Sur-Gard SG-System III Скачать руководство пользователя страница 2

WARNING 

Please Read Carefully

Note to Installers

This warning contains vital information. As the only individual in contact with system users, it is your 

responsibility to bring each item in this warning to the attention of the users of this system.

System Failures

This system has been carefully designed to be as effective as possible. There are circumstances, however, 

involving fire, burglary, or other types of emergencies where it may not provide protection. Any alarm 

system of any type may be compromised deliberately or may fail to operate as expected for a variety of 

reasons. Some but not all of these reasons may be:

 Inadequate Installation

A security system must be installed properly in order to provide adequate protection. Every installation 

should be evaluated by a security professional to ensure that all access points and areas are covered. 

Locks and latches on windows and doors must be secure and operate as intended. Windows, doors, walls, 

ceilings and other building materials must be of sufficient strength and construction to provide the level of 

protection expected. A reevaluation must be done during and after any construction activity. An evalua-

tion by the fire and/or police department is highly recommended if this service is available.

 Criminal Knowledge

This system contains security features which were known to be effective at the time of manufacture. It is 

possible for persons with criminal intent to develop techniques which reduce the effectiveness of these 

features. It is important that a security system be reviewed periodically to ensure that its features remain 

effective and that it be updated or replaced if it is found that it does not provide the protection expected.

 Access by Intruders

Intruders may enter through an unprotected access point, circumvent a sensing device, evade detection by 

moving through an area of insufficient coverage, disconnect a warning device, or interfere with or prevent 

the proper operation of the system.

 Power Failure

Control units, intrusion detectors, smoke detectors and many other security devices require an adequate 

power supply for proper operation. If a device operates from batteries, it is possible for the batteries to 

fail. Even if the batteries have not failed, they must be charged, in good condition and installed correctly. 

If a device operates only by AC power, any interruption, however brief, will render that device inopera-

tive while it does not have power. Power interruptions of any length are often accompanied by voltage 

fluctuations which may damage electronic equipment such as a security system. After a power interrup-

tion has occurred, immediately conduct a complete system test to ensure that the system operates as 

intended.

 Failure of Replaceable Batteries

This system’s wireless transmitters have been designed to provide several years of battery life under nor-

mal conditions. The expected battery life is a function of the device environment, usage and type. Ambi-

ent conditions such as high humidity, high or low temperatures, or large temperature fluctuations may 

reduce the expected battery life. While each transmitting device has a low battery monitor which identi-

fies when the batteries need to be replaced, this monitor may fail to operate as expected. Regular testing 

and maintenance will keep the system in good operating condition.

 Compromise of Radio Frequency (Wireless) Devices

Signals may not reach the receiver under all circumstances which could include metal objects placed on 

or near the radio path or deliberate jamming or other inadvertent radio signal interference.

 System Users

A user may not be able to operate a panic or emergency switch possibly due to permanent or temporary 

physical disability, inability to reach the device in time, or unfamiliarity with the correct operation. It is 

important that all system users be trained in the correct operation of the alarm system and that they know 

how to respond when the system indicates an alarm.

 Smoke Detectors

Smoke detectors that are a part of this system may not properly alert occupants of a fire for a number of 

reasons, some of which follow. The smoke detectors may have been improperly installed or positioned. 

Smoke may not be able to reach the smoke detectors, such as when the fire is in a chimney, walls or roofs, 

or on the other side of closed doors. Smoke detectors may not detect smoke from fires on another level of 

the residence or building.
Every fire is different in the amount of smoke produced and the rate of burning. Smoke detectors cannot 

sense all types of fires equally well. Smoke detectors may not provide timely warning of fires caused by 

carelessness or safety hazards such as smoking in bed, violent explosions, escaping gas, improper storage 

of flammable materials, overloaded electrical circuits, children playing with matches or arson.
Even if the smoke detector operates as intended, there may be circumstances when there is insufficient 

warning to allow all occupants to escape in time to avoid injury or death.

 Motion Detectors

Motion detectors can only detect motion within the designated areas as shown in their respective installa-

tion instructions. They cannot discriminate between intruders and intended occupants. Motion detectors 

do not provide volumetric area protection. They have multiple beams of detection and motion can only be 

detected in unobstructed areas covered by these beams. They cannot detect motion which occurs behind 

walls, ceilings, floor, closed doors, glass partitions, glass doors or windows. Any type of tampering 

whether intentional or unintentional such as masking, painting, or spraying of any material on the lenses, 

mirrors, windows or any other part of the detection system will impair its proper operation.
Passive infrared motion detectors operate by sensing changes in temperature. However their effectiveness 

can be reduced when the ambient temperature rises near or above body temperature or if there are inten-

tional or unintentional sources of heat in or near the detection area. Some of these heat sources could be 

heaters, radiators, stoves, barbeques, fireplaces, sunlight, steam vents, lighting and so on.

