Weekly program for night setback of heat
When the controller is supplied, it is set for night setback of heat
between 22:00 and 06:00 for all days of the week. See chapter 7 for a
more detailed description of the time schedule.
Procedure for changing the weekly program:
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15 16 17
18
0
23
22
21
20
19
24
K1
MO
P 14
1
Select parameter number P 14 by pressing
or
. The
parameter number is increased and decreased by pressing
or
.
2
When the parameter number has been selected, the 24-hour time
bar will be displayed showing “MO” for Monday.
3
Scroll in the 24-hour time bar by pressing
or
until you
get to the segment to be changed. The segment will flash.
4
Change the half-hour segments by pressing
. A filled-in
segment will result in daytime operation. When a segment has
been changed, the next segment will start to flash.
5
Scroll on to “TU” for Tuesday by pressing
.
6
Change the half-hour segments for Tuesday by pressing
.
7
Repeat steps 5 and 6 for each day of the week.
8
Exit by pressing
or
.
4.5.2
Reduction in heating during a holiday period
It is possible to program up to six holiday periods. During a holiday
period, the heating is controlled at the setpoint for the night. No
holiday periods are programmed prior to delivery. See chapter 7 for a
more detailed description of time schedules.
Procedure for setting a holiday period:
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15 16 17
18
0
23
22
21
20
19
24
K1
P 63
1
1
Select parameter number P 63 by pressing
or
. The
parameter number is increased and decreased by pressing
or
. Press
and
at the same time to get to P 15 – P 99.
2
Select a holiday period (1–6) by pressing
or
.
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15 16 17
18
0
23
22
21
20
19
24
K1
P 64
01.01
3
Go to P 64 by pressing
.
4
Set the start date (month.day) by pressing
or
. Hold the
button down for fast increase/decrease.
Содержание 2112
Страница 1: ...TAC 2112 Manual 0 004 7459 3 GB 1999 08 01 T1 P1...
Страница 2: ......
Страница 62: ...TAC 2112 Manual Commissioning Protocol List of Parameters A 6 6 0 004 7459 3 GB 1999 08 01 TAC AB...
Страница 66: ...TAC 2112 Manual Index Index 4 4 0 004 7459 3 GB TAC AB 1999 08 01...
Страница 68: ...TAC 2112 Manual Reply form 1999 08 01 TAC AB...
Страница 69: ......
Страница 70: ...TAC AB J gershillgatan 18 SE 213 75 MALM SWEDEN 46 40 38 68 50 www tac se...