TAC 2112, Manual
Functional Description
7:12 (22), 0-004-7459-3 (GB)
1999-08-01, TAC AB
7.3.9 Pump control
The pump control acts to utilise the heat accumulated in the building
as efficiently as possible by allowing the circulation pump to operate
only when there is a specific heating requirement.
Pump stop
The circulation pump is stopped and the setpoint for the supply
temperature is set to
Min. supply temperature
in the following cases:
•
The outdoor temperature exceeds the
Outdoor temperature for
pump stop
limit.
•
The calculated setpoint for the supply temperature is less than the
Supply temperature for pump stop
limit.
The pump stop has a fixed switch-off delay of 5 minutes, i.e. the
pump runs for at least 5 minutes every time (does not apply for pump
exercise – see below).
Restarting the pump
The circulation pump is restarted with a fixed hysteresis of 1.5
°
C.
The pump can be restarted only after a set time, the
Min. pump off
time
. However, the pump can be started immediately in the event of
frost protection if so required (see below) or in operating modes other
than timed operation.
Pump exercise
The pump starts at 12:00 and runs for one minute every Monday in
order to prevent pump seizure, for example during the summer
months.
Frost protection
The pump always starts and the valve is controlled whenever the
outdoor temperature is less than +3
°
C in order to prevent freezing in
the heating installation.
Parameters
P No. Parameter
Min.
Max.
Step
Default Comments
P 72
Pump stop on/off
0 (off)
1 (on)
1
1 (on)
0=off, 1=on
P 73
Outdoor temp. for pump stop 3 °C
50 °C
1 °C
20 °C
P 74
Supply temp., pump stop
0 °C
120 °C
1 °C
20 °C
P 75
Exercise on/off
0 (off)
1 (on)
1
1 (on)
0=off, 1=on
P 76
Min. pump off time
0 h
12 h
0,5 h
2 h
h=hours
Содержание 2112
Страница 1: ...TAC 2112 Manual 0 004 7459 3 GB 1999 08 01 T1 P1...
Страница 2: ......
Страница 62: ...TAC 2112 Manual Commissioning Protocol List of Parameters A 6 6 0 004 7459 3 GB 1999 08 01 TAC AB...
Страница 66: ...TAC 2112 Manual Index Index 4 4 0 004 7459 3 GB TAC AB 1999 08 01...
Страница 68: ...TAC 2112 Manual Reply form 1999 08 01 TAC AB...
Страница 69: ......
Страница 70: ...TAC AB J gershillgatan 18 SE 213 75 MALM SWEDEN 46 40 38 68 50 www tac se...