 Warning Devices 

Warning devices such as sirens, bells, horns, or strobes may not warn people or waken someone sleeping 

if there is an intervening wall or door. If warning devices are located on a different level of the residence 

or premise, then it is less likely that the occupants will be alerted or awakened. Audible warning devices 

may be interfered with by other noise sources such as stereos, radios, televisions, air conditioners or other 

appliances, or passing traffic. Audible warning devices, however loud, may not be heard by a hearing-

impaired person.

 Telephone Lines

If telephone lines are used to transmit alarms, they may be out of service or busy for certain periods of 

time. Also an intruder may cut the telephone line or defeat its operation by more sophisticated means 

which may be difficult to detect.

 Insufficient Time

There may be circumstances when the system will operate as intended, yet the occupants will not be pro-

tected from the emergency due to their inability to respond to the warnings in a timely manner. If the sys-

tem is monitored, the response may not occur in time to protect the occupants or their belongings.

 Component Failure

Although every effort has been made to make this system as reliable as possible, the system may fail to 

function as intended due to the failure of a component.

 Inadequate Testing

Most problems that would prevent an alarm system from operating as intended can be found by regular 

testing and maintenance. The complete system should be tested weekly and immediately after a break-in, 

an attempted break-in, a fire, a storm, an earthquake, an accident, or any kind of construction activity 

inside or outside the premises. The testing should include all sensing devices, keypads, consoles, alarm 

indicating devices and any other operational devices that are part of the system.

 Security and Insurance

Regardless of its capabilities, an alarm system is not a substitute for property or life insurance. An alarm 

system also is not a substitute for property owners, renters, or other occupants to act prudently to prevent 

or minimize the harmful effects of an emergency situation.

Limited Warranty

Digital Security Controls warrants the original purchaser that for a period of twelve months from the date 
of purchase, the product shall be free of defects in materials and workmanship under normal use. During 
the warranty period, Digital Security Controls shall, at its option, repair or replace any defective product 
upon return of the product to its factory, at no charge for labour and materials. Any replacement and/or 
repaired parts are warranted for the remainder of the original warranty or ninety (90) days, whichever is 
longer. The original purchaser must promptly notify Digital Security Controls in writing that there is 
defect in material or workmanship, such written notice to be received in all events prior to expiration of 
the warranty period. There is absolutely no warranty on software and all software products are sold as a 
user license under the terms of the software license agreement included with the product. The Customer 
assumes all responsibility for the proper selection, installation, operation and maintenance of any prod-
ucts purchased from DSC. Custom products are only warranted to the extent that they do not function 
upon delivery. In such cases, DSC can replace or credit at its option.

International Warranty

The warranty for international customers is the same as for any customer within Canada and the United 
States, with the exception that Digital Security Controls shall not be responsible for any customs fees, 
taxes, or VAT that may be due.

Warranty Procedure

To obtain service under this warranty, please return the item(s) in question to the point of purchase. All 
authorized distributors and dealers have a warranty program. Anyone returning goods to Digital Security 
Controls must first obtain an authorization number. Digital Security Controls will not accept any shipment 
whatsoever for which prior authorization has not been obtained.

Conditions to Void Warranty

This warranty applies only to defects in parts and workmanship relating to normal use. It does not cover:

• damage incurred in shipping or handling;

• damage caused by disaster such as fire, flood, wind, earthquake or lightning;

• damage due to causes beyond the control of Digital Security Controls such as excessive voltage, 

mechanical shock or water damage;

• damage caused by unauthorized attachment, alterations, modifications or foreign objects;

• damage caused by peripherals (unless such peripherals were supplied by Digital Security Controls);

• defects caused by failure to provide a suitable installation environment for the products;

• damage caused by use of the products for purposes other than those for which it was designed;

• damage from improper maintenance;

• damage arising out of any other abuse, mishandling or improper application of the products.

Items Not Covered by Warranty

In addition to the items which void the Warranty, the following items shall not be covered by Warranty: (i) 
freight cost to the repair centre; (ii) products which are not identified with DSC's product label and lot 
number or serial number; (iii) products disassembled or repaired in such a manner as to adversely affect 
performance or prevent adequate inspection or testing to verify any warranty claim. Access cards or tags 
returned for replacement under warranty will be credited or replaced at DSC's option. Products not cov-
ered by this warranty, or otherwise out of warranty due to age, misuse, or damage shall be evaluated, and 
a repair estimate shall be provided. No repair work will be performed until a valid purchase order is 
received from the Customer and a Return Merchandise Authorisation number (RMA) is issued by DSC's 
Customer Service.

Digital Security Controls’s liability for failure to repair the product under this warranty after a reasonable 
number of attempts will be limited to a replacement of the product, as the exclusive remedy for breach of 
warranty. Under no circumstances shall Digital Security Controls be liable for any special, incidental, or 
consequential damages based upon breach of warranty, breach of contract, negligence, strict liability, or 
any other legal theory. Such damages include, but are not limited to, loss of profits, loss of the product or 
any associated equipment, cost of capital, cost of substitute or replacement equipment, facilities or ser-
vices, down time, purchaser’s time, the claims of third parties, including customers, and injury to prop-
erty. The laws of some jurisdictions limit or do not allow the disclaimer of consequential damages. If the 
laws of such a jurisdiction apply to any claim by or against DSC, the limitations and disclaimers con-
tained here shall be to the greatest extent permitted by law. Some states do not allow the exclusion or lim-
itation of incidental or consequential damages, so that the above may not apply to you.

