CHAPTER ONE - INTRODUCTION
5
SG-Sys
tem I Operating Man
ual
1
Parallel Printers
For UL and ULC Listed applications the following UL/ULC Listed printer can be used with the SG-System III:
• Seiko DPU-414
Serial Printers
For UL and ULC Listed applications the following UL/ULC Listed printer can be used with the SG-System III:
• Seiko DPU-414
NOTE: Do NOT use printer cables that have only 1 common ground wire.
UL Manual Mode
For UL manual mode, each event will activate the internal buzzer to be acknowledged manually. Each event will also be sent automatically
to the connected printer.
For Central Station applications, the signaling performance of each DACT (Digital Alarm Communication Transmitter) shall be manually
tracked. Failure to receive a signal from a DACT over 24 hour period shall be handled as a trouble signal.
Description (Hardware)
Basic Configuration:
The basic configuration consists of one 19" rack mounted chassis comprising the following:
•
SG-BP3 Backplane
provides interconnection of modules and communications interface
•
SG-CPM3 Module
contains the CPU that controls all communication to and from up to 24 receiver modules, printers, including 2
serial ports, a parallel port and an ethernet connection.
•
SG-PSU3 Power Supply Unit
provides power to all modules of the system.
•
SG-DC/DC3
provides 5VDC power output required for the SG-DRL3 line cards. A slot exists for a second SG-DC/DC3 voltage con-
verter. In the event of a failure, the redundant SG-DC/DC3 can be removed/replaced without powering down the unit.
•
SG-PSC3
(Power Supply Controller) monitors the states of the power and fan for each SG-MLRF3.
•
SG-MLRF3:
The metal rack of the SG-System III that incorporates the LCD and SG-BP3.
•
SG-DRL3/DRL3E Line Card:
Each SG-DRL3/DRL3E line card monitors one telephone line. Stores on the card up to 64 profiles for
data management including 8 different handshaking protocols. Each card has a 512-event buffer.
•
SG-DRL3-2L Line Card
: Each SG-DRL3-2L line card monitors up to two telephone lines. Stores on the card up to 64 profiles for data
management including 8 different handshaking protocols. Each card has a 512-event buffer.
•
SG-DRL3-IP Line Card
: Each SG-DRL3-IP line card supports up to 1536 IP transmitters and can supervise up to 512 transmitters.
Each line card has a 512-event buffer.
SG-BP3 Backplane
The SG-BP3 interconnects system modules and racks as well as providing communication outputs as indicated in figure 1-6.
SG-DRL3-IP
Opt #
Program Option
Permitted in UL 864?
(Y/N)
Possible Settings
Settings Permitted (UL
864)
13
15
19
1A
1B
1C
1D
1E
1F
Transmitter Failure Debounce Time
Transmitter Restoral Debounce Time
Mask Transmitter Restoral
Mask Transmitter Failure
Mask Transmitter Swap
Mask Transmitter Unencrypted
Mask Invalid Report
Mask Unknown Account
Mask Supervised Acc Exceeded
N
N
N
N
N
N
N
N
N
5-65535
5-65535
OFF
OFF
OFF
OFF
OFF
OFF
OFF
300
300
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Table 1-1: UL864 Programming Requirements
Содержание SG-System III
Страница 22: ...Line Card In This Chapter Standby Mode on page 19 Line Fault on page 21...
Страница 92: ...In this Chapter Options 00 47 on page 90 SG DRL3 IP Programming...
Страница 100: ...Printer Words...
Страница 105: ...Telco Connector Pin Outs...
Страница 107: ...DEC HEX BIN Conversion Chart...
Страница 109: ...ASCII Character Chart...
Страница 111: ...SG DRL3 SG DRL3E SG DRL3 2L Communication Formats...
Страница 113: ...Ports...
Страница 115: ...Events Messages...
Страница 124: ...Glossary...