CHAPTER FOUR - PROGRAMMING/OPERATION
29
SG-Sys
tem I Operating Man
ual
4
NOTE: For changes to this program option a reset of the unit is required before the new parameters are used.
Option 03: Gateway Address
Default (0.0.0.0)
This section is the Gateway of the SG-CPM3. The gateway address will be entered as a dotted decimal number. Example: 192.168.002.001.
Each segment of the Gateway IP address shall have a valid range from 000 to 254. The gateway is used in the event that the data being sent
is not on the same network as the SG-CPM3. The data will need to be sent through a router. This is the IP address of the router.
NOTE: For changes to this program option a reset of the unit is required before the new parameters are used.
NOTE: The IP address and gateway must be on the same Subnet in order to change one or the other.
Option 04: Auto Update Time & Date
Default (0)
This option allows the automation to update the SG-CPM3 time via the TCP/IP port. When enabled, should the SG-CPM3 fail to get the time
& date within 24 hours period (started after the last update is received or reset), it will generate a status message to the printer and automa-
tion, following the internal trouble protocol. The Trouble status on the SG-System III will not be affected. The Receiver Console time update
function must be disabled when using this feature or there is a possibility that the SG-CPM3 will not remain synchronized with the automa-
tion PC.
Printer message: "Time&Date Update Fail"
Automation message: 0RRLLL[#0000¦NRU0000]
NOTE: Confirm that the automation software package supports time and date update.
Option 05: Contrast Adjust
Default (80)
Allows the contrast of the message display screen to be adjusted. The contrast can also be adjusted from any screen by holding the UP and
ENTER buttons simultaneously to increase the level, or by holding the ENTER and DOWN buttons simultaneously to decrease the level.
Option 06: Password Menu
Default (CAFE)
Allows the SG-System III users and passwords to be erased or changed. Sixteen users with 4-digit passwords are available for use on the
SG-System III. User 0 is the Master user, and users 1 through F may be assigned to individual operators. The Master user will provide access
to all menus, while the operators will have access to the SG-CPM3 settings as a view only (except passwords), other than to set the time and
date.
This is to meet ULC-S559 Standard applicable to Fire Monitoring Equipment. All users are able to ACK alarm messages and view the Trou-
ble menu.
To erase a user, program the password for that user to 'FFFF'.
NOTE: User “0” cannot be erased.
Option 07: COM1 Baud Rate
Default (9600)
Determines the baud rate at which the SG-CPM3 will communicate to the automation software via serial port 1. Valid selections are: 1200,
2400, 4800, 9600, 19200, 38400, 57600.
NOTE: For changes to this program option a reset of the unit is required before the new parameters are used.
Содержание SG-System III
Страница 22: ...Line Card In This Chapter Standby Mode on page 19 Line Fault on page 21...
Страница 92: ...In this Chapter Options 00 47 on page 90 SG DRL3 IP Programming...
Страница 100: ...Printer Words...
Страница 105: ...Telco Connector Pin Outs...
Страница 107: ...DEC HEX BIN Conversion Chart...
Страница 109: ...ASCII Character Chart...
Страница 111: ...SG DRL3 SG DRL3E SG DRL3 2L Communication Formats...
Страница 113: ...Ports...
Страница 115: ...Events Messages...
Страница 124: ...Glossary...