Disclaimer of Warranties

This warranty contains the entire warranty and shall be in lieu of any and all other warranties, 
whether expressed or implied (including all implied warranties of merchantability or fitness for a par-
ticular purpose) And of all other obligations or liabilities on the part of Digital Security Controls Digi-
tal Security Controls neither assumes responsibility for, nor authorizes any other person purporting to 
act on its behalf to modify or to change this warranty, nor to assume for it any other warranty or liabil-
ity concerning this product.

This disclaimer of warranties and limited warranty are governed by the laws of the province of Ontario, 
Canada.

WARNING: Digital Security Controls recommends that the entire system be completely tested on a 
regular basis. However, despite frequent testing, and due to, but not limited to, criminal tampering 
or electrical disruption, it is possible for this product to fail to perform as expected.

Installer ’s Lockout

Any products returned to DSC which have the Installer’s Lockout option enabled and exhibit no other 
problems will be subject to a service charge.

Out of Warranty Repairs

Digital Security Controls will at its option repair or replace out-of-warranty products which are returned 
to its factory according to the following conditions. Anyone returning goods to Digital Security Controls 
must first obtain an authorization number. Digital Security Controls will not accept any shipment whatso-
ever for which prior authorization has not been obtained.

Products which Digital Security Controls determines to be repairable will be repaired and returned. A set 
fee which Digital Security Controls has predetermined and which may be revised from time to time, will 
be charged for each unit repaired.

Products which Digital Security Controls determines not to be repairable will be replaced by the nearest 
equivalent product available at that time. The current market price of the replacement product will be 
charged for each replacement unit.

Содержание SG-System III

Страница 1: ...l contains information regarding product use and function in addition to manufacturer liability and restrictions pertaining to it The entire manual should be read carefully version 2 0 SG System III O...

Страница 2: ...e to the failure of a component Inadequate Testing Most problems that would prevent an alarm system from operating as intended can be found by regular testing and maintenance The complete system shoul...

Страница 3: ...21 4 Programming Operation 25 Introduction on page 26 Console Software on page 26 Debug on page 26 Manual Programming on page 27 SG CPM3 Options on page 28 5 Advanced Programming 43 SG DRL3 2L DRL3E S...

Страница 4: ...es shall be protected and routed so that they do not come in contact with burrs cooling fan or heatsinks which could cause damage to the insulation of conductors Holes in metal shall have smooth well...

Страница 5: ...In This Chapter In This Chapter System Overview on page 2 Approvals on page 3 Description Hardware on page 5 Receiver Setup and Operation on page 12 Description Operation on page 12 Introduction...

Страница 6: ...ownload for software upgrades for all supported line cards and the SG CPM3 DSP technology patent pending Up to 64 different options set profiles per line card Up to 8 different handshakes per profile...

Страница 7: ...ar Alarm Control Units CAN ULC S559 04 Equipment for Fire Signal Receiving Centres and Systems FM approved EN60950 1 2006 Standard for Information Technology Equipment AS NZS 60950 1 2003 Information...

Страница 8: ...AC Mask UPS 1 Bat Mask UPS 2 AC Mask UPS 2 Bat Mask SG TCP 1 Mask SG Serial 1 Mask SG TCP 2 Mask SG Serial 2 Mask TCP Printer 1 Mask Parallel 1 Mask SG Serial 1 Mask TCP Printer 2 Mask Parallel 2 Mas...

Страница 9: ...for a second SG DC DC3 voltage con verter In the event of a failure the redundant SG DC DC3 can be removed replaced without powering down the unit SG PSC3 Power Supply Controller monitors the states...

Страница 10: ...information and directs line card information to the appropriate outputs Along with its built in scroll buttons and large LCD message screen the SG CPM3 features TCP IP parallel printer and two serial...

Страница 11: ...ed transmitters periodically This allows the receiver to determine whether the transmitters are still online The receiver maintains a table of all installed transmitters and monitors their status pres...

Страница 12: ...t to a receptacle controlled by a switch Notes 1 All external devices should be mounted in the same room as the receiver 2 All circuits are power limited except AC input 3 Maintain 6 5 mm 1 4 separati...

Страница 13: ...ct Pack Failure to do so may result in damage to the unit Using the provided RJ 45 patch cables connect the Output of the primary SG System III shelf address 1 to the Input of the secondary System III...

Страница 14: ...ons the equipment shall be rack mounted and energized by a permanently wired supply in accordance with C22 1 Canadian Electri cal Code Part 1 Safety Standard for Electrical Installations section 32 Co...

