CHAPTER FIVE - ADVANCED PROGRAMMING
63
SG-System I Operating Manual
5
Example:
1234A1 becomes '1234 A 1' becomes [#1234|NBA1]
Values programmed in Options 30/130/230-5F/15F/25F, 70/170/270 other than in this table will default to UAxx for Undecoded Alarm.
Bit 3 - Convert BFSK format to SIA.
The BFSK outputs will be converted to a SIA format. The automation Output will use the Protocol ID of 'R'.
When this option is enabled it has precedence over the BFSK RS232 Option A4/1A4/2A4. The Accounts 3/x to 4/x Option76/176/276 may
be used to insert a leading 0 to the account code.
Example:[#123|NFA1]
Bit 4 - Convert comma (',') to forward slash ('/')
When enabled, any commas will be converted to a forward slash.
Example: [#1234|NBA1,2,3] becomes [#1234|NBA1/2/3]
Bit 5 - SIA Recovery
Some older SIA panels require that all blocks of the call be NACK'd for the call to be complete or it would assume that if one block was
acknowledged then all blocks were correctly acknowledged, and not resend the blocks that were NACK'd. This option will turn off the func-
tionality where, if one block is NACK'd, then all blocks (regardless if they are correct or not) will be NACK'd. In order to disable the SIA
recovery option, disable this bit option (default setting). By disabling the SIA recovery, the receiver will send Acknowledgement signals for
the blocks that require it and NACK the ones that will require it.
To enable the SIA recovery set bit 5 to 1. If a signal has any portion of the call NACK'd then the entire call will receive a NACK. Please con-
tact technical support for more information and updates to the list of panels affected.
Bit 6 - Pulse to SIA Hex zone numbers
This option is to be used if it is desired to have pulse conversion digits that are starting with HEX output a zone number in SIA. This option
functions the same as “Convert Pulse formats to SIA” Option 172/272 - bit 2, but will also append a zone number when the pulse event code
starts with a Hex Digit.
Examples – with option 72 bit 2 and 6 enabled (Option 72/172/272 = 44)
1 - Pulse signal received 1234 41
Printer Output 1234-41-BA41
Automation put [#1234|NBA41]
2 – Pulse signal received 1234 B2
Printer Output 1234-B2-OPB2
Automation put [#1234|NOPB2]
2 – Pulse signal received 1234 3C
Printer Output 1234-3C-BA3C
Automation put [#1234|NBA3C]
Value
Codes
SIA
41
42
43
46
48
4F
4D
50
52
54
5C
62
66
68
6D
70
74
7C
A
B
C
F
H
O
M
P
R
T
\
b
f
h
m
p
t
|
BA
BA
CL
FA
HA
OP
MA
PA
BR
TA
OC
BR
FH
HH
MH
PH
TH
UB
Содержание SG-System III
Страница 22: ...Line Card In This Chapter Standby Mode on page 19 Line Fault on page 21...
Страница 92: ...In this Chapter Options 00 47 on page 90 SG DRL3 IP Programming...
Страница 100: ...Printer Words...
Страница 105: ...Telco Connector Pin Outs...
Страница 107: ...DEC HEX BIN Conversion Chart...
Страница 109: ...ASCII Character Chart...
Страница 111: ...SG DRL3 SG DRL3E SG DRL3 2L Communication Formats...
Страница 113: ...Ports...
Страница 115: ...Events Messages...
Страница 124: ...Glossary...