TimeProvider 2300/2700 User’s Guide
098-00564-000 Revision A3 – July, 2013
Appendix A System Messages
System Notification Messages
T1E1 Input LOSS
OF SIGNAL (LOS)
026
Minor
No
T1E1 Input LOSS OF
SIGNAL (LOS)
E1T1 Input LOSS OF
SIGNAL cleared
Check if cable is
securely connected.
Check signal source
is present and
configured properly.
No action required
T1E1 Input ALARM
INDICATION
SIGNAL (AIS)
027
Minor
No
T1E1 Input ALARM
INDICATION SIGNAL
(AIS)
T1E1 Input ALARM
INDICATION SIGNAL
cleared
Check alarm condition
and frame format of input
source signal in T1/E1
port.
No action required
T1E1 Input OUT OF
FRAME (OOF)
028
Minor
No
T1E1 Input OUT OF
FRAME (OOF)
E1T1 Input OUT OF
FRAME cleared
Check frame format of
input source signal in
T1/E1 port. It should
match with the input
configuration for the port.
No action required
T1E1 Input CRC
ERROR (CRC)
029
Minor
No
T1E1 Input CRC ERROR
(CRC)
E1T1 Input CRC ERROR
cleared
Enable CRC in input
source signal, or disable
CRC in TimeProvider
2300/2700 T1/E1 input
port.
No action required
T1E1 Input
BIPOLAR
VIOLATION (BPV)
030
Minor
No
T1E1 Input BIPOLAR
VIOLATION (BPV)
E1T1 Input BIPOLAR
VIOLATION cleared
Check input source
signal or the connection
cable.
No action required
Table A-1. System Notification Messages (Continued)
Description
Event
ID
Msg
Level
Trans-
itory
MsgText
Corrective Action