Страница 15: ...rial Automation Serial Printer TCP Connection DRL3 IP Network Connection Serial Automation Serial Printer TCP Connection DRL3 IP Network Connection Power Cord Refer to the Note Power Cord Refer to the...

Страница 16: ...t will have its red LED off If the LED is on make sure the telephone line is connected to the correct port 8 Press the ACK button until all of the initial signals have been acknowledged ACK button has...

Страница 17: ...Data Byte Protocol The SG System III receiver uses a default configuration of 9600 Baud rate 1 start bit 8 data bits 0 parity bits and 2 stop bits structure to transmit and receive signals on the RS 2...

Страница 18: ...utomation 30 seconds is recommended If a heartbeat fails to get a response from the computer automation the SG CPM3 will immediately transmit the heartbeat again up to 4 attempts The SG System III by...

Страница 19: ...perating Modes In This Chapter Contrast Adjust on page 16 Active Mode on page 16 Manual Mode on page 16 Standby Mode on page 17 System Trouble and System Information on page 17 AHS Table Management on...

Страница 20: ...ter IP 30 0 25 26 User Define LCD Message Line 1 User Define LCD Message Line 1 User Define LCD Message Line 2 User Define LCD Message Line 2 IP 30 0 21 112 IP 30 0 21 112 Nov 29 2010 08 18 04 Nov 29...

Страница 21: ...llow the user to access the System Information menu To return to the main screen press the UP and DN buttons simultaneously or wait for it to timeout before this is available AHS Table Management New...

Страница 22: ...Line Card In This Chapter Standby Mode on page 19 Line Fault on page 21...

Страница 23: ...ne line and the SG CPM3 Depending on the system s status the following conditions will be displayed for each line card LED ON OFF FLASHING LINE Red Line Fault Line Normal N A STATUS Yellow On line Off...

Страница 24: ...2 per table above The number of flashes on the yellow LED indicates the following errors Flashes Error 1 CPM Absent 2 Line card clock not set 3 EBUS command to disable the line card was sent 4 Printer...

Страница 25: ...egin flashing When the SG CPM3 Error condition is corrected the alarm messages in the event buffer will be transmitted to the SG CPM3 with the corresponding time date the alarm has been received SG DR...

Страница 26: ...nt code AAAAAA indicates that data has been received but is not valid e g The packet is encrypted and the SG DRL3 IP does not have the proper key or the T LINK transmitter packet was rejected NAK four...

Страница 27: ...e local authorities type NID Network Interface Device before leaving the premises e g UL installations UL60950 Listed NID Supervised Receiver Database The receiver has the capability of monitoring IP...

Страница 28: ...In This Chapter Introduction on page 26 Console Software on page 26 Debug on page 26 Manual Programming on page 27 SG CPM3 Options on page 28 Programming Operation...

Страница 29: ...DRL3 2L Profiles 1 63 cannot be set through debug DRL3 If the line card reboots changes made with set option through debug are lost To make changes per manent use the Write option ALL PROGRAMMING WIT...

Страница 30: ...nter Channel 2 is on available on DRL3 2L line cards 5 Enter 03 and press enter If debug output is needed from 2 channels repeat steps 3 5 for the other channel Manual Programming The user interface c...

Страница 31: ...can also be done from the SG Systems Console software System Information Lists information such as CPM3 version product ID and MAC address Cold Boot Line Card A cold boot will set the line card back t...

Страница 32: ...ssibility that the SG CPM3 will not remain synchronized with the automa tion PC Printer message Time Date Update Fail Automation message 0RRLLL 0000 NRU0000 NOTE Confirm that the automation software p...

Страница 33: ...0 To enable the printer messages to be outputted to a serial printer and a computer HyperTerminal via the COM2 set to 1 This condition is for devices that set CTS pin HIGH To enable the printer messa...

Страница 34: ...able to communicate to each other then the synchronization of the new entries will fail A text message shall be outputted to the printer when AHS synchronization starts stops or fails A text message...

Страница 35: ...ough 99 to determine the time interval between heartbeat transmis sions Enter the value 00 to disable heartbeat transmission NOTE When 00 is used heartbeats will not be sent to automation software thi...

Страница 36: ...allations may not have the full configuration This mask option is used to enable or disable the supervision of the right hand SG DC DC3 for shelf 1 To disable reporting of the trouble turn the appropr...

Страница 37: ...fault 01 on Some installations may not have the full configuration This mask option is used to enable or disable the supervision Fan trouble for shelf 2 To disable reporting of the trouble turn the ap...

Страница 38: ...cts the permitted setting is 00 Option 26 Mask SG TCP 2 Default 00 off SG TCP trouble mask for shelf 2 If set SG TCP trouble conditions are not reported OFF Condition reported ON Condition not reporte...

Страница 39: ...sk for shelf 2 If set SG TCP Printer trouble conditions are not reported OFF Condition reported ON Condition not reported masked For UL Listed products the permitted setting is 00 Option 2C Mask Paral...

