Appendix A System Messages
System Notification Messages
T1E1 Input
FREQUENCY
ERROR
031
Minor
No
T1E1 Input FREQUENCY
ERROR
E1T1 Input FREQUENCY
ERROR cleared
Not supported at this
time.
No action required
SYNCE/T1E1 input
SSM changed
032
Event
Yes
SYNCE/E1T1 input SSM
changed
n/a
No action required
n/a
INCOMPATIBLE
TRANSPORT
TYPE
051
Minor
No
INCOMPATIBLE
TRANSPORT TYPE
INCOMPATIBLE
TRANSPORT TYPE
cleared
No action required
PTP input lost
052
Minor
No
PTP INPUT LOST
PTP INPUT LOST
cleared
Check Ethernet
connection.
Check PTP input
configuration
Check that PTP
Master is functioning
No action required
PTP master
switched
053
Event
Yes
PTP master switched
n/a
Check Status of
configured masters.
n/a
PTP input
time/frequency not
traceable
054
Event
No
PTP input time/frequency
not traceable
PTP INPUT NOT
TRACEABLE cleared
No action required
Table A-1. System Notification Messages (Continued)
Description
Event
ID
Msg
Level
Trans-
itory
MsgText
Corrective Action