![Sur-Gard SG-System III Скачать руководство пользователя страница 33](http://html1.mh-extra.com/html/sur-gard/sg-system-iii/sg-system-iii_operating-manual_1406547033.webp)
CHAPTER FOUR - PROGRAMMING/OPERATION
30
SG-Sys
tem I Operating Man
ual
4
Option 08: COM1 Data Bits
Default (8)
Determines the number of data bits used to communicate to the Automation Software connected on serial port 1. Choose 7 or 8 to indicate 7,
or 8 data bits.
Option 09: COM1 Parity
Default (0)
Determines the parity of serial port 1.
NOTE: The number of stop bits can not be changed and will always be 2.
NOTE: For changes to this program option a reset of the unit is required before the new parameters are used.
Option 0A: Serial Printer Format
Default (0)
The Serial printer is COM 2 on the receiver. Setting option [0A] to "01" (this will display as CTS pin high in programming mode), will
require the CTS to be set high and print to both HyperTerminal™ and physical serial printer. By setting option [0A] to "02" (this will display
as DCD pin high in programming mode), DCD will need to be set high. This option affects how the COM2 Serial Port is supervised.
To disable the option set to [0].
To enable the printer messages to be outputted to a serial printer and a computer /HyperTerminal via the COM2, set to [1]. (This condition is
for devices that set CTS pin HIGH.
To enable the printer messages to be outputted to a serial printer and a computer/Hyper Terminal via the COM2, set to [2].
(This condition is for devices that set the DCD pin HIGH.)
NOTE: For changes to this program option a reset of the unit is required before the new parameters are used.
Option 0B: Serial Baud Rate
Default (3) - 9600
Determines the baud rate at which the SG-CPM3 will communicate to the serial printer connected on serial port 2.
Valid entries are: 1200, 2400 4800 9600 19200 38400, 57600.
NOTE: For changes to this program option a reset of the unit is required before the new parameters are used.
Option 0C: Serial Data Bits
Default (8)
Determines the number of data bits used to communicate to the serial printer connected on serial port 2. Choose 7 or 8 to indicate 7 or 8 data
bits.
NOTE: For changes to this program option a reset of the unit is required before the new parameters are used.
Numeric Setting
Display
Description
0
None
no parity (default)
1
Odd
odd parity
2
Even
even parity
Содержание SG-System III
Страница 22: ...Line Card In This Chapter Standby Mode on page 19 Line Fault on page 21...
Страница 92: ...In this Chapter Options 00 47 on page 90 SG DRL3 IP Programming...
Страница 100: ...Printer Words...
Страница 105: ...Telco Connector Pin Outs...
Страница 107: ...DEC HEX BIN Conversion Chart...
Страница 109: ...ASCII Character Chart...
Страница 111: ...SG DRL3 SG DRL3E SG DRL3 2L Communication Formats...
Страница 113: ...Ports...
Страница 115: ...Events Messages...
Страница 124: ...Glossary...