Страница 40: ...llback The TCP IP connection is the primary output of the automation computer alarms It is estimated that sockets may appear and disappear reg ularly as processes are terminated and reconstituted Afte...

Страница 41: ...e serial output on the primary shelf If that fails the CPM will reboot and send to the serial output on the secondary shelf It will continue to send to the serial connection without stop or until the...

Страница 42: ...onsole Reset Fallback Manual Re start from Console Reset Fallback CHAPTER FOUR PROGRAMMING OPERATION 39 SG System I Operating Manual 4 Flow Diagram for Automation Fallback Mode 1 Power Up Restart TCP...

Страница 43: ...The printer outputs can be configured in a similar approach as the automation outputs except that only acceptable values are LOOP 01 or ALL 02 ALL is transmitting the printer message to all active po...

Страница 44: ...n PC However in some situations it may be desirable to automatically correct the time of the SG System III The SG System III will update its time once an hour Valid values are 590 to 590 value represe...

Страница 45: ...baud rate setting Any cards that do not have the correct setting will not be seen by the CPM3 and signals received by that line card will not be outputted Line Card compatible baud rates NOTE Line car...

Страница 46: ...In this Chapter SG DRL3 2L DRL3E System Options on page 46 SG DRL3 SG DRL3 2L Static Options on page 48 SG DRL3 SG DRl3 2L Dynamic Options on page 59 Advanced Programming...

Страница 47: ...user operator to edit the profiles NOTE DNIS Dialled Number Identification Service This number represents the dialled number or the num ber being called ANI Automatic Number Identification This number...

Страница 48: ...ceiver itself devoted to certain customers the SG System III can handle any format at any time through the use of profiles Each line card holds its own look up table that can be shared through line po...

Страница 49: ...re used Programming menu display will be C1 C2 All other values are not valid For channels that are disabled no information shall be displayed and no status troubles will be generated any trouble cond...

Страница 50: ...not busy out and have a loss of time present The status will still be displayed on the status LED but the system will not busy out If the option is programmed to 01 the line card will NOT buffer any n...

Страница 51: ...o the output 03Send 3 hex digit line card number to the output leading Zeros will be inserted prior to the line card number 0ASend 3 digit line card number as entered no conversion 0DSend 3 digit line...

Страница 52: ...105 205 then send the first handshake The value pro grammed hex at this location will be multiplied by 100ms e g 100ms 200ms The SG DRL3 default is 0A for 1000ms 100ms x default value The minimum tim...

Страница 53: ...Type 2 7D 4 3 with Checksum Sur Gard 80 Bellcore Caller Name 1D 4 1 Partial Extended Pulse 52 4 1 Varitech 85 DMP Serial 1 21 3 16 1 Scantronics Super Fast 2A 4 2 Varitech 86 DMP Serial 3 22 4 16 1 S...

Страница 54: ...ons SG DRL3 2L Option 10D 20D Line Conditions Default 000 Line Conditions is a bit enabled option If programmed as 00 the line card will detect a single ring If bit 1 is programmed the line card will...

Страница 55: ...es The line fault and line restoral messages for the auxiliary line are as indicated below The computer message for a line fault and line restoral on the auxiliary line are the same as the primary lin...

Страница 56: ...ceived instead of the originating telephone number Unknown Call The originating telephone number has not been received or was not transmitted SG DRL3 Option 13 Caller Source to SG Automation SG DRL3 2...

Страница 57: ...s full after loss of communication with the SG CPM3 Program Option 1C 11C 21C with one of the following NOTE The status condition will be indicated on the LED even though the unit does not busy out th...

Страница 58: ...from this debug option if the debug task for the selected debug menu is enabled This can be done via the serial debug from the console software application Reason LED Status Flashes System absent 1 On...

Страница 59: ...04 08 33 32 01 01 SG 99 802 1234 Alarm Zone SG DRL3 Option 25 Phone Line Voltage Select SG DRL3 2L Option 125 225 Phone Line Voltage Select Default 00 for approx 20V To calculate the proper setting us...

Страница 60: ...on is 5 seconds When the Dialer Presence tone option is enabled the Pre handshake delay option 05 105 205 is not functional This timing is in order to syn chronize the handshakes sent by the receiver...

Страница 61: ...uld be left at the Greenwich Mean Time 24 setting An option setting of 00 is disabled All settings above 24 must act as a disabled state 00 When the DMP panel calls in and requests a time update the r...

Страница 62: ...ons 30 3F 3 1 4 1 Digit 0 F SG DRL3 2L Options 130 230 13F 23F 3 1 4 1 Digit 0 F The line card uses a unique Sur Gard communication format to transmit data through the System to the central station co...

Страница 63: ...e Decoding Library Do NOT use values other than 20 7F ASCII SG DRL3 Options 50 5F 4 3 Digit 0 F SG DRL3 2L Options 150 250 15F 25F 4 3 Digit 0 F Defaults The line card will use the fifth digit of data...

Страница 64: ...on software packages are unable to process an alarm using the event codes listed in the Decoding Library Where a central station monitors thousands of accounts belonging to different companies the sam...

Страница 65: ...lse to SIA and Convert BFSK to SIA set Option72 0C Bit 0 Force SIA Zone Number The receiver will decode SIA Alarms sent without Zone numbers and add 00 as the zone number to the automation output Exam...

Страница 66: ...or not will be NACK d In order to disable the SIA recovery option disable this bit option default setting By disabling the SIA recovery the receiver will send Acknowledgement signals for the blocks t...

Страница 67: ...output level of the handshake kiss off Refer to the chart below for ranges For the first digit 0 is the most sensitive and 5 is the least sensitive For the second digit B is the loudest and 9 is the q...

Страница 68: ...ted in SIA two leading 0 zeros will be communicated in front of the 3 digit account EX S1011 00AAA Nri0 FH00 05 If the alarm is reported in 3 1 3 1 extended 3 2 BFSK SIA 3 8 ACRON formats then a leadi...

Страница 69: ...possible solution by programming this option This option should be left as a default and should be changed only on the recommendation of a Sur Gard technician When pro grammed as 00 the inter digit t...

Страница 70: ...which 3 digit account codes will be able to activate the 2 way audio feature Program the first digits of the desired account codes in Option 7B 17B 27B For example To allow all 3 digit account codes...

Страница 71: ...omation output Option 7A 17A 27A Option 7C 17C 27C Switch Reason or 7B 17B 27B to Audio 00 1 1 2 3 00 1 2 3 5 1 4 1 2 00 00 3 4 3 4 1 3 1 5 Yes Yes No No No No Yes Alarm code 2 falls within the code r...

Страница 72: ...ormats bit position will disable audio for the format For example if the user wants audio to work only for 3 digit pulse and SIA formats Option 17F 27F would have to be programmed as 11 hex which enab...

Страница 73: ...Handshake Selection SG DRL3 2L Options 181 281 through 188 288 Handshake Selection Defaults The channel is a multi format receiver capable of sending several handshakes to a dialer panel Often it is...

Страница 74: ...automation libraries 2D Double dual tone handshake1400 Hz 100ms 100ms pause and 2300 Hz 100ms tone with a kiss off of 1400 Hz 8D Single tone DTMF handshake Kiss off EC SURTEC handshake FB CFSK Full d...

Страница 75: ...n 8E 18E 28E Handshake 6 duration Option 8F 18F 28F Handshake 7 duration Option 90 190 290 Handshake 8 duration SG DRL3 Option 91 Inter Handshake Duration SG DRL3 2L Option 191 291 Inter Handshake Dur...

Страница 76: ...ulse extended extended formats 104091sssssss245sXssYZ If Option 94 is set to 02 than the leading digit of any account code greater than four digits will be stripped if it is a zero This option will wo...

Страница 77: ...checksum cannot be distin guished because all of them contain a total of 5 digits 4 2 and 5 1 cannot be distinguished because all of them contain a total of 6 digits NOTE The printer messages for the...

Страница 78: ...4 3 output for reporting to the computer and the printer Pro gram one of the following Example 1 1234 05 1234 05 0505 16 0505 16 The receiver will interpret this information as 1234 516 Example 2 1234...

Страница 79: ...Fast and Ademco 4 1 Express set Option 99 199 299 to 22 SG DRL3 Option 9A Error Counter SG DRL3 2L Option 19A 29A Error Counter Default 00 When this option is set it will configure the number of cons...

Страница 80: ...may be enabled The default is 0x01 meaning output with 6RRLLL protocol Do not convert to SIA do not process Modem II text blocks and only decode the first 4 digits of Modem II account codes NOTE The l...

Страница 81: ...AA YY Alarm When this option is programmed as 01 the Scantronics formats will not be decoded and the received data is passed to the outputs automation 8RRLLLAAAAAAsCCCCsCCCCsC DC4 9 digit channels 8RR...

Страница 82: ...232 Default 00 This option is used to strip hex digits on the automation output The line card will emulate the Radionics 6500 RS 232 protocol on pulse for mats Ademco Express and Varitech only When Op...

Страница 83: ...on Examples 00 BFSK format will be reported as Radionics 6500 The protocol identi fier will be a 6 Example 1 Code 21 Computer Output 604091 055sAsss2 Example 2 Code B1 Computer Output 604091 055sOsss1...

Страница 84: ...or 2 way Audio Transfer Default 00 These 8 options are used to provide the dial out number if the user wishes to transfer the call to another extension Up to 16 digits may be programmed including any...

Страница 85: ...s SG DRL3 2L Option 1B0 2B0 CCITT Audio Format Enable bits Default 00 This option is similar to option 7F 17F 27F It gives you the ability to enable and disable audio for the selected CCITT formats A...

Страница 86: ...Close USR 04 AREA2 TIMAREA 2 DECIMAL setting Automation P01001 20999 L0401TIMAREA 1 P01001 20999 L0402TIMAREA 2 Printer 00 01 001 20999 Close USR 04 AREA1 TIMAREA 1 00 01 001 20999 Close USR 04 AREA2...

Страница 87: ...rs B0 BF and C0 CF will be translated to Ademco High Speed Whenever a 4 2 code beginning with B is received an opening report is sent and whenever a 4 2 code beginning with a C is received a closing r...

Страница 88: ...BF 101001 1234 F222 2222 2 01 001 1234 F222 2222 2 1234 C1 101001 1234 1444 4444 4 01 001 1234 1444 4444 4 1234 C2 101001 1234 2444 4444 4 01 001 1234 2444 4444 4 1234 C3 101001 1234 3444 4444 4 01 00...

Страница 89: ...il log will be made Fax tone detection This will occur in the common mode detection for formats In this check the line card is looking for the 1170 ON report from the DSP Once in this check the line s...

Страница 90: ...L3 Option BB Sur Gard DTMF 4 3 Format Output SG DRL3 2L Option 1BB 2BB Sur Gard DTMF 4 3 Format Output Default 00 Each digit of this option controls how the 4 3 format computer output string is format...

Страница 91: ...r codes without conversion X1 Convert the last 2 digit user codes to decimal as shown here User Code Received 00 to 99 B0 to B9 C0 to C9 D0 to D9 E0 to E9 F0 to F9 User Code after Conversion 00 to 99...

Страница 92: ...In this Chapter Options 00 47 on page 90 SG DRL3 IP Programming...

Страница 93: ...in hexadecimal Options 09 0C Receiver Gateway Default 00 00 00 00 This represents 000 000 000 000 This is the address of the Gateway through which the SG DRL3 IP must communicate to reach the transmit...

Страница 94: ...option shall be programmed as B4 180s For UL Commercial Burg Installations standard encrypted line security this option shall be programmed as C8 200s For UL Commercial Fire installations single comm...

Страница 95: ...nsmitter Swap Trouble Mask Default 00 This programmable mask enables or disables the reporting of the T LINK transmitter swap condition on the SG DRL3 IP receiver Setting the mask to 0 signifies the t...

Страница 96: ...ble will not be reported NOTE For UL Listed products the permitted setting is 00 Option 1F Accounts Exceeded Trouble Mask Default 00 This programmable mask enables or disables the reporting if the ac...

Страница 97: ...e in section 3A and low byte in section 3B If this option is changed the console connected to the SG DRL3 IP must be programmed with the new port number 00 No time set from SG CPM3 a code corruption c...

Страница 98: ...er When set to 01 the SG DRL3 IP will output the DNIS received from a GS transmitter instead of the RRLLL Option 46 Account Digit Stripping Default 00 The option controls the output of the account num...

Страница 99: ...h the receiver will need to support the s protocol via the Sur Gard output format in order for this feature to work Available settings for SIM Number output 00 Disabled No SIM Number output 01 SIM Num...

Страница 100: ...Printer Words...

Страница 101: ...GENERAL ALARM 0A FIRE ALARM 29 POLLING LOOP OPEN 0B SMOKE 2A POLLING LOOP SHORT 0C COMBUSTION 2B EXPANSION MODULE FAILURE 0D WATER FLOW 2C SENSOR TAMPER 0E HEAT 2D EXPANSION MODULE TAMPER 0F PULL STA...

Страница 102: ...P ACTIVATED 6B NOTIFICATION APPLIANCE 4 CHECK 4C PUMP FAILURE 6C RESERVED 4D RESERVED 6D RESERVED 4E RESERVED 6E SYSTEM PERIPHERAL 4F RESERVED 6F POLLING LOOP OPEN 50 SYSTEM TROUBLE 70 POLLING LOOP SH...

Страница 103: ...9 KEYSWITCH O C 8A RESERVED AA RESERVED 8B RESERVED AB CALLBACK REQUEST MADE 8C PROTECTION LOOP AC SUCCESSFUL DOWNLOAD ACCESS 8D PROTECTION LOOP OPEN AD UNSUCCESSFUL ACCESS 8E PROTECTION LOOP SHORT AE...

Страница 104: ...AUTO ARM FAIL EE RESERVED CE O C PARTIAL ARMED EF UNBYPASS CF EXIT ERROR F0 RESERVED D0 USER PRESENT F1 MANUAL TRIGGER TEST D1 RECENT CLOSE F2 PERIODIC TEST REPORT D2 SOUNDER RELAY DISABLED F3 PERIODI...

Страница 105: ...Telco Connector Pin Outs...

Страница 106: ...Ring Channel 3 A Tip Ring Channel 4 B Tip Ring Channel 4 9 10 11 12 13 14 15 16 34 35 36 37 38 39 40 41 A Tip Ring Channel 5 B Tip Ring Channel 5 A Tip Ring Channel 6 B Tip Ring Channel 6 A Tip Ring...

Страница 107: ...DEC HEX BIN Conversion Chart...

Страница 108: ...11 0000 1100 0000 1101 0000 1110 0000 1111 0001 0000 0001 0001 0001 0010 0001 0011 0001 0100 0001 0101 0001 0110 0001 0111 0001 1000 0001 1001 0001 1010 027 028 029 030 031 032 033 034 035 036 037 038...

Страница 109: ...ASCII Character Chart...

Страница 110: ...ding ASCII on printer Options 70 170 270 Hex Character Code Character Code Character 20 30 31 32 33 34 35 36 37 38 39 41 42 43 44 45 46 47 48 Space 0 1 2 3 4 5 6 7 8 9 A B C D E F G H 49 4A 4B 4C 4D 4...

Страница 111: ...SG DRL3 SG DRL3E SG DRL3 2L Communication Formats...

Страница 112: ...ed 2300Hz 1800Hz 40bps 4 3 Checksum ID O C 2300Hz SIA FSK Level 1 2 and 3 SIA FSK 110bps 300bps tonal data ACK Silent Knight Fast 1400Hz 1900Hz 14bps 3 1 4 1 or 3 2 4 2 NO 1400Hz Silent Knight Fast 14...

Страница 113: ...Ports...

Страница 114: ...port Figure 10 Printer Port RS 232 Serial Automation The serial automation port is used to send automation signals to the automation computer using the Sur Gard Automation pro tocol Only the serial po...

Страница 115: ...Events Messages...

Страница 116: ...SS is slot SG 01 001 0000 DSP FAULT DRL Online Timeout Timer Expires 001001 0000 NYSssSS Where ss is shelf and SS is slot SG 01 001 0000 DRL ON LINE TIMEOUT Audio Initiated S01001 1234 NLFssSS Where...

Страница 117: ...ble IP IP IP IP Remote shutdown has been sent to the transmitter Where XXXXXXXXXX is the account code of the transmitter IP IP IP IP is the current IP address of the transmitter 000001 0000000001 NYX0...

Страница 118: ...x Possible Compromise Attempt 001001 XXXXXXXXXX NPC IP IP IP IP where IP is transmitters IP and X is the trans mitters account SG 01 001 XXXXXXXXXX PC Possible Compromise Attempt COLDBOOT was performe...

Страница 119: ...FAX Call failed due to detection of Noise on the call chan nel 1 001001 0000 NYC0101 NOISE SG 01 001 0000 COMMUNICATION FAIL NOISE Communication Fail Due to No Response from the panel CH2 001129 0000...

Страница 120: ...LC Firmware Update Failed GET DNIS Table No Automation message SG 01 002 0000 GET DNIS Table SET DNIS Table No Automation message SG 01 002 0000 SET DNIS Table Line Card Default By Console No Automati...

Страница 121: ...000 0000 NVZ0100 SG 01 000 0000 NVZ0100 TCP IP 1 Printer Failed TCP IP Shelf 1 Printer Restoral 001000 0000 NVY0100 SG 01 000 0000 NVY0100 TCP IP 1 Printer Restored TCP IP Shelf 2 Printer Failure 0010...

Страница 122: ...0 0000 NAT0002 SG 01 000 0000 NAT0002 PSC 1 Failed Shelf 1 PSC Restoral 001000 0000 NAR0002 SG 01 000 0000 NAR0002 PSC 1 Restored Shelf 2 PSC Failure 001000 0000 NAT0003 SG 01 000 0000 NAT0003 PSC 2 F...

Страница 123: ...0000 RESET by CONSOLE Invalid Password to Enter LCD Program 001000 0000 NLX0000 SG 01 000 0000 NLX0000 User 0 Local Programming Denied Local Programming Begin via LCD 001000 0000 NLB0000 SG 01 000 00...

Страница 124: ...Glossary...

Страница 125: ...software package and PC which connects to the receiver to receive alarm events The automation can be connected either by direct serial connection or TCP Automation Message The alarm information deliv...

Страница 126: ...ceiver Event The specific type of alarm being reported by the panel Event Code A term used to describe a character or group of characters in an automation output This character s is used to represent...

Страница 127: ...ed by the IEEE any OEM company which manufactures Ethernet devices must apply for and purchase an OUI Organizationally Unique Identifier which consists of a block of 16 777 216 MAC addresses all of wh...

Страница 128: ...controlled via an option in both the line card and the SG CPM3 RS 232 An asynchronous point to point serial communications protocol Used to communicate between the SG DRL3 and a PC for the SG DRL3 s d...

Страница 129: ...ttons used for the user interface This board also connects directly to the LCD screen SIA Security Industry Association Sometimes referred to as the SIA format which is an example of FSK modu lation T...

Страница 130: ...grees to the terms of this EULA If the SOFTWARE PRODUCT is an upgrade any transfer must also include all prior versions of the SOFTWARE PRODUCT f Termination Without prejudice to any other rights DSC...

Страница 131: ...public service commission or corporation commission for information Alarm dialing equipment must be able to seize the telephone line and place a call in an emer gency situation It must be able to do t...

Отзывы: